8 M512-4 N.T.S.
SIGNATURE DATE TITLE A
11 10 9
8 7
6 5
4 3
2 1
11 10 9
8 7
6 5
4 3
2 1
B C
D F
E G
H J
K A
B C
D E
F G
H J
K REV DESCRIPTION DWN CHK APVD APVD CHK DWN DESCRIPTION DATE REV APVD CHK DWN DESCRIPTION REV APVD CHK DWN DESCRIPTION REV REV.
DRAWN CHECKED DESIGN APPROVED SCALE DWG NO.
S.R. PAYNE 1-23-91 DIESEL OIL STORAGE TANK DO-V-2A DO-V-1A PI 11A PT 11A 1 1/2"DO(1)-1-1 3/4"DO(60)-1-5 DO-V-701A 1/2"DO(6)-1-1 RO 1A 2"
DO-FA-3A NOTE 2 NOTE 11 3"DO(57)-1-1 DO-P-1A DIESEL OIL DAY TANK LS 10A M
STICK MEASUREMENT CAP & NOZZLE FOR 2"
3"DO(56)-1-1 2"DO(56)-1-1 3/4"DO(56)-1-1 (L.C.)
DO-V-56A 1/4" NOTE 11 NOTE 2 3"DO(9)-1 DO-V-702A FOR CONT. SEE DWG. M512-2 (B/8,11) 1 1/2"DO(1)-1-1 1 1/2"DO(1)-1-3 DO-V-628(V)
DO-V-718A DO-V-4A DO-V-40A STICK MEASUREMENT PLUG & NOZZLE FOR (L)
(H)
L H
A LS 12A LS 11A DO-FA-1A NOTE 2 NOTE 11 2"DO(57)-1-3 VENT (D)
(D)
(D)
(D)
(D)
(D)
(D)
(D) 3/4"DO(3)-1-1 3/4"DO(3)-1-3 3/4"DO(3)-1-5 3/4"DO(3)-1-7 1"DO(2)-1-1 1"DO(2)-1-3 1"DO(2)-1-5 1"DO(2)-1-7 DO-V-7A DO-V-6A DO-V-614(V)
DO-V-611(V)
DO-V-612(V)
DO-V-613(V)
DO-V-610(V)
DO-V-609(V)
DO-V-615(V)
DO-V-616(V)
DO-V-617(V)
DO-V-618(V)
DO-V-627(V)
DO-V-14 1"DO(4)-1-2 1"DO(4)-1-1 1"DO(5)-1-2 (D)
(D)
(D) 2"DO(57)-1-6 NOTE 11 NOTE 2 DO-FA-4 LS 13 LS 14 A
H L
(H)
(L)
PLUG & NOZZLE FOR STICK MEASUREMENT DO-V-43 DO-V-12 1 1/2"DO(5)-1-1 DO-V-712 NOTE 2 NOTE 11 3/4" 2"
DO-V-56C (L.C.)
3/4"DO(56)-1-3 2"DO(56)-1-3 2"DO(56)-1-3 2"
CAP & NOZZLE FOR STICK MEASUREMENT M
LS 21 DIESEL OIL DAY TANK DO-P-2 3"DO(57)-1-5 NOTE 11 NOTE 2 DO-FA-2 2"
RO 2
1/2"DO(6)-1-3 DO-V-711 1 1/2"DO(5)-1-1 PT 16 PI 16 DO-V-10 DIESEL OIL STORAGE TANK DO-V-602(V)
DO-V-606(V)
DO-V-603(V)
DO-V-607(V)
DO-V-605(V)
DO-V-608(V)
DO-V-601(V)
DO-V-604(V) 3/4"DO(57)-1-22 DO-V-6B DO-V-7B 1"DO(2)-1-8 1"DO(2)-1-6 1"DO(2)-1-2 3/4"DO(3)-1-8 3/4"DO(3)-1-6 3/4"DO(3)-1-4 3/4"DO(3)-1-2 (D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
VENT 2"DO(57)-1-4 NOTE 11 NOTE 2 DO-FA-1B LS 11B LS 12B A
H L
(H)
(L)
PLUG & NOZZLE FOR STICK MEASUREMENT DO-V-40B NOTE 4 (THIS DWG)
DO-V-4B DO-V-718B DO-V-629(V) 1 1/2"DO(1)-1-4 1 1/2"DO(1)-1-2 FOR CONT. SEE DWG. M512-3 (A-B/11)
DO-V-702B NOTE 2 NOTE 11 1/4" DO-V-56B (L.C.)
