ML060090291

From kanterella
Jump to navigation Jump to search

License Change Request S05-08 Containment Isolation Valves
ML060090291
Person / Time
Site: Salem  
(DPR-070, DPR-075)
Issue date: 12/09/2005
From: Tosch K
State of NJ, Dept of Environmental Protection
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NUREG-1482, Rev 1
Download: ML060090291 (1)


Text

Richard J. Codey Acting Governor <

Department of Environmental Protection Division of Environmental Safety and Health Radiation Protection and Release Prevention Element

-Bureau of Nuclear Engieering; P. O.Box 415 Trenton, New Jersey 08625-0415 Tel (609) 984-7700 Fax(609)984-7513-Bradley M. Campbell Commissioner

.' December 9, 2005 United States Nuclear Regulatory Commission

'Document Control Desk

-- --Washinton C2O55;.:.---5 0<:

 ;;"ear' S c W' i' -r:'-0 I,

I-

i 1_-

i .I 1,,

I 

Subject:

,Salem Generating Station Units 1 and 2 Docket Nos. 50-272 and 50-311 License Change Request S05-08

'r4~_:

. __z

.T A_ lrs

-ontaament isolation valves PSEG Nuclear LLC 'submitted the proposed change to the Salem Technical Specifications by letter to the NRC dated-September 26,2005. The proposed amendment would eliminate-the Surveillance.

Requirement for containment isolation valvs ithat are being returned to service after maintenance, repair or replacement as allowed by Section 4.4.2 of.NUREG-1482, Revision 1.

The BNE is opposed to the elimination of this surveillance requirement. Since NUREG-1482, Revision 1, allows for this surveillance to be eliminated only if certain conditions are met, we recommend that the surveillance requirement be revised as follows:

Each containment isolation valve shall be demonstrated OPERABLE prior to returning the valve to service after maintenance, repair or replacement work is performed on the-valve or its associated

pacttor, control ror powercir bypiefomance of a,-cycling test and,..

.verification ofisolation time, nless the conditions of Section 4.4.2 of NUREG-1482, Revision 1, aremet.-

If you need to discuss this subject. further, please contact Elliot Rosenfeld at (609) 984-7548.

Sincerely, Ken 'W. Tosch, Acting Assistant Director Radiation Protection and Release Prevention Element New Jersey is an Equal Opportunity Employer Recycled Paper