ML061580121

From kanterella
Jump to navigation Jump to search

Southern Nuclear Operating Company Response to NRC Question Regarding the Vogtle, Units 1 & 2 First Revised Order EA-03-009 Relaxation Request, Alternate Examination Coverage for Reactor Pressure Vessel Head Penetration Nozzles
ML061580121
Person / Time
Site: Vogtle  
Issue date: 06/02/2006
From: Grissette D
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
CAW-06-2157, EA-03-009, NL-06-1217, WCAP-16493-NP, WCAP-16493-P
Download: ML061580121 (14)


Text

Don E. Grissette Vice President Southern Nuclear Operating Company, Inc.

40 Inverness Center Parkway Post Office Box 1295 Birmingham. Alabama 35201 Tel 205,992.6474 Fax 205,992.0341 SOUTHERNA COMPANY Energy to Serve Your World' NL-06-1217 June 2, 2006 Docket Nos.:

50-424 50-425 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Southern Nuclear Operating Company Response to NRC Question Regarding the Vogtle Electric Generating Plant Units I and 2 First Revised Order EA-03-009 Relaxation Request, Alternate Examination Coverage for Reactor Pressure Vessel Head Penetration Nozzles Ladies and Gentlemen:

On May 31, 2006, Southern Nuclear Operating Company (SNC) received one question by facsimile from the NRC staff conceroing SNC's First Revised Order EA-03009 relaxation request, dated May 18, 2006, regarding alternate examination coverage for reactor pressure vessel head penetration nozzles for Vogtle Electric Generating Plant (VEGP) Units 1 and 2.

Enclosure I contains the SNC response to the NRC question. Enclosure 2 provides an application for withholding, affidavit, proprietary information notice, and copyright notice for information proprietary to Westinghouse Electric Company, LLC. Enclosure 3 provides six copies of a non-proprietary version of Westinghouse Electric Company WCAP-1 6493-NP Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper head Penetrations to Support Continued Operation: Vogtle Units I and 2," dated May 2006. Enclosure 4 provides six copies of a proprietary version of Westinghouse Electric Company WCAP-I6493-P Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units 1 and 2," dated November 2005.

(Affirmation and signature provided on the following page.)

A/GD 5evs~I

(*t0e 1166m~

4ýrnc/S

U. S. Nuclear Regulatory Commission NL-06-1217 Page 2 Mr. D. E. Grissette states he is a Vice President of Southern Nuclear Operating Company, is authorized to execute this oath on behalf of Southern N.iclear Operating Company and to the best of his knowledge and belief, the facts set forth, in this letter are true.

This letter contains no.NRC commitments. If you have any questions, please advise.

Respectfully submitted, SOUTHERN NUCLEAR OPERATING COMPANY Don E. Grissette

  • I nf/

and~n,.hnA.

2006.

,."'~ " o. =

Notay PublU

£ i/I

, My commission expires DEG/LPH/sdI

, "*./?.

-J,.+

/ft."

0vi

Enclosures:

1.

SNC response to the NRC question

2.

Westinghouse Letter CAW-06-2157, Application for Withholding, Affidavit, Proprietary Information Notice, and Copyright Notice for Information Proprietary to Westinghouse Electric Company, LLC

3.

Six copies of a non-proprietary version of Westinghouse Electric Company WCAP-16493-NP Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units I and 2

4.

Six copies of a proprietary version of Westinghouse Electric Company WCAP-16493-P Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units'l and 2 cc:

Southern Nuclear Operating Company Mr. J. T. Gasser, Executive Vice President Mr. T. E. Tynan, General Manager - Plant Vogtle RType: CVC7000 U. S. Nuclear Regulatory Commission Dr. W. D. Travers, Regional Administrator Mr. C. Gratton, NRR Project Manager - Vogtle Mr. G. J. McCoy, Senior Resident Inspector - Vogtle

Southern Nuclear Operating Company Response to NRC Question Regarding the Vogtle Electric Generating Plant Units I and 2 First Revised Order EA-03-009 Relaxation Request, Alternate Examination Coverage for Reactor Pressure Vessel Head Penetration Nozzles Enclosure I SNC response to the NRC question

Southern Nuclear Operating Company Response to NRC Question Regarding the Vogtle Electric Generating Plant Units 1 and 2 First Revised Order EA-03-009 Relaxation Request, Alternate Examination Coverage for Reactor Pressure Vessel Head Penetration Nozzles

1.