3/4"DO(56)-1-2 2"DO(56)-1-2 3"DO(56)-1-2 2"
CAP & NOZZLE FOR STICK MEASUREMENT M
LS 10B DIESEL OIL DAY TANK DO-P-1B 3"DO(57)-1-2 NOTE 11 NOTE 2 DO-FA-3B 2"
RO 1B 1/2"DO(6)-1-2 DO-V-701B 3/4"DO(60)-1-10 1 1/2"DO(1)-1-2 PT 11B PI 11B DO-V-1B DO-V-2B DIESEL OIL STORAGE TANK DO-V-44 DO-V-5 (L.C.)
(L.C.)
(L.C.)
1 1/2"DO(1)-1-6 1 1/2"DO(1)-1-5 (D)
(D)
DO-V-11 DO-V-630 (DO-TK-3C)
(DO-TK-2)
(DO-TK-3B)
(DO-TK-1B)
(DO-TK-3A)
(DO-TK-1A)
FOR CONT. SEE DWG.
M512-1 (C/5) 2"DO(56)-1-3 NOTES:
FOR GENERAL NOTES AND LEGEND SEE DRAWING M512-1.
1.
2.
ALL INSTRUMENTATION ON THIS DRAWING TO BE IDENTIFIED BY PREFIX "DO" UNLESS SPECIFICALLY NOTED OTHERWISE.
EXAMPLE:
FO 3.
DIESEL OIL STORAGE AND DAY TANK VENTS TO BE PIPED OUTSIDE OF BUILDING.
4.
THIS DIESEL FUEL OIL VALVE IS NO LONGER FUNCTIONAL. INTERNAL PARTS HAVE BEEN REMOVED.
(M512-1)
(M512-1)
(M512-1) (M512-1)
(M512-1) (M512-1)
(M512-1)
(M512-1)
(M512-1)
(M512-1)
(M512-1)
(M512-1)
(M512-1)
(M512-1)
NOTE 4 (THIS DWG)
(M512-1)
(M512-1)
(M512-1)
(M512-1)
FLOW DIAGRAM DIESEL OIL &
MISCELLANEOUS SYSTEMS DIESEL GENERATOR BUILDING FSAR FIG.
3"DO(9)-1 3"DO(9)-1-1 3"DO(9)-1-2 3"DO(9)-1 3"DO(9)-1-7 1"DO(2)-1-4 DO-V-9B DO-V-8B DO-V-9A DO-V-8A DO-V-13 4"DO(9)-1-9 3/4"DO(57)-1-20 3/4"DO(57)-1-14 3/4"DO(57)-1-12 3/4"DO(57)-1-18 3/4"DO(57)-1-10 3/4"DO(57)-1-8 3/4"DO(57)-1-16 3/4"DO(57)-1-21 3/4"DO(57)-1-19 3/4"DO(57)-1-13 3/4"DO(57)-1-11 3/4"DO(57)-1-17 3/4"DO(57)-1-15 3/4"DO(57)-1-9 3/4"DO(57)-1-7 3/4"DO(57)-1-24 3/4"DO(57)-1-25 3/4"DO(57)-1-26 (VENT)
(VENT)
(VENT)
DO-V-41B DO-V-41A DO-V-42 NOTE 4 (THIS DWG) 3/4"DO(57)-1-23 3/8"PI(1)-ST-DO-LS-13 3/4"DO(5)-1-2 FILLING CONNECTION PLUG & NOZZLE 2"
3"DO(56)-1-2 2"
3"DO(56)-1-1 DO-ST-5 DO-V-58 NC 3"DO(9)-1-7 3"DO(9)-1-2 3"DO(9)-1-1 DO-V-61 DO-V-62 DO-V-63 DO-V-64 CONT FROM M513 (E/11)
DO-V-59 DO-V-57 (M512-1)
(M512-1)
NOTE 11 NOTE 2 NOTE 2 NOTE 11 (M512-1) (M512-1)
DO-F-5 DO-V-70 DO-V-69 PI 5
D0-V-71(TH)
DO-V-73 DO-V-72 DPIS 5
DO-AV-1 DO-AV-2 DPIS 6
DO-AV-3 DPIS 7
DO-F-7 DO-V-74 DO-V-77 DO-V-78 DO-V-79 DO-V-81 PI 6
(M512-1)
NOTE 22 NOTE 2 NOTE 2 NOTE 22 (M512-1) (M512-1)
DO-V-60 NOTE 2 NOTE 11 (M512-1) (M512-1)
CONT ON M513 (E/10)
DO-FI-1 L.C.
