DCL-05-112, Request for Authorization to Use Delta Protections Respiratory Protection Suits and Assignment of Assigned Protection Factors

From kanterella
(Redirected from ML052920044)
Jump to navigation Jump to search

Request for Authorization to Use Delta Protections Respiratory Protection Suits and Assignment of Assigned Protection Factors
ML052920044
Person / Time
Site: Humboldt Bay, Diablo Canyon
(DPR-007, DPR-080, DPR-082)
Issue date: 10/07/2005
From: Jacobs D
Pacific Gas & Electric Co
To:
Document Control Desk, NRC/FSME
References
DCL-05-112, HBL-05-024, OL-DPR-07, OL-DPR-80, OL-DPR-82
Download: ML052920044 (67)


Text

Pacific Gas and Electric Company Donna Jacobs Diablo Canyon Power Plant Vice President P. 0. Box 56 Nuclear Services Avila Beach, CA 93424 805. 545.4600 October 7, 2005 Fax: 805.545.4234 PG&E Letter DCL-05-112 HBL-05-024 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Docket No. 50-275, OL-DPR-80 Docket No. 50-323, OL-DPR-82 Diablo Canyon Units I and 2 Docket No. 50-133, OL-DPR-7 Humboldt Bay Unit 3 Request for Authorization to Use Delta Protection's Respiratory Protection Suits And Assignment of Assigned Protection Factors

Dear Commissioners and Staff:

Pacific Gas & Electric Company (PG&E) is requesting authorization to use Delta Protection respiratory protection suits at Humboldt Bay Power Plant (HBPP) and Diablo Canyon Power Plant (DCPP). These suits are manufactured in France and have no National Institute for Occupational Safety and Health (NIOSH) approval for use as a respirator in the United States. Pursuant to 10 CFR 20.1703(b), PG&E must request authorization from the Nuclear Regulatory Commission (NRC) for the use of equipment that has not been tested or certified by NIOSH. Pursuant to 10 CFR 20.1705, PG&E must also request authorization from the NRC before using an assigned protection factor (APF) in excess of those specified in Appendix A of 10 CFR 20. Since these suits have no NIOSH approval for use as a respirator in the United States, PG&E is requesting authorization for their use as respiratory protection equipment and assignment of an APF.

PG&E has evaluated the Mururoa V4 MTH2 and Mururoa V4 F1 models of the respiratory protection suits manufactured in France. The Enclosure to this letter provides the documentation supporting the request for authorization for the Mururoa V4 MTH2 and V4 F1 suits. As described in the enclosure, approval of this request would improve worker safety in areas of airborne radioactivity and minimize the potential for facial/skin contamination and heat stress.

Authorization to use these suits will allow PG&E to proceed with procedure changes and complete training necessary for the use of the suits during decontamination and decommissioning efforts that are scheduled to take place at HBPP in the beginning of 2006. Therefore, PG&E is requesting NRC approval by December 31, 2005.

A member of the STARS (Strategic Teaming and Resource Sharing) Alliance PM S

S

/

Callaway

  • Comanche Peak.

Diablo Canyon.

Palo Verde.

South Texas Project

  • Wolf Creek

Document Control Desk PG&E Letter DCL-05-112 October 7, 2005 HBL-05-024 Page 2 As mentioned in Section 1.3 of the enclosure, the NRC has previously authorized use of Mururoa V4 suits for Duke Energy Corporation in a letter dated June 30, 2003 (ADAMS Accession No: ML031810133), for Entergy Operations, Incorporated in a letter dated February 1, 2005 (ADAMS Accession No: ML050330405), and most recently for Florida Power and Light Company in a letter dated April 8, 2005 (ADAMS Accession No: ML050980119).

PG&E has identified the following as commitments associated with this request:

1. The Mururoa V4 F1 and V4 MTH2 single-use suits will be integrated into the PG&E respiratory program using all instructions for use and emergency features supplied by the manufacturer except for the step that involves performing a visual inspection of the suit before removing the shipping protection. PG&E proposes to perform the visual inspection after the shipping protection has been removed. See the Implementation section of the enclosure for a more detailed explanation.
2. New lesson plans will be developed to train workers on Mururoa's features, donning, use and removal, cautions and use of the mouth strip and tear off strips for routine and emergency egress. PG&E will use all instructions for use and emergency features (see Implementation section of the enclosure) supplied by the manufacturer to develop these lesson plans, with the one exception noted in item 1 above.
3. Radiation Protection personnel will be provided additional training for selection, approval, issue, equipment set-up, operation and maintenance instructions for the Mururoa suits.
4. PG&E will use the Corrective Action Program to document any unexpected problems with the suits and track corrective actions taken. PG&E will report to the manufacturer any defects or incidences that may occur with the suits.
5. All suits are understood to be "single-use," and will be discarded after a single use.
6. The Mururoa V4 F1 and V4 MTH2 suits will not be used in environments that are immediately dangerous to life and health (IDLH) atmosphere.

If you have any questions, please contact Jack Chadwick at HBPP (707) 444-0878 or Mark Somerville at DCPP (805) 545-4007.

A member of the STARS (Strategic Teaming and Resource Sharing) Atliance Caltaway.

Comanche Peak.

Diabto Canyon.

Palo Verde.

South Texas Project.

