ell-v?

Cooper-NEW-RECOVERY.XLS - NUREGCR-5496 r

~1~

ICooper OP Recovery Table B-8 IE Frequency Table B-4 1 crit-yr =

8760 cnt-hr 1 shutdown-yr =

8760 SD-hr Offsite Power Recovery Data (industry) I

_IE Frequency Data (Cooper)

Feq (for Plant-Severe-LOOP Freq (for full shutdown Lognormal Centered Grid-Related Weather Category power ops.) ops.)

median (hr.) =

0.49 3.08 5.68 PC 4.57E-06 9.34E-02 EF=

10.6 2.14 14.7 GR 1.63E-07 1.43E-03 mu =

-0.71 1.13 1.74 SW 5.94E-07 5.20E-03 sigma=

1.44 0.46 1.63 Total 5.32E-06 1.14E-05 Frequency Plant-Severe-weighted Diesel all AC Time Centered Grid-Related Weather average Generators Power 0

1.000 1.000 1.000 1.000 1.000 1.000 0.5 0.496 1.000 0.932 0.560 0.917 0.514 1

0.311 0.993 0.856 0.393 0.841 0.330 1.5 0.219 0.940 0.793 0.305 0.771 0.235 2

0.165 0.825 0.739 0.249 0.707 0.176 2.5 0.129 0.675 0.692 0.209 0.648 0.135 3

0.104 0.524 0.652 0.178 0.595 0.106 3.5 0.086 0.392 0.617 0.155 0.545 0.084 4

0.072 0.287 0.585 0.136 0.500 0.068 4.5 0.062 0.207 0.557 0.121 0.459 0.056 5

0.053 0.148 0.531 0.109 0.420 0.046 5.5 0.046 0.105 0.508 0.100 0.386 0.038 6

0.041 0.075 0.487 0.092 0.354 0.032 6.5 0.036 0.053 0.467 0.085 0.324 0.027 7

0.032 0.038 0.449 0.079 0.297 0.023 7.5 0.029 0.027 0.433 0.074 0.273 0.020 8

0.026 0.020 0.417 0.070 0.250 0.017 8.5 0.024 0.014 0.403 0.066 0.229 0.015 9

0.022 0.010 0.389 0.062 0.210 0.013 9.5 0.020 0.007 0.377 0.059 0.193 0.011 10 0.018 0.005 0.365 0.056 0.177 0.010 10.5 0.017 0.004 0.354 0.054 0.162 0.009 11 0.015 0.003 0.343 0.051 0.149 0.008 11.5 0.014 0.002 0.333 0.049 0.136 0.007 12 0.013 0.002 0.324 0.047 0.125 0.006 12.5 0.012 1.2E-03 0.315 0.046 0.115 0.005 13 0.011 9.3E-04 0.306 0.044 0.105 4.6E-03 13.5 0.011 7.0E-04 0.298 0.042 0.096 4.1 E-03 14 0.010 5.3E-04 0.291 0.041 0.088 3.6E-03 14.5 0.009 4.1 E-04 0.283 0.040 0.081 3.2E-03 15 0.009 3.1E-04 0.276 0.038 0.074 2.8E-03 15.5 0.008 2.4E-04 0.270 0.037 0.068 2.5E-03 16 0.008 1.9E-04 0.263 0.036 0.063 2.2E-03 16.5 0.007 1.4E-04 0.257 0.035 0.057 2.0E-03 17 0.007 1.1 E-04 0.251 0.034 0.053 1.8E-03 17.5 6.4E-03 8.7E-05 0.246 0.033 0.048 1.6E-03 18 6.1 E-03 6.8E-05 0.240 0.032 0.044 1.4E-03 18.5 5.8E-03 5.4E-05 0.235 0.031 0.041 1.3E-03 19 5.5E-03 4.2E-05 0.230 0.030 0.037 1.1 E-03 19.5 5.2E-03 3.3E-05 0.225 0.030 0.034 1.0E-03 20 4.9E-03 2.6E-05 0.221 1

