.James Kim - Limerick - Phone Call Memo - Thursday, May 25, 2006 - 1:00 PM
1.11.1-----.-,--,-.----.----.P-,--
A age I From:
Edwin Forrest To:
James Kim Date:
05/25/2006 2:01:47 PM
Subject:
Limerick - Phone Call Memo - Thursday, May 25, 2006 - 1:00 PM Phone Call to Doug Walker, Limerick licensing, Requested by projects. Harold Rothstein and Paul Reichert participated from the Washington Group.
Limerick did an initial sensitivity study that showed they would have to reduce CR in leakage to 100 cfm in order to make the 5 REM limit. This is slightly higher than the tracer gas value, but does not provide much margin.
Limerick would like to propose taking partial credit for RERS mixing following the Bechtel curve in 2.5 minute increments from time 3 minutes to time 22.5 minutes when the curve reaches the 50 % mixing. At that time, the assumption would be conservatively a constant 50 % mixing for the remainder of the accident although mixing would actually be higher. Limerick would also reduce the CR in leakage to about 225 cfm. There would be no crediting for filtering in the 15.5 minute draw down period.
I responded to Doug, et. al, that this is something that could be considered, that it does appear to provide some basis for at least partial credit for mixing.
Ed Forrest 301-415-3755 CC:
Margie Kotzalas; Mark Blumberg; Robert Dennig
r:\\temn\\rWI0001n -TMP Page 1 P'Lt0mn(WAOAfli TMP Page 1]
Mail Envelope Properties (4475F10A.1B5:19: 35694)
Subject:
Creation Date From:
Created By:
Limerick - Phone Call Memo - Thursday, May 25, 2006 - 1:00 PM 05/25/2006 2:01:46 PM Edwin Forrest EBF@nrc.gov Recipients OWGWPOO2.HQGWDOO1 JSK (James Kim) nrc.gov OWGWPOO 1.HQGWDOO 1 RLD CC (Robert Dennig)
WMB 1 CC (Mark Blumberg) nrc.gov OWGWPOO2.HQGWDOO1 MXK5 CC (Margie Kotzalas)
Post Office OWGWPOO2.HQGWDOO1 OWGWPOO1.HQGWDOO1 OWGWPOO2.HQGWDOO1 Route nrc.gov nrc.gov Files MESSAGE Options Expiration Date:
Priority:
ReplyRequested:
Return Notification:
Concealed
Subject:
Security:
Size 1746 Date & Time 05/25/2006 2:01:46 PM None Standard No None No Standard Junk Mail Handling Evaluation Results Message is not eligible for Junk Mail handling Message is from an internal sender Junk Mail settings when this message was delivered Junk Mail handling disabled by User
c:\\temp\\GW}00001.TMP Page 2j Junk Mail handling disabled by Administrator Junk List is not enabled Junk Mail using personal address books is not enabled Block List is not enabled