WoLf Creek

Document Control Desk October 7, 2005 Page 3 PG&E Letter DCL-05-112 HBL-05-024 Sincerely, Don Jacobs Vice lesident, Nuclear Services Enclosure cc:

Bruce S. Mallett Emilio M. Garcia John B. Hickman Terry W. Jackson Girija S. Shukla Diablo Distribution PG Fossil Gen HBPP Humboldt Distribution A member of the STARS (Strategic Teaming and Resource Sharing) Alliance Callaway.

Comanche Peak

  • Diablo Canyon. Palo Verde.

South Texas Project.

Wolf Creek

Enclosure PG&E Letter DCL-05-112 HBL-05-024 REQUEST FOR AUTHORIZATION TO USE DELTA PROTECTION MURUROA V4 MTH2 and V4 F1 SINGLE-USE ENCAPSULATING SUITS

Enclosure PG&E Letter DCL-05-112 HBL-05-024 CONTENTS

1.0 INTRODUCTION

2 1.1 PURPOSE..............................

2 1.2 REGULATORY REQUIREMENTS...........................

2 1.2.1 Requirements of 10 CFR 20..............................

2 1.3 PRECEDENTS..............................

3 2.0 TECHNICAL JUSTIFICATION..........................

3 2.1 SCOPE.................

4 2.2 DISCUSSION..................................................................................5 2.2.1 Suit Construction.................

5 2.2.2 Safety Features of V4 F1 and V4 MTH2 Models.................... 6 2.2.3 Implementation.............................................

7

3.0 CONCLUSION

9

4.0 REFERENCES

10 5.0 ATTACHMENTS 5.1 Mururoa V4 Fully Enclosed Suits - General Description 5.2 European Standard EN 1073-1 for Ventilated Protective Clothing 5.3 Protection Factor Determined During Fit Test Exercises for V4 F1 5.4 Certificate No. 0073/197/162/12/97/0028 for Mururoa V4 F1 Issued by the Institute of Nuclear Protection and Security 5.5 Certificate No. 0073/197/162/01/96/0001 Issued for the Mururoa V4 MTH2 by the Institute of Nuclear Protection and Security 5.6 Protection Factor Determined During Fit Test Exercises for the Mururoa V4 MTH2 5.7 Instructions for Use 1

Enclosure PG&E Letter DCL-05-112 HBL-05-024

1.0 INTRODUCTION

1.1 PURPOSE Regulation 10 CFR 20.1703(b) indicates that all respiratory equipment that is not certified by the National Institute for Occupational Safety and Health (NIOSH) must be submitted to the Nuclear Regulatory Commission (NRC) for analysis and approval based on quantified test data. Regulation 10 CFR 20.1 705 requires authorization from the NRC before using an assigned protection factor (APF) in excess of those specified in Appendix A to 10 CFR 20.

Pacific Gas and Electric Company (PG&E) is requesting authorization to use the Mururoa fully enclosed suit models V4 F1 and V4 MTH2, manufactured by Delta Protection in France, at Humboldt Bay Power Plant (HBPP) and Diablo Canyon Power Plant (DCPP). PG&E is also requesting authorization to use an APF of 5,000 with the Mururoa V4 suits. Because of the advanced safety features for emergency breathing and emergency escape built into these models, PG&E may choose to use the Mururoa V4 F1 and V4 MTH2 suits without dedicated rescue personnel.

1.2 REGULATORY REQUIREMENTS 1.2.1 Requirements of 10 CFR 20 The following regulatory requirements are relevant to this request:

Regulation 10 CFR 20.1703(a) requires that if a licensee assigns or permits the use of respiratory protection equipment to limit the intake of radioactive material, the licensee shall use only respiratory protection equipment that is tested and certified by NIOSH.

Regulation 10 CFR 20.1703(b) allows the licensee to use equipment that has not been tested or certified by NIOSH, or for which there is no schedule for testing or certification to submit an application to the NRC for authorized use of this equipment.

Regulation 10 CFR 20.1703(f) requires provision of standby rescue persons, whenever an unaided individual would have difficulty in extricating himself or herself from an atmosphere-supplying suit.

2

Enclosure PG&E Letter DCL-05-112 HBL-05-024 Regulation 10 CFR 20.1705 requires the licensee to obtain authorization from the NRC before using an APF in excess of those specified in Appendix A to Part 20.

Regulation 10 CFR 20 Appendix A, APFs for Respirators, lists as item 11, atmosphere supplying respirators (particulate, gases and vapors), suit in a continuous flow operating mode. No NIOSH approval schedule is currently available for atmosphere supplying suits. This equipment may be used in an acceptable respiratory protection program as long as all the other minimum program requirements, with the exception of fit testing, are met (i.e., 10 CFR 20.1703).

Therefore, based on the above requirements, PG&E requests authorization to use the Mururoa V4 F1 and V4 MTH2 respiratory protection suits and an APF of 5,000 for the suits.

The technical justification demonstrates that there will be no undue hazard to life or property.

1.3 PRECEDENTS The NRC has previously authorized use of Mururoa V4 suits for Duke Energy Corporation, Entergy Operations, Inc., and most recently for Florida Power and Light Company. The following table summarizes the date of the NRC approval letters, the NRC's ADAMS accession number for each of the approval letters, the Mururoa suit model that was approved for each company and the APFs approved by the NRC per each company's request.

