MONTHYEARML0616300262006-06-0707 June 2006 Technical Specifications, Issuance of Amendment Setpoint Verification of Trip Actuating Devices, MC6956 and MC6958 Project stage: Approval ML0514701082006-06-0707 June 2006 License Amendments, Issuance of Amendment Setpoint Verification of Trip Actuating Devices, MC6956 and MC6958 Project stage: Approval 2006-06-07
[Table View] |
|
---|
Category:Technical Specifications
MONTHYEARML24045A0882024-02-22022 February 2024 Correction to the Technical Specifications to Reflect Appropriate Pages Removed and Retained by Previous License Amendments ML23339A0442023-12-0505 December 2023 Issuance of Amendment No. 68, 301 and 277 Regarding Changes to Implement the Independent Spent Fuel Storage Installation Physical Security Plan ML23100A1172023-11-17017 November 2023 NRC Response - Indian Point Energy Center Generating Units 1, 2, and 3 Letter with Enclosures Regarding Changes to Remove the Cyber Security Plan License Condition ML22307A0452023-11-17017 November 2023 Enclosure 1 - Amendment No. 297 to Rfl No. DPR-26 for Indian Point Unit 2 License Amendment Request to Modify Tech Specs for Staffing Requirements with Spent Fuel Transfer to Dry Storage ML20297A3262020-11-23023 November 2020 Enclosure 2, Draft Conforming Amendments for Transfer of Facility Operating Licenses to Holtec International, Owner, and Holtec Decommissioning International, LLC, Operator ML20100H9922020-06-0202 June 2020 Issuance of Amendment No. 269 Proposed Technical Specification Changes to City Water Surveillance Requirement and Condensate Storage Tank Required Action A.1 ML20081J4022020-04-28028 April 2020 Issuance of Amendment No. 294 Permanently Defueled Technical Specifications ML20110A0052020-04-27027 April 2020 Correction to Amendment No. 267 Issued April 10, 2020, Changes to Technical Specifications for a Permanently Defueled Condition ML20071Q7172020-04-10010 April 2020 Issuance of Amendment Nos. 292 and No. 267 Changes to Technical Specification Sections 1.1, 4.0, and 5.0 for a Permanently Defueled Condition ML19175A0422019-09-11011 September 2019 Arkansas Units 1 and 2; Grand Gulf, Unit 1; Indian Point 2 and 3; Palisades; River Bend, Unit 1; Waterford Unit 3 - Issuance of Amendments to Adopt TSTF-529, Clarify Use and Application Rules ML19072A1342019-03-15015 March 2019 Amended Provisional Operating License DPR-5, 3-22-2019 ML18212A1902018-09-17017 September 2018 Renewed Facility Operating License DPR-64, Technical Specifications, Appendix a ML18212A1852018-09-17017 September 2018 Renewed Facility Operating License DPR-26, Technical Specifications, Appendix B ML18212A1942018-09-17017 September 2018 Renewed Facility Operating License DPR-64, Technical Specifications, Appendix B ML18212A1952018-09-17017 September 2018 Renewed Facility Operating License DPR-64, Technical Specifications, Appendix C ML16064A2152016-04-12012 April 2016 Issuance of Amendments Cyber Security Plan Implementation Schedule NL-16-027, Response to Request for Additional Information Related to License Amendment Request Regarding Conditional Exemption from End-of-Life (Eol) Moderator Temperature Coefficient (Mtc) Measurement2016-03-0202 March 2016 Response to Request for Additional Information Related to License Amendment Request Regarding Conditional Exemption from End-of-Life (Eol) Moderator Temperature Coefficient (Mtc) Measurement ML15349A7942016-02-23023 February 2016 Generation, Unit No. 2 - Issuance of Amendment Extension of the Containment Integrated Leak Rate Test to 15 Years NL-15-144, License Amendment Request - Conditional Exemption from End-of-Life (Eol) Moderator Temperature Coefficient (Mtc) Measurement2015-12-10010 December 2015 License Amendment Request - Conditional Exemption from End-of-Life (Eol) Moderator Temperature Coefficient (Mtc) Measurement NL-15-144, Indian Point, Units 2 and 3 - License Amendment Request - Conditional Exemption from End-of-Life (Eol) Moderator Temperature Coefficient (Mtc) Measurement2015-12-10010 December 2015 Indian Point, Units 2 and 3 - License Amendment Request - Conditional Exemption from End-of-Life (Eol) Moderator Temperature Coefficient (Mtc) Measurement NL-15-118, Post Accident Monitoring (PAM) Report for an Inoperable Reactor Vessel Level Indication System (RVLIS) Train B, Indian Point Unit 32015-09-0303 September 2015 Post Accident Monitoring (PAM) Report