ML061980478

From kanterella
Jump to navigation Jump to search

Draft Question Re Proposed RTD Bypass Amendment
ML061980478
Person / Time
Site: Cook 
(DPR-058)
Issue date: 07/14/2006
From: Tam P
NRC/NRR/ADRO/DORL/LPLIII-1
To: Scarpello M, Waters J
Indiana Michigan Power Co
References
TAC MD2106
Download: ML061980478 (2)


Text

From:

Peter Tam To:

Scarpello, Michael; Waters, Joe Date:

07/14/2006 11:13:36 AM

Subject:

D. C. Cook Unit 1: Draft Question re. Propsoed RTD Bypass Amendment (TAC MD2106)

Michael, Joe:

This is regarding your 5/31/06 application for amendment. We have developed the following draft question, and would like to discuss it with you in a conference call:

The amendment request involves the removal of the resistance temperature detector (RTD) bypass manifolds. This will affect the RTD response time, which is used in the OTT trip function. The OTT trip initiates automatic protective actions to mitigate the consequences of the following events, and therefore would be affected by the change in RTD response time:

1.

Loss of electrical load/turbine trip

2.

Uncontrolled rod cluster control assembly (RCCA) bank withdrawal at power

3.

Chemical Volume Control System (CVCS) malfunction that results in a decrease in the boron concentration in the reactor coolant

4.

Inadvertent opening of a pressurizer safety or relief valve For each event, show that OTT will continue to provide adequate protection from departure from nucleate boiling following the requested change in RTD response time.

This e-mail aims solely to prepare you and others for the requested conference call. This e-mail does not convey a formal NRC staff position, and does not formally request for additional information. We will discuss disposition of this question in the requested conference call.

Peter S. Tam, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation e-mail: pst@nrc.gov Tel.: 301-415-1451 CC:

Miranda, Samuel; Nakoski, John; Somers, Christopher Mail Envelope Properties (44B7B4A0.E11 : 12 : 35330)

Subject:

D. C. Cook Unit 1: Draft Question re. Propsoed RTD Bypass Amendment (TAC MD2106)

Creation Date 07/14/2006 11:13:36 AM From:

Peter Tam Created By:

PST@nrc.gov Recipients Action Date & Time aep.com Transferred 07/14/2006 11:14:30 AM jrwaters (Joe Waters) mkscarpello (Michael Scarpello)

nrc.gov TWGWPO01.HQGWDO01 Delivered 07/14/2006 11:13:43 AM JAN1 CC (John Nakoski)

Opened 07/14/2006 11:15:33 AM SXM1 CC (Samuel Miranda)

Opened 07/14/2006 1:37:26 PM nrc.gov TWGWPO02.HQGWDO01 Delivered 07/14/2006 11:13:37 AM CMS3 CC (Christopher Somers)

Opened 07/14/2006 11:13:47 AM Post Office Delivered Route aep.com TWGWPO01.HQGWDO01 07/14/2006 11:13:43 AM nrc.gov TWGWPO02.HQGWDO01 07/14/2006 11:13:37 AM nrc.gov Files Size Date & Time MESSAGE 2682 07/14/2006 11:13:36 AM Options Auto Delete:

No Expiration Date:

None Notify Recipients:

Yes Priority:

Standard ReplyRequested:

No Return Notification:

None Concealed

Subject:

No Security:

Standard To Be Delivered:

Immediate Status Tracking:

Delivered & Opened