I Previously Approved Authorization Requests I

Date of ADAMS Mururoa Company NRC Accession Model(s) iAuthorized IApproval for Approval IApproved I APE J Letter Letter 1

Duke 6/3012003 ML031810133 V4 F1 2,000 Energy V4 MTH2 2,000 Florida V4 F1 5,000 Power and 4/8/2005 ML050980119 Light V4 MTH2 5,000 Entergy 2/1/2005 ML050330405 2,000 Operations V4 MTH2 3

Enclosure PG&E Letter DCL-05-112 HBL-05-024 In addition, the Mururoa V4 F1, V4 MTH2 and similar suits are widely used in western European nuclear power plants. These suits are also sold in China, South Africa, and South America. The Mururoa V4 MTH2 model was approved for use in 1996, and the Mururoa V4 F1 was approved for use in 1997.

4

Enclosure PG&E Letter DCL-05-112 HBL-05-024 2.0 TECHNICAL JUSTIFICATION 2.1 SCOPE PG&E reviewed the following documents from Delta Protection:

(a)

Mururoa V4 Fully Enclosed Suits - General Description (Attachment 5.1)

(b)

European Standard EN 1073-1 for ventilated protective clothing (Attachment 5.2)

(c)

Protection Factor determined during fit test exercises for V4 F1 (Attachment 5.3)

(d)

Certificate No. 0073/197/162112/97/0028 for Mururoa V4 F1 issued by the Institute for Nuclear Protection and Security (Attachment 5.4)

(e)

Certificate No. 0073/197/162/01/96/0001 issued for Mururoa V4 MTH2 by the Institute for Nuclear Protection and Security (Attachment 5.5)

(f)

Protection Factor determined during fit test exercises for V4 MTH2 (Attachment 5.6)

(g)

Instructions for Use - Mururoa V4 MTH2 and V4F1 (Attachment 5.7)

PG&E also physically inspected the Mururoa V4 F1 and V4 MTH2 suits.

The European Standard EN 1073-1 (Attachment 5.2) requires that suit material be tested for resistance to abrasion, flex cracking, puncture, blocking, tear and flammability, strength of seams, joins and assemblies, damage resistance of exhaust valves, designed flow rates for pressure range of supplied air, noise level and quality of the visor. According to the testing standard, three workers should perform standard exercises; each wearing two different suits inside a chamber filled with a test agent (Sodium Chloride), and measure the leakages during the exercise regimen lasting 20 minutes.

Operating parameters are set to manufacturer's instructions. Standard exercises include walking on a treadmill at 2 miles per hour (mph)

(3 minutes), moving arms up and down above head while looking upward (3 minutes), and squatting continuously (3 minutes). To ensure worker's comfort, two additional practical exercises, walking at 2 mph (5 minutes), and loading a bucket with wood chips from the base of a hopper and emptying it into the opening on top (15 minutes), should be performed by two workers at specified air flow rates.

Certificate No. 0073/197/162/12/97/0028 (Attachment 5.4) states that the Mururoa V4 F1 passed in all categories tested and provided a protection 5

Enclosure PG&E Letter DCL-05-112 HBL-05-024 factor greater than 50,000. Certificate No. 0073/197/162/01/96/0001 (Attachment 5.5) states that the Mururoa V4 MTH2 passed in all categories tested and provided a protection factor greater than 50,000. Please note that the term protection factor used in the European Standard is equivalent to the fit factor used in the United States and is not the same as the APF used in 10 CFR 20. Based on a review of the manufacturer's documentation, the Mururoa V4 F1 and V4 MTH2 suits represent a better design than the currently approved bubble hood and rain suit combination and provide better worker protection. This data supports an APF of 5,000.

2.2 DISCUSSION 2.2.1 Suit Construction The Mururoa suit models V4 F1 and V4 MTH2 meet International Standards Organization (ISO) 8194 and EN 1073-1 standards and the manufacturer is ISO 9001 certified. The manufacturer indicates that approximately 60,000 Mururoa garments/suits are used by European nuclear power plants each year.

The Mururoa single-use suits have the following desirable features that are not available in the bubble hoods and rain suits manufactured in the United States:

(1) One piece single-use suit that includes welded gloves and booties with tie straps (2) Fire proof (up to 650C)

(3)

Made of PVC or Ethyfuge with reinforced elbows, knees and crotch areas (4)

Dual zippers - metal zipper inside and plastic zipper outside (5) Helmet made of clear PVC material that provides distortion-free vision and large enough for wearing a headset (6)

Welded sleeve to insert communication cable (7)

A removable strip near the mouth that could be used for emergency breathing in case of loss of supplied air (8)

An egress strip stretching from left arm, over the head, to right arm that is used for undressing and for self-rescue in an emergency, such as loss of supplied air (9)

Air intake located at the waist with a built-in regulator that can adjust, but not block, air flow 6

Enclosure PG&E Letter DCL-05-112 HBL-05-024 (10) Two exhaust valves that provide ventilation, and also protect from overpressure (11) Very low noise level at maximum air flow (12) Air flow to hands, feet, face and chest The Mururoa V4 F1 suit shall be supplied with air at 85 pounds per square inch gauge (psig) measured at the inlet. Air hoses of any length may be used with the Mururoa V4 F1 as long at the required inlet pressure is provided. A regulator at the inlet can adjust the air flow from 41 cubic feet per minute (cfm) maximum to 9 cfm at the minimum. The regulator cannot shut off the air supply to ensure user safety. Noise level is kept between 76 decibels (dB) at maximum air flow and 58 dB at minimum air flow. Air flows through manifolds to the chest, hands and feet. There are two exhaust vents on the back, one behind the neck and one at the lower back. The exhaust vents have patented magnetic seals to prevent any aspiration of contaminants if supplied air is lost. The suit is made of nonflammable PVC, but should not be brought in direct contact with any material colder than 41 OF or hotter than 1400F. Open flames or sparks could melt or perforate the skin. The suit has a three year shelf-life and is required by the manufacturer to be stored between 320F and 1400F. The Mururoa suit is approved for use with many different fittings in Europe and can be fitted with Schrader, Foster or CEJN fittings.