NRC Ouestion NRC staff requests that the licensee submit the stress and fracture mechanics analysis that Is summarized in the table on page 10 of the licensee's attachment to letter dated May 18, 2006. A NRC staff review of the stress and fracture mechanics analysis is necessary to verify licensee's basis for alternative examination requirements proposed in the relaxation request.

SNC Response contains proprietary versions of Westinghouse Electric Company WCAP-16493-P Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units I and 2,"

dated November 2005, which contain the requested analysis information.

Southern Nuclear Operating Company Response to NRC Question Regarding the Vogtle Electric Generating Plant Units 1 and 2 First Revised Order EA-03-009 Relaxation Request, Alternate Examination Coverage for Reactor Pressure Vessel Head Penetration Nozzles Westinghouse Letter CAW-06-2157, Application for Withholding, Affidavit, Proprietary Information Notice, and Copyright Notice for Information Proprietary to Westinghouse Electric Company, LLC

Westinghouse Westinghouse Electric Company NudearSeivices P.O. Box355 Pittsburgh, Pennsylvania 15230-0355 USA U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Directtel:

Direct fax:

e-mail:

(412) 374-4643 (412) 374-4011 greshaja@westinghouse.com Our ref CAW-06-2157 June 2, 2006 APPLICATION FOR WITHHOLDING PROPRIETARY INFORMATION FROM PUBLIC DISCLOSURE

Subject:

WCAP-16493-P, Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units 1 and 2," November 2005 (Proprietary)

The proprietary information for which withholding is being requested in the above-referenced report is further identified in Affidavit CAW-06-2157 signed by the owner of the proprietary information, Westinghouse Electric Company LLC. The affidavit, which accompanies this letter, sets forth the basis on which the information may be withheld from public disclosure by the Commission and addresses with specificity the considerations listed in paragraph (bX4) of 10 CFR Section 2.390 of the Commission's regulations.

Accordingly, this letter authorizes the utilization of the accompanying affidavit by Southern Nuclear Operating Company (SNC).

Correspondence with respect to the proprietary aspects of the application for withholding or the Westinghouse affidavit should reference this letter, CAW-06-2157, and should be addressed to J. A. Gresham, Manager, Regulatory Compliance and Plant Licensing, Westinghouse Electric Company LLC, P.O. Box 355, Pittsburgh, Pennsylvania 15230-0355.

Very truly yours, Greglaty oManager Regulatory Compliance and Plant Licensing Enclosures cc: B. Benney A BNFL Group company

CAW-06-2157 bcc: J. A. Gresham (ECE 4-7A) IL R. Bastien, IL (Nivelles, Belgium)

C. Brinkman, IL (Westinghouse Electric Co., 12300 Twinbrook Parkway, Suite 330, Rockville, MD 20852)

RCPL Administrative Aide (ECE 4-7A) IL, IA (letter and affidavit only)

J. Andrachek C.Ng A BNFL Group company

CAW-06-2157 AFFIDAVIT COMMONWEALTH OF PENNSYLVANIA:

ss COUNTY OF ALLEGHENY:

Before me, the undersigned authority, personally appeared J. A. Gresham, who, being by me duly sworn according to law, deposes and says that he is authorized to execute this Affidavit on behalf of Westinghouse Electric Company LLC (Westinghouse), and that the averments of fact set forth in this Affidavit are true and correct to the best of his knowledge, information, and belief:

AGresham, Manager Regulatory Compliance and Plant Licensing Sworn to and subscribed before me this 2nd day June, 2006.

Notary Public Notadal Seal Shawa L brod, Notar Public Monaneville Bore, Allegheny Cunty My Commissn Exms January 29, 2007 Member. Pennsvania Assocatbn Of NoWades

2 CAW-06-2157 (1)

I am Manager, Regulatory Compliance and Plant Licensing, in Nuclear Services, Westinghouse Electric Company LLC (Westinghouse), and as such, I have been specifically delegated the function of reviewing the proprietary information sought to be withheld from public disclosure in connection with nuclear power plant licensing and rule making proceedings, and am authorized to apply for its withholding on behalf of Westinghouse.