0.029 0.031 9.OE-04 20.5 4.7E-03 2.1E-05 0.216 1

0.028 0.029 8.1E-04 21 4.5E-03 1.7E-05 0.212 0.027 0.026 7.2E-04 21.5 4.3E-03 1.3E-05 0.208 0.027 0.024 6.5E-04 22 4.1 E-03 1.1E-05 0.204 0.026 0.022 5.8E-04 22.5 3.9E-03 8.6E-06 0.200 0.026 0.020 5.22-04 K-12

Cooper-NEW-RECOVERY.XLS - NUREGCR-5496 Frequency Plant-Severe-weighted Diesel all AC Time Centered Grid-Related Weather average Generators Power 23 3.7E-03 7.0E-06 0.196 0.025 0.019 4.7E-04 23.5 3.6E-03 5.6E-06 0.192 0.025 0.017 4.2E-04 24 3.4E-03 4.6E-06 0.189 0.024 0.016 3.7E-04 24.5 3.3E-03 3.7E-06 0.186 0.023 0.014 3.4E-04 25 3.1 E-03 3.OE-06 0.182 0.023 0.013 3.0E-04 25.5 3.02-03 2.5E-06 0.179 0.023 0.012 2.7E-04 26 2.9E-03 2.0E-06 0.176 0.022 0.011 2.4E-04 26.5 2.8E-03 1.7E-06 0.173 0.022 0.010 2.2E-04 27 2.6E-03 1.4E-06 0.170 0.021 0.009 2.0E-04 27.5 2.5E-03 1.1 E-06 0.167 0.021 0.009 1.8E-04 28 2.4E-03 9.2E-07 0.165 0.020 0.008 1.62-04 28.5 2.4E-03 7.6E-07 0.162 0.020 0.007 1.4E-04 29 2.3E-03 6.3E-07 0.159 0.020 0.007 1.32-04 29.5 2.2E-03 5.2E-07 0.157 0.019 0.006 1.2E-04 30 2.1E-03 4.3E-07 0.154 0.019 0.006 1.1 E-04 30.5 2.0E-03 3.6E-07 0.152 0.019 0.005 9.5E-05 31 2.0E-03 3.0E-07 0.150 0.018 0.005 8.5E-05 31.5 1.9E-03 2.5E-07 0.147 0.018 0.004 7.72-05 32 1.8E-03 2.1E-07 0.145 0.018 0.004 6.9E-05 32.5 1.8E-03 1.8E-07 0.143 0.017 0.004 6.32-05 33 1.7E-03 1.5E-07 0.141 0.017 0.003 5.6E-05 33.5 1.6E-03 1.3E-07 0.139 0.017 0.003 5.1 E-05 34 1.6E-03 1.1 E-07 0.137 0.017 0.003 4.6E-05 34.5 1.5E-03 8.9E-08 0.135 0.016 0.003 4.1 E-05 35 1.5E-03 7.5E-08 0.133 0.016 0.002 3.7E-05 35.5 1.4E-03 6.4E-08 0.131 0.016 0.002 3.4E-05 36 1.4E-03 5.4E-08 0.129 0.016 0.002 3.1 E-05 36.5 1.4E-03 4.6E-08 0.128 0.015 0.002 2.8E-05 37 1.3E-03 3.9E-08 0.126 0.015 0.002 2.5E-05 37.5 1.3E-03 3.3E-08 0.124 0.015 0.002 2.2E-05 38 1.2E-03 2.8E-08 0.122 0.015 0.001 2.0E-05 38.5 1.2E-03 2.4E-08