The Mururoa V4 MTH2 suit is made of Ethyfuge material which is fully incinerable. This material is more flexible than the PVC used in the V4 F1 suit. The Mururoa V4 MTH2 is constructed the same way as the V4 F1 suit.

Breathing air is required at the same pressure (85 psig). The regulator can adjust air flow between 9 cfm and 41 cfm. Noise level varies from 58 dB at minimum air flow to 76 dB at maximum air flow. There are two additional air vents near the chin for cooling the face. The suit is also fire-retardant and can be used in ambient temperatures up to 1400F. Storage requirements are the same as for the V4 F1 suit. The V4 MTH2 suits are also available with multiple fittings.

2.2.2 Safety Features of V4 F1 and V4 MTH2 Models Both Mururoa suit models are light-weight (2.5 pounds), made of fire-retardant material and can be used in temperatures up to 1400F. Contact with open flames or grinding/welding sparks is prohibited. Built-in gloves, booties with binding ties, reinforced elbows, knees and crotch protect against accidental tear, puncture and cracking. A transparent helmet with a six inch by eight inch clear face plate provides a distortion-free view. Dual magnetic ventilation valves provide needed ventilation and relief of excess pressure in 7

Enclosure PG&E Letter DCL-05-112 HBL-05-024 case suit is squeezed or pinched unexpectedly. Noise level at maximum air flow is less than 80 dB. Length of air hose supplying Grade D breathing air is not stipulated, but the pressure of air at inlet is required to be 85 psig for both the V4 F1 and V4 MTH2 suits. Air flow can be adjusted by the user for his/her comfort, but cannot be shut off. In case of loss of air, the user can remove the mouth strip and move the opening close to his face, or enlarge the opening, to breathe outside air. Altemately, the user can pull the escape strip from either forearm, over the head and towards the other forearm, and rip the suit in two halves. This escape strip is normally used for egress from the suit when the work activity has been completed.

The Mururoa suit's design does not permit its use in an immediately dangerous to life and health (IDLH) atmosphere. PG&E plans to use this suit for protection against radioactive particulate contamination only and not in IDLH situations. The Mururoa suit is also not designed for use with any personal cooling units such as a Vortex tube, but can be used with a cooling vest supplied by the manufacturer, if desired.

2.2.3 Implementation PG&E has a respiratory program in full compliance with 10 CFR 20. The Mururoa V4 F1 and V4 MTH2 suits will be integrated into PG&E's respiratory program using all instructions for use and emergency features (see attachments 5.1 and 5.7) supplied by the manufacturer with one exception.

Under the Dressing section of the Instructions for Use, the manufacturer describes performing a visual inspection of the suit before removing the shipping protection, which includes cardboard on the visor and inside the garment, and removable plastic protection on the visor. PG&E proposes to perform this visual inspection of the suit and its components after the shipping protection material has been removed. This will allow removing the shipping protection material outside of the contaminated area, thus, reducing the potential for radioactive waste. According to the manufacturer, both the cardboard and the plastic are used solely to maintain the integrity of the visor during transit and storage.

The Mururoa V4 Fl and V4 MTH suits are single-use suits, and each suit will be discarded after a single use.

New lesson plans will be developed to train workers on Mururoa's features, donning, use and removal, cautions and use of mouth strip and tear off strips for routine and emergency egress.

Radiation Protection personnel will be provided with additional training for the selection, approval, issue, equipment set-up, operation and maintenance 8

Enclosure PG&E Letter DCL-05-1 12 HBL-05-024 instructions for the Mururoa suit. The safety features of the Mururoa suits, namely the tear-off mouth strip and the emergency tear-off strip, make it unnecessary for any standby rescue person to be present. Further justification for requesting exemption from the rescue person provision includes the fact that workers wearing air-supplied suits are typically under continuous surveillance by Radiation Protection technicians using remote video monitoring or under direct Radiation Protection surveillance at the job location due to radiological conditions. Additionally, in many cases, workers are in direct contact with Radiation Protection via audio headsets. The ability to eliminate the rescue worker is also an As Low As Reasonably Achievable (ALARA) consideration since the work areas where air-supplied suits are used are typically areas with high surface and airborne contamination levels.

Decontamination activities in enclosed areas are specifically targeted for the use of the Mururoa suit. In addition, the suits will offer excellent protection at HBPP with respect to high alpha contamination concerns during decommissioning use.

PG&E will use the Corrective Action Program to document any unexpected problems with the suits and track corrective actions taken. PG&E will communicate problems associated with the suits, if they arise, to the manufacturer to ensure that operating experience is shared with other users.