(2)

I am making this Affidavit in conformance with the provisions of 10 CFR Section 2.390 of the Commission's regulations and in conjunction with the Westinghouse "Application for Withholding" accompanying this Affidavit.

(3)

I have personal knowledge of the criteria and procedures utilized by Westinghouse in designating information as a trade secret, privileged or as confidential commercial or financial information.

(4)

Pursuant to the provisions of paragraph (bX4) of Section 2.390 of the Commission's regulations, the following is furnished for consideration by the Commission in determining whether the information sought to be withheld from public disclosure should be withheld.

(i)

The information sought to be withheld from public disclosure is owned and has been held in confidence by Westinghouse.

(ii)

The information is of a type customarily held in confidence by Westinghouse and not customarily disclosed to the public. Westinghouse has a rational basis for determining the types of information customarily held in confidence by it and, in that connection, utilizes a system to determine when and whether to hold certain types of information in confidence. The application of that system and the substance of that system constitutes Westinghouse policy and provides the rational basis required.

Under that system, information is held in confidence if it falls in one or more of several types, the release of which might result in the loss of an existing or potential competitive advantage, as follows:

(a)

The information reveals the distinguishing aspects of a process (or component, structure, tool, method, etc.) where prevention of its use by any of

3 CAW-06-2157 Westinghouse's competitors without license from Westinghouse constitutes a competitive economic advantage over other companies.

(b)

It consists of supporting data, including test data, relative to a process (or component, structure, tool, method, etc.), the application of which data secures a competitive economic advantage, e.g., by optimization or improved marketability.

(c)

Its use by a competitor would reduce his expenditure of resources or improve his competitive position in the design, manufacture, shipment, installation, assurance of quality, or licensing a similar product.

(d)

It reveals cost or price information, production capacities, budget levels, or commercial strategies of Westinghouse, its customers or suppliers.

(e)

It reveals aspects of past, present, or future Westinghouse or customer funded development plans and programs of potential commercial value to Westinghouse.

(f)

It contains patentable ideas, for which patent protection may be desirable.

There are sound policy reasons behind the Westinghouse system which include the following:

(a)

The use of such information by Westinghouse gives Westinghouse a competitive advantage over its competitors. It is, therefore, withheld from disclosure to protect the Westinghouse competitive position.

(b)

It is information that is marketable in many ways. The extent to which such information is available to competitors diminishes the Westinghouse ability to sell products and services involving the use of the information.

(c)

Use by our competitor would put Westinghouse at a competitive disadvantage by reducing his expenditure of resources at our expense.

4 CAW-06-2157 (d)

Each component of proprietary information pertinent to a particular competitive advantage is potentially as valuable as the total competitive advantage. If competitors acquire components of proprietary information, any one component may be the key to the entire puzzle, thereby depriving Westinghouse of a competitive advantage.

(e)

Unrestricted disclosure would jeopardize the position of prominence of Westinghouse in the world market, and thereby give a market advantage to the competition of those countries.

(f)

The Westinghouse capacity to invest corporate assets in research and development depends upon the success in obtaining and maintaining a competitive advantage.

(iii)

The information is being transmitted to the Commission in confidence and, under the provisions of 10 CFR Section 2.390, it is to be received in confidence by the Commission.

(iv)

The information sought to be protected is not available in public sources or available information has not been previously employed in the same original manner or method to the best of our knowledge and belief.

(v) The proprietary information sought to be withheld in this submittal is that which is appropriately marked in WCAP-16493-P, Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units 1 and 2," November 2005 (Proprietary) being transmitted by the SNC letter and Application for Withholding Proprietary Information from Public Disclosure, to the Document Control Desk. The proprietary information as submitted for use by Westinghouse for Vogtle Units I and 2 is expected to be applicable for other licensee submittals in response to certain NRC requirements for justification of the use of fracture mechanics analyses to support continued safe operation of Vogtle Units 1 and 2 with the presence of a crack in a control rod drive head penetration.

This information is part of that which will enable Westinghouse to:

5 CAW-06-2157 (a) Determine the allowable time of safe operation if cracks are found.

(b) Assist the customer to obtain NRC approval.

Further this information has substantial commercial value as follows:

(a)

Westinghouse plans to sell the use of similar information to its customers for purposes of meeting NRC requirements for licensing documentation.

