June 7, 2006 Mr. Michael Kansler President Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601-1839
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF VERMONT YANKEE NUCLEAR POWER STATION LICENSE RENEWAL APPLICATION
Dear Mr. Kansler:
By letter dated January 25, 2006, as supplemented by letter dated March 15, 2006, the U.S.
Nuclear Regulatory Commission (NRC) received the Entergy Nuclear Operations, Inc.
application for renewal of Operating License No. DPR-28 for the Vermont Yankee Nuclear Power Station (VYNPS). The NRC staff is reviewing the information contained in the license renewal application and has identified, in the enclosure, areas where additional information is needed to complete the review. Specifically, the enclosed requests for additional information are from the NRC Project Team that performed the audits at VYNPS.
Based on discussions with Mr. Jim DeVincentis of your staff, a mutually agreeable date for your response is within 30 days of the date of this letter. If you have any questions regarding this letter or if circumstances result in your need to revise the response date, please contact me at 301-415-4053 or by e-mail at jgr@nrc.gov.
Sincerely,
/RA/
Jonathan Rowley, Project Manager License Renewal Branch B Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-271
Enclosure:
Requests for Additional Information cc w/encl: See next page
ML061580640 Document Name: E:\\Filenet\\ML061580640.wpd OFFICE PM:RLRB:DLR LA:DLR BC:RLRB;DLR NAME JRowley IKing JZimmerman DATE 06/ 07 /06 06/ 07 /06 06/ 07 /06
Letter to Michael Kansler from Jonathan Rowley dated June 7, 2006
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF VERMONT YANKEE NUCLEAR POWER STATION LICENSE RENEWAL APPLICATION HARD COPY DLR R/F E-MAIL:
JFair RWeisman AMurphy RPettis GGalletti DShum GBagchi SSmith (srs3)
SDuraiswamy YL (Renee) Li RidsNrrDlr RidsNrrDlrRlra RidsNrrDlrRlrb RidsNrrDe RidsNrrDci RidsNrreEemb RidsNrrDeEeeb RidsNrrDeEqva RidsNrrDss RidsNrrDnrl RidsOgcMailCenter RidsNrrAdes DLR Staff JEads JRowley RLaufer JShea CAnderson, RI MSykes, RI DScrenci, RI MModes, RI DPelton, Sr. Resident MLemoncelli RidsOpaMail
Vermont Yankee Nuclear Power Station cc:
Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406-1415 Mr. David R. Lewis Pillsbury, Winthrop, Shaw, Pittman, LLP 2300 N Street, N.W.
Washington, DC 20037-1128 Mr. David OBrien, Commissioner Vermont Department of Public Service 112 State Street Montpelier, VT 05620-2601 Mr. James Volz, Chairman Public Service Board State of Vermont 112 State Street Montpelier, VT 05620-2701 Chairman, Board of Selectmen Town of Vernon P.O. Box 116 Vernon, VT 05354-0116 Operating Experience Coordinator Vermont Yankee Nuclear Power Station 320 Governor Hunt Road Vernon, VT 05354 G. Dana Bisbee, Esq.
Deputy Attorney General 33 Capitol Street Concord, NH 03301-6937 Chief, Safety Unit Office of the Attorney General One Ashburton Place, 19th Floor Boston, MA 02108 Ms. Deborah B. Katz Box 83 Shelburne Falls, MA 01370 Ms. Carla A. White, RRPT, CHP Radiological Health Vermont Department of Health P.O. Box 70, Drawer #43 108 Cherry Street Burlington, VT 05402-0070 Mr. James M. DeVincentis Manager, Licensing Vermont Yankee Nuclear Power Station P.O. Box 0500 185 Old Ferry Road Brattleboro, VT 05302-0500 Resident Inspector Vermont Yankee Nuclear Power Station U. S. Nuclear Regulatory Commission P.O. Box 176 Vernon, VT 05354 Director, Massachusetts Emergency Management Agency ATTN: James Muckerheide 400 Worcester Rd.
Framingham, MA 01702-5399 Jonathan M. Block, Esq.
Main Street P.O. Box 566 Putney, VT 05346-0566 Mr. John F. McCann Director, Licensing Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Gary J. Taylor Chief Executive Officer Entergy Operations 1340 Echelon Parkway Jackson, MS 39213
Vermont Yankee Nuclear Power Station cc:
Mr. John T. Herron Sr. VP and Chief Operating Officer Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Oscar Limpias Vice President, Engineering Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Christopher Schwartz Vice President, Operations Support Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Michael J. Colomb Director of Oversight Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Travis C. McCullough Assistant General Counsel Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Jay K. Thayer Site Vice President Entergy Nuclear Operations, Inc.
Vermont Yankee Nuclear Power Station P.O. Box 0500 185 Old Ferry Road Brattleboro, VT 05302-0500 Mr. James H. Sniezek 5486 Nithsdale Drive Salisbury, MD 21801 Ms. Stacey M. Lousteau Treasury Department Entergy Services, Inc.
639 Loyola Avenue New Orleans, LA 70113 Mr. Raymond Shadis New England Coalition Post Office Box 98 Edgecomb, ME 04556 Mr. James P. Matteau Executive Director Windham Regional Commission 139 Main Street, Suite 505 Brattleboro, VT 05301 Mr. William K. Sherman Vermont Department of Public Service 112 State Street Drawer 20 Montpelier, VT 05620-2601 Mr. Michael D. Lyster 5931 Barclay Lane Naples, FL 34110-7306 Ms. Charlene D. Faison Manager, Licensing 440 Hamilton Avenue White Plains, NY 10601 Mr. James Ross Nuclear Energy Institute 1776 I Street, NW, Suite 400 Washington, DC 20006-3708
Enclosure VERMONT YANKEE NUCLEAR POWER STATION LICENSE RENEWAL APPLICATION REQUESTS FOR ADDITIONAL INFORMATION (RAIs)
RAI 3.6.2.2-N-08 10 CFR 54.4 (a)(3) requires, in part, that all systems, structures, and components (SSCs) relied on in safety analyses or plant evaluation to perform a function that demonstrates compliance with the Commissions regulations for station blackout (10 CFR 50.63) are within the scope of license renewal. Vernon Hydroelectric Station has been designated as the station blackout (SBO) alternate alternating current source and is used to meet SBO requirements of 10 CFR 50.63.
Are all SSCs (including electrical, mechanical, structural, and civil) associated with the Vernon Hydroelectric Station included in the scope of license renewal? If they are not, please explain why not. If they are, please provide an aging management review for long-lived, passive SSCs associated with the hydroelectric station.
RAI 3.6.2.2-N-01 In the license renewal application (LRA) Table 3.6.2-1, under cable connections (metallic parts),
you have stated that there are no aging effects requiring management and no aging management program (AMP) is required. Further, in LRA Table 3.6-1, under discussion of cable connection metallic parts, you have stated that cable connections outside of active devices are taped or sleeved for protection; and operating experience with metallic parts of electrical cable connections at VYNPS indicated no aging effects requiring management.
Electrical cable connections (metallic parts) are subject to the following aging stressors:
thermal cycling, ohmic heating, electrical transients, vibration, chemical contamination, corrosion, and oxidation. NUREG-1801, Revision 1, AMP XI.E6, Electrical Cable Connection not Subject to 10 CFR 50.49 Environmental Qualification Requirements, specifies that connections associated with cables within the scope of license renewal are part of this program, regardless of their association with active or passive components. Please provide a basis document including an AMP with the ten elements for cable connections or provide a justification for why an AMP is not necessary.