A relationship with the manufacturer will also be developed that allows operating experience from other users to be incorporated into PG&E processes. PG&E will share this experience with the NRC and other utilities that may be interested in the Mururoa suits. PG&E will advise the manufacturer and the NRC as to any defects or concerns regarding the suits and their function. Delta Protection has in place a vendor-user alert system to report any deviations or deficiencies within the product or manufacturing process should they arise. The manufacturer is subjected to checks from the Institute for Nuclear Protection and Security (IPSN) to insure the product has no risk of injury to the user. A second organization called ASQUAL performs annual inspections of the factory to certify that the product manufactured is of the same quality approved by the IPSN Notified Body. Several destructive/nondestructive tests are performed by the manufacturer for each order received from clients. Any defects reported by clients, investigations and corrective actions are documented. Customers are notified of any problems and products are recalled if necessary. This information is made available to ASQUAL for their annual inspections.

PG&E currently uses Powered Air Purifying Respirators (PAPR) for jobs involving high potential for skin contamination from discrete radioactive particles and to prevent intake of airborne contaminants. Because the PAPR covers only the face, workers have to wear protective clothing consisting of coveralls, a hood, gloves, shoe covers and tape for sealing. Plastic outer 9

Enclosure PG&E Letter DCL-05-112 HBL-05-024 garments may also be required if working in a wet environment. The chance of cross contamination during undressing and exit from contaminated areas is high. The Mururoa V4 F1 and V4 MTH2 suits offer a better alternative with their unitized construction and ease of removal and should protect the worker much better against facial/skin contamination and airborne radioactivity, while allowing the worker complete freedom of movement and minimizing heat stress. Approval of an APF of 5,000 for the Mururoa V4 F1 and V4 MTH2 air-supplied suits would allow use of the suits in efforts to control contamination incidents, prevent intakes, and minimize heat stress during decontamination and decommissioning evolutions at PG&E's HBPP and during steam generator replacement and reactor head replacement at DCPP.

10

Enclosure PG&E Letter DCL-05-112 HBL-05-024

3.0 CONCLUSION

Based on the physical inspection of the suits and vendor supplied documentation, PG&E has determined that the Mururoa air-supplied suits offer a safer and more efficient means to protect workers in areas of high radiological contamination, in areas where there is a potential for airborne contamination, and during evolutions which may result in worker heat stress.

The existing rain suits and bubble hoods provide cooling only to the head and force workers to wear the ensemble in a manner that makes self-rescue nearly impossible, thus, requiring a rescue worker to be stationed nearby.

Ease of removal of the Mururoa suit provides for more desirable self-rescue features, and provides a means to undress that minimizes the potential for personnel contamination events.

Pursuant to 10 CFR 20.1703(b), PG&E is hereby requesting authorization to use the recently NRC approved Mururoa V4 F1 and V4 MTH2 respiratory protection suits that are manufactured by Delta Protection in France.

Pursuant to 10 CFR 20.1705, PG&E is also requesting authorization to use an APF of 5,000 with the Mururoa V4 F1 and V4 MTH2 suits. Additionally, the Mururoa suits have advanced safety features for emergency breathing and emergency escape. These advanced features allow self-rescue during emergencies to be a reasonable expectation. Therefore, PG&E may choose to use the Mururoa V4 F1 and V4 MTH2 suits without dedicated rescue personnel present. All test results indicate that this request is reasonable, is authorized by regulation, and will not result in undue hazard to life or property.

11

Enclosure PG&E Letter DCL-05-112 HBL-05-024

4.0 REFERENCES

1. Regulation 10 CFR 20.1703, "Use of individual respiratory protection equipment"
2. Regulation 10 CFR 20.1705, "Application for use of higher assigned protection factors"
3. Regulation 10 CFR 20.2301, "Applications for exemption"
4. Appendix A to 10 CFR 20, "Assigned Protection Factors for Respirators"
5. Regulatory Guide 8.15, "Acceptable Programs for Respiratory Protection,"

Rev. 1

6. NUREG-0041, "Manual of Respiratory Protection Against Airborne Radioactive Material"
7. European Standard EN 1073-1 (January 1998) (Attachment 5.2)
8. EC Type Examination Certificate No. 0073/197/162/12/97/0028 for the Mururoa V4 F1 suit dated December 10, 1997 (Attachment 5.4)
9. EC Type Examination Certificate No. 0073/197/162/12/96/0001 for the Mururoa V4 MTH2 suit dated January 10, 1996 (Attachment 5.6) 12

Enclosure.1 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.1 Mururoa V4 Fully Enclosed Suits - General Description Total Number of Pages in this

Attachment:

5 (Not Including This Page)

Enclosure.1 PG&E Letter DCL-05-112 HBL-05-024 N": Do I USAf 1 MUJRUROA

/

INDICE: a V4 FULLY ENCLOSED SUr D

DATE DArPUCATIN :06109/01 GENERAL DESCRIPTION DELTA PROTECTIOtI3 PAGE :114 MURUROA SUIT The Mururoa suit is a single use garment designed to be used in radioactively contaminated environments. It has been widely used in western European Nuclear Power Plants for more than 20 years. uithout any major problem (the French state company: Electricitd de France use 60,ODO garments each year).

The Mururoa suit is a fully enclosed PVC plastic, supplied-air and pressurized suit, that offers excellent protecticon factor ( -100,000) against any solid, liquid, or gas pollutant. minimizing disoomfort and heat stress and increasing the workees ceficiency.

