Drawing M545-1, Rev 69, Flow Diagram Heating, Ventilation, and Air Conditioning Reactor Building
ML053270148
Person / Time
Site: Columbia 
Issue date: 01/17/2002
From:
Energy Northwest
To:
Office of Nuclear Reactor Regulation
References
M545-1, Rev 69
Download: ML053270148 (1)


Text

NTS DWG NO.

SCALE APPROVED DESIGN CHECKED DRAWN REV.

K J

H G

F E

D C

B A

K J

H G

E F

D C

B 1

2 3

4 5

6 7

8 9

10 11 1

2 3

4 5

6 7

8 9

10 11 A

5208 ACFM INTERLOCK W/RHR PUMP 1 1/2" DRAIN (DIV. 2)

RHR P-2C PUMP RM. #4 1700 CFM 1700 CFM R14 R12 A

800 CFM 800 CFM RM. #5 LPCS PUMP (DIV. 1) 1 1/2" DRAIN W/LPCS PUMP INTERLOCK ACFM 9375 R11 A

1250 CFM 1250 CFM RM. #6 HPCS PUMP 1 1/2" DRAIN W/HPCS PUMP INTERLOCK ACFM 15,625 TI 1

RRA MV/I 1

RRA RRA 1

TE TI 2

RRA MV/I 2

RRA RRA 2

TE A H RRA-FN-1 RRA-FC-1 RRA-CC-1 REA-FD-7 ROA-FD-7 REA-FD-6 5HP M

ROA-FD-6 RRA-FN-5 RRA 1

TS RRA-FC-5 10HP M

RRA-CC-5 R15 A

1750 CFM 1750 CFM RM. #3 RCIC PUMP (DIV. 2)

ACFM 3125 5208 ACFM (DIV. 1)

RHR P-2A PUMP RM. #2 970 CFM 970 CFM A

R6 5208 ACFM INTERLOCK W/RHR PUMP 1 1/2" DRAIN (DIV. 2)

RHR P-2B PUMP RM. #1 1350 CFM 1350 CFM A

R7 REA-FD-5 RRA 2

TS RRA-FN-4 RRA-FC-4 RRA-CC-4 REA-FD-3 ROA-FD-3 RRA-FN-3 RRA-FC-3 RRA-CC-3 3HP M

3HP M

REA-FD-2 ROA-FD-2 RRA-FN-2 RRA-FC-2 RRA-CC-2 3HP ROA-FD-1 RRA-FN-6 RRA-FC-6 RRA-CC-6 2HP A H TS 18 RRA TI 18 RRA MV/I 18 RRA RRA 18 TE CRD PUMP ROOM AUX. COND PUMP ROOM R10 R9 C0439 2200 CFM 2200 CFM 4400 CFM 4400 CFM EL. 471'-0" EL. 471'-0" 7.5HP M

2000 CFM REA-FN-16 SMOKE PURGE FAN (PORTABLE TYPE)

E.D.

E.D.

E.D.

E.D.

FLEX DUCT FOR SMOKE REMOVAL (NORMALLY DISCONNECTED AND STORED)

REACTOR BUILDING EMERGENCY COOLING SYSTEM REACTOR BUILDING EMERGENCY COOLING SYSTEM 5050 CFM 5550 CFM 4070 CFM 6770 CFM SMOKE REMOVAL DUCT CONNECTION 1000 CFM CFM 900 NORTH VALVE ROOM R213 SOUTH VALVE ROOM R214 GENERAL AREA 3HR F.D.

3HR F.D.

REA-FD-4 ROA-FD-4 1900 CFM 2300 CFM 900 CFM 1000 CFM 6500 CFM M

3HP 1 1/2" DRAIN T

A C

A ROA-SPV-12 START ON ISOLATION SIGNAL F,A,Z MV/I 12 RRA TI 12 RRA RRA 12 TE RRA 12 TS R212 REACTOR BUILDING EMERGENCY COOLING SYSTEM D.C. MCC ROOM (DIV. I) 400 CFM RRA-FC-12 RRA-CC-12 SET AT 0.25" S.P.

INSTRUMENTS ARE TAGGED WITH FULL IDENTIFICATION AS FOLLOWS: e.g.

ROA 2

TS IS TAGGED ROA-TS-2 REA 1A dPT IS TAGGED REA-DPT-1A 3.