2" 3"
3" 3"
3" (L) 3" 3"
4" DO-P-8 3"DO(5)-1 3"DO(5)-1 3"DO(5)-1 3"DO(5)-1-3 3"DO(5)-1-3 3" DO(5)-1 3/4" 1/2" 1/2" 3/4" 1/4" 3/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/2" 3/4" 3/4" 3/4" LS 16 LS 15 1"
1" 3/4" DO(5)
DO(9)
DO(9)
DO(5)
DO(5)
DO(9)
DO(5)
FO(1)
DO(9)
DO(5)
DO(5)
DO(9)
DO(5)
DO(9)
DO(5)
FO(1) 1/2" PS 7
SEE DETAIL-1 (J-K/6-7) 3/4" 1/2" DO-V-83 SEE DETAIL-1 (J-K/6-7)
(J-K/6-7)
SEE DETAIL-1 DPIS "B"
SP DETAIL-1 SP (SEE TABLE 1 FOR EPN #)
1/4" 1/4" 1/4" 1/4" 1/4" 1/4" FILTER EPN TABLE 1 DO-V-725 "A"
DO-V-739 DO-V-742 DO-V-732 DO-V-729 DO-V-726 "B"
DO-V-743 DO-V-740 DO-V-737 "C"
DO-V-744 DO-V-741 DO-V-738 "D"
DO-V-733 DO-V-730 DO-V-727 "E"
DO-V-734 DO-V-731 DO-V-728 "F"
DO-F-5 DO-F-6 DO-F-7 EPN 3/4" 3/4" DO-V-724 DO-V-723 DO-V-746 MO 65 "D"
NOTE 11 NOTE 22 RMS FP/1 RMS P/7 EMERG. STOP EMERG. STOP M
M RMS P/8 (M512-1)
(M512-1) 3"DO(9)-1 1 1/2" 1"
3/4" (M512-1)
NOTE 22 NOTE 2 (M512-1)
NOTE 2 (M512-1)
NOTE 22 (M512-1) 3"DO(9)-1 1 1/2" 3/4" 1"
3"DO(9)-1 (M512-1)
(M512-1)
NOTE 22 NOTE 2 (M512-1)
NOTE 2 NOTE 22 (M512-1)
DO-V-87 DO-V-86 DO-V-85 2 1/2" DROP PIPE 4"DO(9)-1-6 2"
4"DO(9)-1-5 2"
2 1/2" DROP PIPE 2 1/2" DROP PIPE DO-V-65 NC NC NC NC 3"FO(1)-1 NC NC NC 3"FO(1)-1 3"DO(5)-1-3 NC NC NC 1"
1 1/2" 3/4" FILTER POLISHER SKID (DO-FP-1)
FD FD DO-V-84 DO-V-722 DO-V-631 ED ED ED DO-V-748 3"
(H) 3" DO-V-745 DO-V-747 DO-V-633 DO-SV-600 3"
DO-V-735 DO-V-736 1/2" 1/2" "C"
"E" "A"
"F" 3"
DO-F-6 DO-V-632 3/4" 3"
ALH A
LITS 15 LI 15 LE 15 SYS FAULT TO DO-LI-16 (ZN G/1)
(ZN G/2)
TO DO-LI-11A A
SYS FAULT LI 10A LITS 10A LE 10A AH AL AH LI 10B LITS 10B LE 10B TO DO-LI-11B SYS FAULT A
(ZN G/1-2)
AL AH AH AH LI 11A LI 11B LI 16 FROM DO-LITS-15 (ZN. B/3)
FROM DO-LITS-10B (ZN. F/11)
FROM DO-LITS-10A (ZN. A/11)
NOTE 5 (THIS DWG)
NOTE 5 (THIS DWG)
NOTE 5 (THIS DWG) 2 1/2" DROP PIPE INSTALLED INSIDE 4" PIPE, SEE DRAWING D-SPL-013 FOR DETAIL.
5.
AH JEFFREY R. MILLER 2-12-91 ROBY CLEAVENGER 4-14-94 R.L. PETERSON 4-14-94 FD-V-38 TO M.H. S4 M741-1 (B/3)
NO 4" YARD PIPING 1" ANTI-SIPHON LINE SERVER84\\00\\DWG RMS RMS RMS 7
12-3-99 REVISED PER 99-03-011-0002 (C/2), 99-03-011-0003 (C,H/10).
KL HL SRP 5
4-14-94 REDRAWN AND REVISED PER 83-0107-1A-237, 83-0107-1A-A51, 83-0107-1B-210, 83-0107-1B-A61, 83-0107-1C-200, 93-09-044-0027, 88-048-0A-370, 88-0048-0A-371 & 88-0048-0A-372.
6 5-4-95 REVISED PER 95-04-014-0003 (G/5-6).
SRP JRM RLP MJH HL RC DATE PAA HL 8
9-16-04 CORRECTED INCORPORATION OF 83-0107-1A-237 (B-C/1).