The Mururoa suit is CGE. approved and complies with CE stancard EN.1073-1 'Protective clothing against Radioactivo Contaminationm It also fulfils the requirements of the I.S.O. 8194 standard 'Radiation ProtecUon-Clothing for protbcion against Radioactva contamination-Design selection,testing and user 1

Enclosure.1 PG&E Letter DCL-05-112 HBL-05-024 N0: Do / USA I 1 M URU ROA INDICE: a V4 FULLY ENCLOSED SIIT DATE DAPFUCATION :060901D GENERAL DESCRIPION D

TCTIQA GENERL DESRIPTIN

-@04(6891836 PAGIE:214 VENhTILATION I EXHAUST In the supplied-air Mururoa suit, the ventilation system is composed or An airflow control valve, preset to a minimum flow of 250 litrestminuto (9 CFM) at 3 bar (42 PSI G). located on the right hip and covered with a protection flap. This flow can be adjusted, from 250 to 1150 litres (9 CFM to 41 CFM) per minute. 1150 litres is obtained wth the top fuilly opened at the feeding pressure of 6 bar (85 PSIG) (refer to graph in annex 11).

A silencer bag which attenuates the noise level less than 58 dBa at 250 litres/minutes to 76 dBa at 1150 litreslrninute.

A manifold system welded to the suit and distributing the air to the helmet, the legs and the arms.

An exhaust by two world patented valves placed in the helmet and in the back. These valves ensure a remarkable airtight seal in case of accidental air-feed cut off, or when putting the suit in under pressure through abrupt movements. The valves regulata the overpressure in the garment between 3 mbar (0.042 PSIG) and 10 mbar (0. 142 PSIG)

For supply air pressure between 3 bar (42 PSIG) and 0 bar (85 PSIG)

The benefits of this system are

- High heat removal through stpeuior airflow

- Non irritating diffuse ventilation

- Resistance free breathing

- High level dt comfort for long and strenuous jobs in contaminated areas

- Very low noise level

Enclosure.1 PG&E Letter DCL-05-112 HBL-05-024 N°. DoUSAf 1 MURUROA I

INDICE: a V4 FULLY ENCLOSED SUrr

.T DATE DAPPUCATI)N :06f09O01 DELTA PROTECT1O0V GENERAL DESCRIPTION 1:1046s 891836 PAGE :3/4 DESIGN CHARACTERISTICS One pbce PVC, fire proof suit. (Thickness a)l100mm for technical data coeamrlng the rnaterlal, refer Annex I of this docurrnt)

WeQ J PVC goves Incorporated arerboots Wth strengthened sole Blnding tes on the overboots Reinforced elbows, knee 3 and crotch Dual zippor syslrm:

- metal zipper for mechanical strwngth

- PVC zipperfor air and gas tjglr&ss (0.30 PVC thicknesa)

Suppb transparent PVC hahrlot, ftiod wth a transparont distortion frea, PVC face platc x 86 ivirg almost the 53me optical qualty as qlaEB.

Oicic release strip from forearm, overhead to forearm, for easy removal. This Is used both for undressing or emerrrncy egress. (Emergency egress takes less than 3 seconds)

Qick release strip for access tb the mouth.

We ed sleeve for communication cable.

Enclosure.1 PG&E Letter DCL-05-112 HBL-05-024 N": DOI USA/ I IN°: DICESf a

MURUROA Pt INDICE: aV4 FULLY ENCLOSED SUIT CATE D'APFUCATION :06109101 DELTA PROTECT1OI'

9GENERAL DESCRIPTION PAGE :414 GENERALCONSIDERAllONS THE MURUROA SUIT IS AVAILABLE IN SIX SIZES Size 0 1,55 m 1,62 meter 5 feet I inch 6 feet 4 inches Size 1 1,60 1,68 meter 573 6-6" Size 2 1,68 1.74 meter 56" 5'8t Size 3 1,74 1,2 meter 58" 6'0" Size 4 1,82 1.92 meter 6'0 2

6'3" Size 6 1,92

)

2,05 meter 673t OB But if any individual selcts a suit size different from the recommended size, the operating and safety charaderstics will not change.

WEIGHT 1200 grams (2.64 LBS)

FEEDING PRESSURE 6 bar (85 PSIG)

FLOW 450 up to 1150 Lit/minute (16 -41 CFM)

STORAGE The sut should be used by the thrd year from the date of manufacture.

It must be stored in its original packaging.

The storage temperature has to stay between 0WC and 60*C (32OF - 1400F) fthe storage temperature was bebw 50C (410F) the suit must be stored approximately 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> at a room temperature until the suit become flexile.

The usage temperature range + 50 C and + 550C (410 - 131°F) depends on air fed temperature

Enclosure.1 PG&E Letter DCL-05-112 HBL-05-024 N": DoIUSAI 1 MURUROA

/k INDICE: a V4 FULLY ENCLOSED SUrT OATE DAPPUCATION :06109101 DELTA PROTECTION JENERAL DESCRIPTION

.*('4(5 89 1836 PAGE :514 MATERIAL PROPERTIES Technical characteristicof PVC material 20100 mm using French standards, which would correspond to ANSI standards.

Characterstkc Standards Resuts l

Unfts Density NFT51063 1.38 gmlcm3 Traction Resistance NFT 54102

> 143 NWomr Stretch before tear NFT 54102

> 178 Tear resistance NFT 46007

> 45 Nlcn?

