December 2, 2005 Mr. Mano K. Nazar Senior Vice President and Chief Nuclear Officer Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106

SUBJECT:

DONALD C. COOK NUCLEAR PLANT, UNIT 2 -

SUMMARY

OF THE STAFFS REVIEW OF THE STEAM GENERATOR TUBE INSERVICE INSPECTION REPORTS FOR THE END-OF-CYCLE 15 REFUELING OUTAGE IN 2004 (TAC NO. MC7015)

Dear Mr. Nazar:

By letter dated October 28, 2004, Indiana Michigan Power Company submitted the 15-day steam generator plugging report in accordance with Technical Specification (TS) Section 4.4.5.5.a. By letter dated February 25, 2005, Indiana Michigan Power Company submitted the 12-month steam generator tube inspection report in accordance with TS Section 6.9.1.5.

The Nuclear Regulatory Commission staff has completed its review of these reports and concluded that Indiana Michigan Power Company has provided the information required by Donald C. Cook Unit 2 TSs, and that no additional follow-up is required at this time. The staffs review summary of the reports is enclosed. Please contact me at 301-415-1451 if you have any questions.

Sincerely,

/RA/

Peter S. Tam, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-316

Enclosure:

As stated cc w/encl: See next page

ML053330032 OFFICE NRR/LPL3-1/PM NRR/LPL3-1/LA EMCB/SC NRR/LPL3-1/BC NAME PTam THarris LLund*

LRaghavan DATE 12/2/05 12/2/05 8/5/05*

12/2/05

  • SE transmitted by memo of 8/5/05.

Donald C. Cook Nuclear Plant, Units 1 and 2 cc:

Regional Administrator, Region III U.S. Nuclear Regulatory Commission 2443 Warrenville Road, Suite 210 Lisle, IL 60532-4352 Attorney General Department of Attorney General 525 West Ottawa Street Lansing, MI 48913 Township Supervisor Lake Township Hall P.O. Box 818 Bridgman, MI 49106 U.S. Nuclear Regulatory Commission Resident Inspector's Office 7700 Red Arrow Highway Stevensville, MI 49127 James M. Petro, Jr., Esquire Indiana Michigan Power Company One Cook Place Bridgman, MI 49106 Mayor, City of Bridgman P.O. Box 366 Bridgman, MI 49106 Special Assistant to the Governor Room 1 - State Capitol Lansing, MI 48909 Mr. John A. Zwolinski Safety Assurance Director Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106 Michigan Department of Environmental Quality Waste and Hazardous Materials Div.

Hazardous Waste & Radiological Protection Section Nuclear Facilities Unit Constitution Hall, Lower-Level North 525 West Allegan Street P. O. Box 30241 Lansing, MI 48909-7741 Lawrence J. Weber, Plant Manager Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106 Mr. Joseph N. Jensen, Site Vice President Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106

ENCLOSURE

SUMMARY

OF REVIEW BY THE OFFICE OF NUCLEAR REACTOR REGULATION STEAM GENERATOR TUBE INSPECTION REPORTS FOR THE END-OF CYCLE 15 REFUELING OUTAGE DONALD C. COOK NUCLEAR PLANT, UNIT 2 DOCKET NO. 50-316 By letter dated October 28, 2004 (ML043090491), Indiana Michigan Power Company (the licensee) submitted the 15-day steam generator plugging report in accordance with Section 4.4.5.5.a of the Technical Specifications (TSs). By letter dated February 25, 2005 (ML050630237), the licensee submitted the 12-month steam generator (SG) tube inspection report in accordance with TS Section 6.9.1.5.

Donald C. Cook (D. C. Cook) Unit 2 has Westinghouse Model 54F steam generators which are designated SG21, SG22, SG23, and SG24. All four steam generators were inspected during the fall 2004 refueling outage. The Westinghouse Model 54F SG consists of approximately 3,592 tubes which have an outside diameter of 0.875-inch and a wall thickness of 0.050-inch.

The tubes have been hydraulically expanded into the tubesheet and are supported by seven 1.12-inch-thick Type 405 stainless steel support plates which contain quatrefoil tube holes through which the tubes pass. The D. C. Cook Unit 2 SGs began operation in 1989 and have thermally-treated Inconel 690 tubing.

The licensee provided the scope, extent, methods, and results of D. C. Cook Unit 2 SG tube inspections in the documents referenced above. In addition, the licensee described corrective actions (i.e., tube plugging or repair) taken in response to the inspection findings.

Based on a review of the information provided, the Nuclear Regulatory Commission (NRC) staff concludes that the licensee provided the information required by the TSs. In addition, the NRC staff concludes that there are no technical issues that warrent follow-up action at this time since the inspections appear to be consistent with the objective of detecting potential tube degradation and the inspection results appear to be consistent with industry operating experience at similarly designed and operated units.

Principal Contributor: L. Miller Date: December 2, 2005