(b)

Westinghouse can sell support and defense of continued safe operation with the presence of cracks in a control rod drive head penetration.

Public disclosure of this proprietary information is likely to cause substantial harm to the competitive position of Westinghouse because it would enhance the ability of competitors to provide similar support documentation and licensing defense services for commercial power reactors without commensurate expenses. Also, public disclosure of the information would enable others to use the information to meet NRC requirements for licensing documentation without purchasing the right to use the information.

The development of the technology described in part by the information is the result of applying the results of many years of experience in an intensive Westinghouse effort and the expenditure of a considerable sum of money.

In order for competitors of Westinghouse to duplicate this information, similar technical programs would have to be performed and a significant manpower effort, having the requisite talent and experience, would have to be expended.

Further the deponent sayeth not.

PROPRIETARY INFORMATION NOTICE Transmitted herewith are proprietary and/or non-proprietary versions of documents furnished to the NRC in connection with requests for generic and/or plant-specific review and approval.

In order to conform to the requirements of 10 CFR 2.390 of the Commission's regulations concerning the protection of proprietary information so submitted to the NRC, the information which is proprietary in the proprietary versions is contained within brackets, and where the proprietary information has been deleted in the non-proprietary versions, only the brackets remain (the information that was contained within the brackets in the proprietary versions having been deleted). The justification for claiming the information so designated as proprietary is indicated in both versions by means of lower case letters (a) through (f) located as a superscript immediately following the brackets enclosing each item of information being identified as proprietary or in the margin opposite such information. These lower case letters refer to the types of information Westinghouse customarily holds in confidence identified in Sections (4XiiXa) through (4XiiXf) of the affidavit accompanying this transmittal pursuant to 10 CFR 2.390(bX 1).

COPYRIGHT NOTICE The reports transmitted herewith each bear a Westinghouse copyright notice. The NRC is permitted to make the number of copies of the information contained in these reports which are necessary for its internal use in connection with generic and plant-specific reviews and approvals as well as the issuance, denial, amendment, transfer, renewal, modification, suspension, revocation, or violation of a license, permit, order, or regulation subject to the requirements of 10 CFR 2.390 regarding restrictions on public disclosure to the extent such information has been identified as proprietary by Westinghouse, copyright protection notwithstanding. With respect to the non-proprietary versions of these reports, the NRC is permitted to make the number of copies beyond those necessary for its internal use which are necessary in order to have one copy available for public viewing in the appropriate docket files in the public document room in Washington, DC and in local public document rooms as may be required by NRC regulations if the number of copies submitted is insufficient for this purpose. Copies made by the NRC must include the copyright notice in all instances and the proprietary notice if the original was identified as proprietary.

Southern Nuclear Operating Company (SNC)

Letter for Transmittal to the NRC The following paragraphs should be included in your letter to the NRC:

Enclosed are:

1. 6 copies of WCAP-16493-P, Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units 1 and 2," November 2005 (Proprietary)
2. 6 copies of WCAP-16493-NP, Revision 0, "Structural Integrity Evaluation of Reactor Vessel Upper Head Penetrations to Support Continued Operation: Vogtle Units 1 and 2," May 2006 (Non-Proprietary)

Also enclosed is Westinghouse authorization letter CAW-06-2157 with accompanying affidavit, Proprietary Information Notice, and Copyright Notice.

As Item 1 contains information proprietary to Westinghouse Electric Company LLC, it is supported by an affidavit signed by Westinghouse, the owner of the information. The affidavit sets forth the basis on which the information may be withheld from public disclosure by the Commission and addresses with specificity the considerations listed in paragraph (b) (4) of Section 2.390 of the Commission's' regulations.

Accordingly, it is respectfully requested that the information which is proprietary to Westinghouse be withheld from public disclosure in accordance with 10 CFR Section 2.390 of the Commission's regulations.

Correspondence with respect to the copyright or proprietary aspects of the items listed above or the supporting Westinghouse affidavit should reference CAW-06-2157 and should be addressed to J. A. Gresham, Manager, Regulatory Compliance and Plant Licensing, Westinghouse Electric Company LLC, P.O. Box 355, Pittsburgh, Pennsylvania 15230-0355.