Weld resistance than material resistance NFT 54122 Pel$0 Tear65 Resistance to cold NFT 51102

-10 aC Vapour permeability NFH 00030 34.1 grm2r24h Votility on a&civatd charnal NFT 51167

<6 Spark perforation NFC 26225 9.2 KV

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.2 EUROPEAN STANDARD EN 1073 FOR VENTILATED PROTECTIVE CLOTHING Total Number of Pages in this

Attachment:

12 (Not Including This Page)

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 EN 1073-1 EUROPEAN STANDARD NORME EUROPEENNE EUROPEAISCHE NORM January 1998 ICS 13.280; 13.340.10 Descriptors: Personal protective equipment, clothing, radioactive contamination.

English version Protective clothing against radioactive contamination Part 1: Requirements and test methods for ventilated protective clothing against particulate radioactive contamination Wtements de protection contre la contamination radioactive - Partie 1:

Exigences et methodes d'essai des vetements contre la contamination radioactive sous forme de particules Schutzkleidung gegen radioaktive Kontamination -Teil 1: Anforderungen und Priifverfahren fur beliiftete Schutzkieidung gegen radioaktive Kontamination durch feste Partikel This European Standard was approved by CEN on 1997-11-23. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CEN member.

The European Standards exist in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, the Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, the Netherlands, Norway, Portugal, Spain, Sweden, Switzerland, and the United Kingdom.

CEN European Committee for Standardization Comite Europeen de Normalisation Europaisches Komitee fur Normung Central Secretariat: rue de Stassart 36, B-1050 Brussels

© 1998. CEN -Ail rights of exploitation in any form and by any means reserved worldwide for CEN national members.

Ref. No. EN 1073-1 :1998 E 1

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 2 EN 1073-1 :1998 Contents Foreword...............................

.2 1 Scope

.3 2 Normative references

.3 3 Definitions

.3 4 Requirements

.4 5 Test methods

.8 6 Marking.10 7 Information supplied by the manufacturer.10 Annex A (normative)

Activity sequence for the testing of the protection factor

.11 Annex ZA (informative)

Clauses of this European Standard addressing essential requirements or other provisions of EU Directives.12 Foreword This European Standard has been prepared by Technical Committee CENITC 162 "Protective clothing including hand and arm protection and lifejackets", the secretariat of which is held by DIN.

This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by July 1998, and conflicting national standards shall be withdrawn at the latest by July 1998.

This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association and supports essential requirements of EU Directive(s).

For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this standard.

The annex A is normative and contains the activity sequence for the testing of the protection factor.

Further parts of this standard will deal with requirements and test methods for unventilated protective clothing and protection against liquids and gases.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.

2

Enclosure.2 PG&E Letter DCL-05-1 12 HBL-05-024 Page 3 EN 1073-1 :1998 1 Scope This European Standard specifies the requirements and test methods for ventilated protective clothing protecting the wearer against particulate radioactive contamination.

This European Standard does not apply for the protection against ionizing radiation and the protection of patients against contamination with radioactive substances by diagnostical and/or therapeutical measures.

2 Normative references This European standard incorporates by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European standard only when incorporated in it by amendment or revision. For undated references the latest edition of the publication referred to applies.

EN 146 Respiratory protective devices - Powered filtering devices incorporating helmets or hoods - Requirements, testing, marking EN 270 Respiratory protective devices - Compressed air line breathing apparatus incorporating a hood - Requirements, testing, marking EN 340 Protective clothing - General requirements EN 530 Abrasion resistance of protective clothing material - Test methods EN 863 Protective clothing - Mechanical properties - Test method: Puncture resistance prEN 943-1 Protective clothing for use against liquid and gaseous chemicals, including liquid aerosols and solid particles -

Performance requirements for ventilated and non-ventilated gas-tight (Type 1) and non-gas-tight (Type 2) protective clothing EN 1146 Respiratory protective devices for self-rescue - Self-contained open-circuit compressed air breathing apparatus incorporating a hood (compressed air escape apparatus with hood) - Requirements, testing, marking EN 25978 Rubber-or plastics-coated fabrics - Determination of blocking resistance (ISO 5978:1990)

EN 29073-4 Textiles - Test methods for nonwovens - Part 4: Determination of tear resistance ISO 5082:1982 Textiles - woven fabrics - Determination of breaking strength - Grab method ISO 7854 Rubber-or plastics-coated fabrics - Determination of resistance to damage by flexing 3 Definitions For the purposes of this standard, the following definitions apply:

3

Enclosure.2 PG&E Letter DCL-05-1 12 HBL-05-024 Page 4 EN 1073-1 :1998 3.1 Protective clothing against radioactive contamination Protective clothing intended to provide protection to the skin and if required to the respiratory tract against radioactive contamination.

3.2 Ventilated protective clothing (against particulate radioactive contamination)

Protective clothing which is supplied with breathable air ensuring internal ventilation and overpressure. This protective clothing provides protection against particulate radioactive contamination for the respiratory tract and the whole body.

3.3 Nominal protection factor (100: inward leakage (IL))

The ratio of the concentration of contaminant in the ambient atmosphere to the concentration of the contaminant in the suit. The concentrations taken into account are the average concentrations recorded during a standardized test.

3.4 Paniculate radioactive contamination Presence of radioactive substances in or on a material or in a place where they are undesirable or could be harmful.