ISOLATION SIGNAL CODES A - REACTOR VESSEL LOW WATER LEVEL F - HIGH DRYWELL PRESSURE Z - HIGH RADIATION REACTOR BUILDING VENTILATION SYSTEM 4.

ASTERISK ( ) INDICATES INSTRUMENT SUPPLIED WITH ASSOCIATED EQUIPMENT.

5.

ALL PRESSURE AND INSTRUMENT ROOT VALVES ARE 3/4"GLOBE VALVES UNLESS NOTED OTHERWISE. ROOT VALVES FOR FLOW ELEMENTS ARE 1/4" SIZE.

6.

a. ALL DUCTWORK BETWEEN OUTERMOST ISOLATION VALVES AND REACTOR BUILDING PENETRATION AND ALL DUCTWORK DIRECTLY CONNECTED TO FAN COIL UNITS RRA-FC-1 THRU -6,-10,-11 THRU -14 IS CLASSIFIED AS FOLLOWS:

SIESMIC CATEGORY I QUALITY CLASS I

b. ALL DUCTWORK DIRECTLY CONNECTED TO AIR HANDLING UNIT RRA-AH-7 IS CLASSIFIED AS FOLLOWS:

SEISMIC CATEGORY II QUALITY CLASS II

c. ALL DUCTWORK HANGERS IN REACTOR BUILDING (UNLESS OTHERWISE NOTED)

ARE CLASSIFIED AS FOLLOWS:

SEISMIC CATAGORY I QUALITY CLASS II

d. ALL DUCTWORK IN REACTOR BUILDING (UNLESS OTHERWISE NOTED) IS CLASSIFIED AS FOLLOWS:

SEISMIC CATAGORY - MODIFIED SEISMIC II QUALITY CLASS II (SEE WNP-2 SPECS., SECTION 15A-4)

EL. 501'-0" EL. 501'-0" OPEN HATCH SHUTDOWN COOLING SUPPLY AREA R315 LOCK CRD EQUIPMENT LOOP "B" AREA SHUTDOWN COOLING GENERAL AREA WEST 400 CFM 300 CFM 300 CFM R306 R316 800 CFM 2100 CFM 1100 CFM 9950 CFM 13,520 CFM 1000 CFM OPEN HATCH EL. 522'-0" EL. 522'-0" 400 CFM 300 CFM 300 CFM MCC ROOM (DIV. 1)

REACTOR BUILDING EMERGENCY COOLING SYSTEM ACFM 5730 A

C A

T F.C.

3HP M

R411 START ON ISOLATION SIGNAL F,A,Z 1100 CFM SET AT 0.25" S.P.

3050 CFM CRD MODULES WEST 1900 CFM 50 CFM ELECTRONICS ROOM 1150 CFM GENERAL AREA 1800 CFM 1800 CFM TIP ROOM R308 850 CFM 450 CFM SHUTDOWN COOLING LOOP "A" AREA VALVE ACCESS AREA R313 R312 CFM 850 1300 CFM NEUTRON MONITORING DRIVE MECHANISM AREA EAST GENERAL AREA ROOM CRD REPAIR 400 CFM 1400 CFM 400 CFM R309 2200 CFM 900 CFM 400 CFM 850 CFM 450 CFM E.D.

A H 5730 ACFM 1 1/2" DRAIN MCC ROOM (DIV. 2)

REACTOR BUILDING EMERGENCY COOLING SYSTEM A

C A

T R410 ROA-FD-16 3HR F.D.

M 3HP START ON ISOLATION SIGNAL F,A,Z RRA 10 TE MV/I 10 RRA TI 10 RRA RRA-FC-10 RRA-FN-10 RRA-CC-10 3HR F.D.

ROA-FD-18 ROA-FD-19 ROA-FD-20 ROA-FD-21 PIPE SPACE R405 CRD MODULES EAST 3HR F.D.

800 CFM ROA-FD-17 SET AT 0.25" S.P.

RWCU PUMP ROOM "A" RWCU PUMP ROOM "B" ACCESS AREA 400 CFM 800 CFM 400 CFM 18,700 CFM 20,420 CFM 850 CFM 850 CFM 3750 CFM 6550 CFM 1100 CFM 3300 CFM R409 2500 CFM 800 CFM 3HR F.D.