.0.121 0.015 0.001 1.8E-05 39 1.2E-03 2.1E-08 0.119 0.014 0.001 1.7E-05 39.5 1.1 E-03 1.8E-08 0.118 0.014 0.001 1.5E-05 40 1.1 E-03 1.5E-08 0.116 0.014 0.001 1.4E-05 40.5 1.1 E-03 1.3E-08 0.115 0.014 0.001 1.2E-05 41 1.0E-03 1.1 E-08 0.113 0.014 0.001 1.1 E-05 41.5 1.0E-03 9.5E-09 0.112 0.013 0.001 1.0E-05 42 9.8E-04 8.2E-09 0.110 0.013 0.001 9.1E-06 42.5 9.5E-04 7.12E-09 0.109 0.013 0.001 8,2E-06 43 9.3E-04 6.1 E-09 0.108 0.013 0.001 7.4E-06 43.5 9.0E-04 5.3E-09 0.106 0.013 0.001 6.7E-06 44 8.8E-04 4.5E-09 0.105 0.012 0.000 6.1E-06 44.5 8.5E-04 3.9E-09 0.104 0.012 0.000 5.52-06 45 8.3E-04 3.4E-09 0.103 0.012 0.000 5.0E-06 45.5 8.1E-04 3.0E-09 0.101 0.012 0.000 4.5E-06 46 7.9E-04 2.6E-09 0.100 0.012 0.000 4.1E-06 46.5 7.7E-04 2.2E-09 0.099 0.012 0.000 3.72-06 47 7.5E-04 1.9E-09 0.098 0.012 0.000 3.4E-06 47.5 7.3E-04 1.7E-09 0.097 0.011 0.000 3.0E-06 48 7.1 E-04 1.5E-09 0.096 0.011 0.000 2.8E-06 48.5 6.9E-04 1.3E-09 0.095 0.011 0.000 2.5E-06 49 6.82-04 1.1 E-09 0.094 0.011 0.000 2.3E-06 49.5 6.6E-04 9.8E-10 0.093 0.011 0.000 2.1 E-06 50 6.5E-04 8.5E-10 0.092 0.011 0.000 1.9E-06 50.5 6.3E-04 7.5E-10 0.091 0.011 0.000 1.7E-06 51 6.1 E-04 6.6E-10 0.090 0.011 0.000 1.5E-06 51.5 6.0E-04 5.7E-10 0.089 0.010 0.000 1.4E-06 52 5.9E-04 5.0E-10 0.088 0.010 0.000 1.3E-06 52.5 5.7E-04 4.4E-10 0.087 0.010 0.000 1.1 E-06 53 5.6E-04 3.9E-10 0.086 0.010 0.000 1.0E-06 53.5 5.5E-04 3.4E-10 0.085 0.010 0.000 9.4E-07 54 5.3E-04 3.0E-10 0.084 0.010 0.000 8.5E-07 K-13

