.r-

, -Z

', ChrisGrIe Lipzr - Re: Palisades Crane/Cask in set down update !

RPage 11 From:

To:

Date:

Subject:

John Giessner Jamnes Cameron; Magdalena Gryglak 10/13/05 6:18AM Re: Palisades Crane/Cask in set down update r

L

Update,

-the plug is out, and the yoke unhooked. They will be starting inspections/corrections of the crane and EATL. They are looking at inspecting the "scratch" on the crane support.

-Target is mid-day to be ready to say the crane is OK.

Unrelated to DFS

-also last night they lost the inverter (nonsafety related) Y210. This powers the PPC (computer) and ERDS (channel to NRC). They made an 8 hr report for loss of ERDS, they needed to take compensatory actions for moni':oring rod locations and flux patterns (all preplanned in procedures).

Jack

>>> Mac dalena Gryglak 10/12/05 11:35 PM >>>

The licensee reset the emergency brake at approximately 22:30 confirming that the main hoist brake was engaged prior to resetting the emergency brake. The main hoist brake held the load as expected (no other contingency actions needed to be taken). The cask was set at the bottom of the pool at approximately 24:00. The licensee will remove the shield plug (or is actually in the process of removing the shieli plug), unhook the yoke, park the crane, and perform further inspections. Some of the follow up actions include the need to readjust the EATL-Energy Absorbing Torque Limiter setting to a higher val je (the set point of 175 ft-lbs was the lower range value used which caused the crane to trip). Big Rock Point used approximately 202 ft lbs after resetting the EATL; their crane is exactly the same as the Palisades crane. During the loading activities last year, the EATL setting was approximately about 197.5 ft-lbs and no crane lock out occurred.

Thank you Magda Is CC:

Christine Lipa; Frances Ramirez; John Ellegood; L. Mark Padovan IlfolisUft in this record was deleted in accordance with the Freedom of Infomafion FOIA->-Em 23

ac tei p\\GW)0000 I.TMP Page 1 l1 Mail Envelope Properties (434E429C.682: 23: 3902)

Subject:

Creation Date:

From:

Created By:

Re: Palisades Crane/Cask in set down update 10/13/05 6:18AM John Giessner JBG~nrc.gov Recipients nrc.gov ch_pc,.CHDO CA], CC (Christine Lipa)

FCR CC (Frances Ramirez)

JAE CC (John Ellegood)

JLC (Jamnes Cameron)

MRD2 (Magdalena Gryglak) nrc.gov owf4_po.OWFNDO LMP CC (L. Mark Padovan)

Post Office chpo.CH DO owf4_po.OWFNDO Route nrc.gov nrc.gov Files MESSAGE Options Expiration Date:

Priority:

Reply Requested:

Return Notification:

Concealed

Subject:

Security:

Size 3548 Date & Time 10/13/05 06:18AM None Standard No None No Standard