1100 CFM 15,420 CFM 12,150 CFM 600 CFM 8870 CFM 11,920 CFM 600 CFM 3250 CFM R407 R406 1250 CFM 1250 CFM 1300 CFM 1100 CFM 600 CFM 50 CFM 1750 CFM PIPE SPACE R408 M545-2 M545-2 M545-2 M545-2 M545-2 1750 CFM RRA-FC-11 RRA-FN-11 ROA-SPV-11 RRA 11 TE MV/I 11 RRA TI 11 RRA RRA 11 TS RRA-CC-11 23,720 CFM 5150 CFM 11,920 CFM 18,700 CFM R412 2200 CFM 3HR F.D.

3HR F.D.

3HR F.D.

3HR F.D.

3HR F.D.

3HR F.D.

(A/6)

(A/6)

(A/5)

(A/5)

(A/3) 2.

NOTES 1.

FOR FLOW DIAGRAM LEGEND, SYMBOLS, AND ABBREVIATIONS, SEE DRAWING M501.

FSAR FIG.

2" SW A

2 1/2" SW A H ROA-FD-5 2 1/2" SW C

2" SW 2" SW 1 1/2" DRAIN E.D.

INTERLOCK W/RHR PUMP M

1 1/2" SW 1 1/2" DRAIN M

E.D.

INTERLOCK W/RCIC PUMP REA-FD-1 A H 2" SW RRA-FN-12 ROA-AD-12 400 CFM ROA-AD-10 REA-FD-19 2" SW A H E.D.

1 1/2" DRAIN 2" SW E.D.

RC REV DATE DESCRIPTION DWN CHK APVD APVD CHK DWN DESCRIPTION DATE REV APVD CHK DWN DESCRIPTION DATE REV APVD CHK DWN DESCRIPTION DATE REV HEATING, VENTILATION FLOW DIAGRAM AND AIR CONDITIONING REACTOR BUILDING R.B. CLEAVENGER 9-7-89 M545-1 SIGNATURE DATE TITLE REA-FD-16 63 DWG. M545 REDRAWN INTO DWG. M545 SHEETS 1 THROUGH 3 PER BDC 55-0931-0A-201 AND REVISED PER BDC 89-0141-0A-200.

69 FN/16 RMS AO 12 ROA RMS S12 RRA RMS S11 RRA AO 11 ROA ROA-AD-11 ROA-SPV-10 AO 10 ROA RMS S10 RRA RRA 10 TS INLET SAMPLE A H SAMPLE OUTLET MOBILE AIR PARTICULATE RADIATION MONITOR (SEE DWG. M893-3 FOR DETAILS)

RRA-SR-40 FIS 2

RRA RE 2

RRA RIS 2

RRA RR 2

RRA RMS RRA RRA RMS RRA RMS RRA RMS RRA RMS RRA RMS FN/1 FN/5 FN/4 FN/3 FN/2 FN/6 REA

/

/

90 3

6 SRP HSM H.S. McCLUER C.O. ROMINE S.R. PAYNE 3-6-90 3-6-90 3-6-90 TOP TIER M

3600 CFM 3100 CFM FIC 3A FE 3A M

REA 3A REA 3B REA REA REA-FN-3 REA-FU-3 REA-FL-3 REA-HF-3 dPIT dPIT 7-1/2HP CONN. FOR PORTABLE HEPA UNIT 4000 CFM RMS FN/3/2 FN/3/1 RMS REA REA REA-AD-3A 4000 CFM 16,420 CFM 500 CFM REV. PER BDC 89-0086-0D-212 (E-G/5-7,J/5-6).

PAA 64 RC MRG 5/

/90 11 dPI 3A dPI 3B 65 REV PER 89-0086-2D-A73 (G/7).

PAA REA REA

/

7 18 90

/

SRP GL REV PER 55-1362-0A-200 (B/1-4,8-11) 66 HL RC LS 5

24 91

/

/

LEGEND ALL VALVES SUFFIXED WITH A (TH) DENOTE A THROTTLED VALVE.

1.

67 REV. PER 55-1800-0A-302 (H/1-2).

PAA SRP MRG 68 REV. PER 94-09-030-0003 (H/1-2).

HL 7.

THESE VALVES SHALL BE CLASSIFIED AS FOLLOWED:

SEISMIC CATAGORY I QUALITY CLASS I CODE GROUP C SEISMIC CATAGORY I AIR SUPPLY PIPING & TUBING TO THESE VALVES SHALL BE:

CODE GROUP D QUALITY CLASS I 8/7/92 11/17/94 KL SW NORTHWEST COLUMBIA GENERATING STATION 69 1/17/02 REV PER 96-0132-OA-300 (G-H/3-4).

NT KL SRP