Cooper-NEW-RECOVERY.XLS - NUREGCR-5496 Frequency Plant-Severe-weighted Diesel all AC Time Centered Grid-Related Weather average Generators Power 54.5 5.2E-04 2.7E-10 0.083 0.010 0.000 7.7E-07 55 5.1 E-04 2.3E-10 0.082 0.010 0.000 7.0E-07 55.5 5.OE-04 2.1E-10 0.082 0.010 0.000 6.3E-07 56 4.9E-04 1.8E-10 0.081 0.009 0.000 5.8E-07 56.5 4.8E-04 1.6E-10 0.080 0.009 0.000 5.22-07 57 4.7E-04 1;4E-10 0.079 0.009 0.000 4.7E-07 57.5 4.6E-04 1.3E-10 0.078 0.009 0.000 4.3E-07 58 4.5E-04 1.1E-10 0.078 0.009 0.000 3.9E-07 58.5 4.4E-04 9.9E-11 0.077 0.009 0.000 3.51E-07 59 4.3E-04 8.8E-11 0.076 0.009 0.000 3.2E-07 59.5 4.2E-04 7.8E-11 0.075 0.009 0.000 2.9E2-07 60 4.1E-04 6.9E-11 0.075 0.009 0.000 2.62-07 60.5 4.0E-04 6.2E-11 0.074 0.009 0.000 2.4E-07 61 3.9E-04 5.5E-11 0.073 0.008 0.000 2.2E-07 61.5 3.9E-04 4.9E-11 0.072 0.008 0.000 2.0E-07 62 3.8E-04 4.3E-11 0.072 0.008 0.000 1.82-07 62.5 3.7E-04 3.9E-11 0.071 0.008 0.000 1.6E-07 63 3.6E-04 3.4E-11 0.070 0.008 0.000 1.5E-07 63.5 3.6E-04 3.1E-11 0.070 0.008 0.000 1.3E-07 64 3.5E-04 2.7E-11 0.069 0.008 0.000 1.2E-07 64.5 3.4E-04 2.5E-11 0.069 0.008 0.000 1.1 E-07 65 3.4E-04 2.2E-11 0.068 0.008 0.000 1.02-07 65.5 3.3E-04 2.0E-11 0.067 0.008 0.000 9.2t-08 66 3.22-04 1.8E-11 0.067 0.008 0.000 8.32-08 66.5 3.2E-04 1.6E-11 0.066 0.008 0.000 7.62-08 67 3.1 E-04 1.4E-11 0.066 0.008 0.000 6.92-08 67.5 3.0E-04 1.3E-11 0.065 0.008 0.000 6.22-08 68 3.0E-04 1.1 E-11 0.064 0.007 0.000 5.72-08 68.5 2.9E-04 1.0E-11 0.064 0.007 0.000 5.22-08 69 2.9E-04 9.1E-12 0.063 0.007 0.000 4.7E-08 69.5 2.82-04 8.2E-12 0.063 0.007 0.000 4.3E-08 70 2.8E-04 7.4E-12 0.062 0.007 0.000 3.9E-08 70.5 2.7E-04 6.6E-12 0.062 0.007 0.000 3.52-08 71 2.7E-04 6.02-12 0.061 0.007 0.000 3.22-08 71.5 2.6E-04 5.4E-12 0.061 0.007 0.000 2.9E-08 72 2.6E-04 4.8E-12 0.060 0.007 0.000 2.6E-08 72.5 2.52-04 4.4E-12 0.060 0.007 0.000 2.42-08 73 2.52-04 3.92-12 0.059 0.007 0.000 2.2E-08 73.5 2.4E-04 3.5E-12 0.059 0.007 0.000 2.0E-08 74 2.4E-04 3.22-12 0.058 0.007 0.000 1.82-08 74.5 2.4E-04 2.92-12 0.058 0.007 0.000 1.6E-08 75 2.3E-04 2.6E-12 0.057 0.007 0.000 1.5E-08 75.5 2.3E-04 2.4E-12 0.057 0.007 0.000 1.42-08 76 2.22-04 2.1 E-12 0.056 0.006 0.000 1.22-08 76.5 2.2E-04 1.9E-12 0.056 0.006 0.000 1.12E-08 77 2.2E-04 1.7E-12 0.055 0.006 0.000 1.0E-08 77.5 2.1E-04 1.6E-12 0.055 0.006 0.000 9.32-09 78 2.1 E-04 1.42-12 0.054 0.006 0.000 8.42-09 78.5 2.1 E-04 1.3E-12 0.054 0.006 0.000 7.72-09 79 2.0E-04 1.22-12 0.054 0.006 0.000 7.012-09 79.5 2.0E-04 1.1E-12 0.053 0.006 0.000 6.3E-09 80 2.0E-04 9.7E-13 0.053 0.006 0.000 5.8E-09 80.5 1.9E-04 8.8E-13 0.052 0.006 0.000 5.3E-09 81 1.9E-04 8.0E-13 0.052 0.006 0.000 4.8E-09 81.5 1.9E-04 7.2E-13 0.052 0.006 0.000 4.32-09 82 1.8E-04 6.6E-13 0.051 0.006 0.000 4.0E-09 82.5 1.8E-04 6.02-13 0.051 0.006 0.000 3.6E-09 83 1.82-04 5.4E-13 0.050 0.006 0.000 3.3E-09 83.5 1.7E-04 5.0E-13 0.050 0.006 0.000 3.0E-09 K-14