for an Inoperable Reactor Vessel Level Indication System (RVLIS) Train B, Indian Point Unit 3 ML15226A1592015-09-0303 September 2015 Issuance of Amendment Changes to Reactor Vessel Heatup and Cooldown Curves and Low Temperature Overpressure Protection System Requirements ML15110A0092015-05-26026 May 2015 Issuance of Amendment Re Implementation of Technical Specification Task Force Traveler 510, Revision 2, Revision to Steam Generator Program Inspection Frequencies & Tube Sample Selection(Tac Nos. MF3752 & MF3753) ML15083A4902015-04-0202 April 2015 Issuance of Amendment Proposed License Amendment Regarding a Change to Technical Specification 3.1.4 Reactivity Control Systems ML15028A3082015-03-13013 March 2015 Issuance of Amendment Extension of the Type a Containment Integrated Leak Rate Test Frequency from 10 to 15 Years NL-14-128, Proposed License Amendment Regarding Extending the Containment Type a Leak Rate Testing Frequency to 15 Years2014-12-0909 December 2014 Proposed License Amendment Regarding Extending the Containment Type a Leak Rate Testing Frequency to 15 Years ML14265A3292014-09-24024 September 2014 Issuance of Amendment Temporary Change to Technical Specification 3.8.6 Battery 22 Surveillance Requirement (Exigent Circumstances) NL-14-121, Indian Point, Unit 2, Updated Final Safety Analysis Report (Ufsar), Revision 25, Technical Requirements Manual2014-09-17017 September 2014 Indian Point, Unit 2, Updated Final Safety Analysis Report (Ufsar), Revision 25, Technical Requirements Manual ML14287A2942014-09-17017 September 2014 Updated Final Safety Analysis Report (Ufsar), Revision 25, Technical Requirements Manual ML14198A1612014-09-0505 September 2014 Issuance of Amendment H* Alternate Repair Criteria for Steam Generator Tube Inspection and Repair (Tac No. MF3369) ML14169A5832014-07-17017 July 2014 Issuance of Amendment Revised Containment Integrity Analysis (Tac No. MF0591) NL-14-053, Response to Request for Additional Information Regarding Emergency Diesel Generator Fuel Oil Storage Supplies2014-04-14014 April 2014 Response to Request for Additional Information Regarding Emergency Diesel Generator Fuel Oil Storage Supplies NL-14-035, Proposed Changes to Technical Specifications Regarding Reactor Vessel Pressure/Temperature Limit Curves2014-04-0101 April 2014 Proposed Changes to Technical Specifications Regarding Reactor Vessel Pressure/Temperature Limit Curves ML14045A2482014-03-0505 March 2014 Issuance of Amendment Pressure-Temperature Limit Curves and Low Temperature Over Pressure Requirements NL-14-032, Supplemental Information to Proposed Changes to Indian Point 2 Technical Specifications Regarding Reactor Vessel Heatup and Cooldown Curves and Low Temperature Over Pressure Requirements Indian Point Unit Number 22014-02-24024 February 2014 Supplemental Information to Proposed Changes to Indian Point 2 Technical Specifications Regarding Reactor Vessel Heatup and Cooldown Curves and Low Temperature Over Pressure Requirements Indian Point Unit Number 2 NL-14-001, Proposed License Amendment for Alternate Repair Criteria for Steam Generator Tube Inspection and Repair2014-01-16016 January 2014 Proposed License Amendment for Alternate Repair Criteria for Steam Generator Tube Inspection and Repair NL-14-001, Indian Point, Unit 2 - Proposed License Amendment for Alternate Repair Criteria for Steam Generator Tube Inspection and Repair2014-01-16016 January 2014 Indian Point, Unit 2 - Proposed License Amendment for Alternate Repair Criteria for Steam Generator Tube Inspection and Repair CNRO-2012-00009, Entergy Responses to Request for Additional Information Regarding Changes to the Quality Assurance Program Manual & Associated Plant Technical Specifications Re Staff Qualifications2012-11-20020 November 2012 Entergy Responses to Request for Additional Information Regarding Changes to the Quality Assurance Program Manual & Associated Plant Technical Specifications Re Staff Qualifications NL-12-039, Proposed License Amendment Regarding Atmospheric Dump Valves2012-05-23023 May 2012 Proposed License Amendment Regarding Atmospheric Dump Valves NL-12-002, Proposed Change to Containment Purge System and Pressure Relief Line Isolation Instrumentation Technical Specifications2012-01-11011 January 2012 Proposed Change to Containment Purge System and Pressure Relief Line Isolation Instrumentation