LOP Instrumentation 3.3.£. 1 Table 3.3.8.1-1 (page 1 of 1)

Loss of Power Instrumentation REQUIRED CHANNELS SURVEILLANCE ALLOWABLE FUNCTION PER BUS REQUIREMENTS VALUE

1.

4160 V Essential Service System Bus 2

SR 3.3.8.1.3 2 2796.85 V and Undervoltage (Loss of Voltage)

SR 3.3.8.1.4

2.

4161) V Essential Service System Bus Undervoltage (Degraded Voltage)

a.

Bus Undervoltage/Time Delay 2

SR 3.3.8.1.1 2 3851 V and c 3881 V SR 3.3.8.1.2 with time delay SR 3.3.8.1.5 2 5.7 seconds and s 8.3 seconds

b. Time Delay (No LOCAW 1

SR 3.3.8.1.1 2 279 seconds and SR 3.3.8.1.2 s 321 seconds SR 3.3.8.1.5 I

Dresden 2 and 3 3.3.8. 1 -3 Amendment :°- 219/210