Technical Specifications NL-11-119, Proposed Change to the Technical Specification Requirement for Containment Sump Level Indication2011-10-18018 October 2011 Proposed Change to the Technical Specification Requirement for Containment Sump Level Indication NL-10-072, Proposed Technical Specification Change Regarding RWST Surveillance Requirement2010-10-0606 October 2010 Proposed Technical Specification Change Regarding RWST Surveillance Requirement NL-09-167, Proposed Exigent License Amendment Re One Time Extension of the Auxiliary Boiler Feedwater Pump Allowed Outage Time2009-12-15015 December 2009 Proposed Exigent License Amendment Re One Time Extension of the Auxiliary Boiler Feedwater Pump Allowed Outage Time NL-09-129, Indian Point, Unit 3, Proposed License Amendment to Change Technical Specifications Regarding Surveillance Requirements for AC and DC Sources2009-11-19019 November 2009 Indian Point, Unit 3, Proposed License Amendment to Change Technical Specifications Regarding Surveillance Requirements for AC and DC Sources NL-09-129, Proposed License Amendment to Change Technical Specifications Regarding Surveillance Requirements for AC and DC Sources2009-11-19019 November 2009 Proposed License Amendment to Change Technical Specifications Regarding Surveillance Requirements for AC and DC Sources NL-09-119, Proposed License Amendment Regarding Diesel Generator Air Start Receiver Pressure, Indian Point Units 2 & 32009-11-17017 November 2009 Proposed License Amendment Regarding Diesel Generator Air Start Receiver Pressure, Indian Point Units 2 & 3 ML0834304242009-05-29029 May 2009 License Amendment, Technical Specifications Regarding Removal of Spent Fuel from Unit 1 and Drain Down of the Spent Fuel Pool NL-08-137, Reply to Request for Additional Information Regarding Amendment Application on Control Room Envelope Habitability2008-09-18018 September 2008 Reply to Request for Additional Information Regarding Amendment Application on Control Room Envelope Habitability ML0811401772008-06-0909 June 2008 Tec Specs to Amedment 236, License No. DPR-64 for Indian Point, Unit 3 ML0727805822007-10-0404 October 2007 Technical Specifications, Change of Pressure-temperature and Low Temperature Protection System Limits 2024-02-22
[Table view] |
Text
LOP DG Start Instrumentation 3.3.5 SURVEILLANCE REQUIREMENTS_______
SURVEILLANCE FREQUENCY SR 3.3.5.1 Perform CHANNEL CHECK of the 480 V bus 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Degraded Voltage Function.
----- NOTE-------------- -------- 31 days Verification of setpoint not required SR 3.3.5.2 Perform TADOT of the 480 V bus Degraded Voltage Function.
SR 3.3.5.3 Perform TADOT of each of the following: 24 months
- a. 480 V bus Undervoltage Function; and
- b. 480 V bus SBO Function.
SR 3.3.5.4 Perform ACTUATION LOGIC TEST of each of the 24 months following:
- a. 480 V bus Undervoltage Function; and
- b. 480 V bus SBO Function.
SR 3.3.5.5 Perform CHANNEL CALIBRATION with Allowable 24 months Values as follows:
- a. 480 V bus Undervoltage Function Allowable Value:
Ž:206.6 V with a time delay5*3.7 seconds.
- b. 480 V bus Degraded Voltage Function Allowable Value:
Ž:419 V and5*423 V with time delays as follows:
- i. 2:153 seconds and5*207 seconds (No SI Signal); and ii. Ž 8.4 seconds and
- 11.4 seconds (Coincident SI).
C. 480 V bus SBO Function Allowable Value:
2t 198.6 V.
INDIAN POINT 2 3.3.5-4 INDIN No. 24 7 PONT3.35-4Amendment
LOP DG Start Instrumentation 3.3.5 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TiME C. Required Action and associated C.1 Enter applicable Immediately Completion Time not met. Condition(s) and Required Action(s) for OR the associated DG made inoperable by LOP DO Two channels of Degraded start instrumentation.
Voltage Function inoperable in one or more buses.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY
NOTE ---- --- _-
Verification of setpoint not required 31 days SR 3.3.5.1 Perform TADOT.
SR 3.3.5.2 Perform CHANNEL CALIBRATION with Allowable Value as follows:
- a. Undervoltage (480 V bus) Relay Allowable 24 months Value Ž:200 V.
- b. Degraded Voltage (480 V bus) Relay (Non-Si) 18 months Allowable Value Ž:414 V with a time delay
<z45 seconds.
- c. Degraded Voltage (480 V bus) Relay 18 months (Coincident SI) Allowable Value Ž!414 V with a time delay
INDIAN POINT 3 3.3.5-2 INDIN 23 1 PONT3.35-2Amendment