3.5 Seam A permanent fastening between two or more pieces of protective clothing material.

3.6 Assemblage A permanent fastening between two or more different garments, or between protective clothing and accessories, obtained, for example by sewing, welding, vulcanising, gluing.

3.7 Join A non-permanent fastening between two different garments, or between protective clothing and accessories.

3.8 Closure A device, for example, zipper, touch and close fastener, etc., to close openings for donning or removing the protective clothing.

4 Requirements 4.1 Design 4.1.1 Protective clothing against radioactive contamination shall comply with the general requirements specified in EN 340.

4.1.2 The design of the protective clothing shall be such that the protective clothing is straightforward to put on and take off, and to minimize the risk of contamination. Testing according to practical performance test (see 5.2).

4.1.3 The clothing can be designed for single or multiple use.

4.1.4 The ventilated protective clothing (see 3.2} may consist of one or several parts. The clothing may be fitted with a respiratory protective device to enable the wearer to breath in case of failure of the primary air supply.

4.2 Materials The materials used for protective clothing against particulate radioactive contamination shall meet the requirements according to table 1 after the pretreatment in accordance with 5.1.1 and after the conditioning according to 5.1.2.

4

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 5 EN 1073-1 :1998 Table 1: Requirements for the materials Applicable for Requirement Classification Test according to reusable single use materials 6 > 2000 Cycles EN 530, Method 2 00 5 > 1 500 Cycles abrasive paper Abrasion resistance 4 > 1000 Cycles according to prEN yes yes 3 > 500 Cycles 943-1 and 9 kPa 2 > 100 Cycles downward pressure 1 > 10 Cycles 6 > 100000 Cycles 5 > 40000 Cycles Flex cracking 4 > 1 5000 Cycles resistance 3 > 5000 Cycles ISO 7854 Method B yes no resisance 2 > 2500 Cycles 1 > 1000 Cycles 3 > 100 N Puncture resistance 2 > 50 N EN 863 yes yes 1 > 10 N Resistance to 2 no blocking blocking (see note 1 blocking EN 25978 yes no 1 )

6 > 150 N 5 > 80 N Tear resistance 3 > 20 N EN 29073-4 yes yes 3 > 20 N 2>10 N I >2 N Flammability of Shall not continue materials, visor and to burn EN 1146 (single yes yes ancillary parts burner test)

NOTE 1: Uncoated materials shall not be tested against resistance to blocking. The test report shall be marked "Not tested against...........

NOTE 2: If protection against hazardous chemicals is required then testing has to be carried out according to the relevant chemical standards.

4.3 Nominal protection factor (100:1L)

Ventilated protective clothing shall be classified according to table 2. Testing according to 5.4 with the necessary activity sequence according to annex A, at the minimum design air flow rate.

5

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 6 EN 1073-1 :1998 Table 2: Leakage Maximum value of mean inward leakage into the hood during exercise of Class Nominal protection factor One activity All activities 5

0,004 0,002 50000 4

0,01 0,005 20000 3

0,02 0,01 10000 2

0,04 0,02 5000 1

0,10 0,05 2000 NOTE 1: Maximum value is calculated as the average performance over all test sequences.

NOTE 2: Nominal protection factor is the reciprocal of the IL obtained durinc all activities (100: IL) 4.4 Seam strength, Joins and Assemblages 4.4.1 Seam strength A sample of each type of straight seam construction shall be tested in accordance with A.2 of ISO 5082

1982 (Constant-rate-of-traverse). Three specimens of each type of seam shall be tested and the mean of each set of three samples calculated. The garment seam performance shall be classified according to the levels of performance given in table 3 using the lowest result, i.e. the weakest seam type.

NOTE: The test method described in ISO 5082 :1982 is only applicable to straight seams joining two pieces of material.

Table 3: Classification of seam strength Class Seam strength N

5 300 4

125 3

75 2

50 1

30 4.4.2 Joins and assemblages The joins and assemblages between the suit and detachable parts e.g. between gloves and sleeves, boots and trouser legs, shall be tested in accordance with 5.5 and withstand a pull of 100 N.

4.5 Visor The visor shall comply with table 4. Where antifogging compounds are used or specified by the manufacturer they shall not have an adverse affect on the health of the wearer, or on the clothing.

6

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 7 EN 1073-1 :1998 Table 4: Requirements for the visor Properties of the visor Requirement Testing the loss of sight shall not exceed to read letters on a chart at a Distortion of vision two scales on the optometrical distance of 5 m during the practical chart performance test according to 5.2 shall not be visibly damaged in Mechanical strength such a way as to be likely to affect according to EN 146 the performance of the suit system 4.6 Air supply system Couplings and connections shall comply with EN 270.

The connection between the compressed air supply tube and the suit, including attachments, threaded parts, belt or other parts, or means of stabilising the suit to the body shall withstand a 250 N pull when tested according to 5.5.

NOTE: The test should be performed before the inward leakage test.

4.7 Breathing hose The breathing hose shall comply with the requirements of EN 270.

4.8 Air flow rate Two suit systems shall be tested, one of which has to be preconditioned as specified in 5.1.4. When tested the air flow rate into the suit system shall not be less than the manufacturers' minimum design flow rate. The maximum flow rate shall not exceed the maximum as stated by the manufacturer. Test in accordance with 5.3.

The flow rate and the distribution of the air into the suit system shall not cause distress to the wearer by local cooling. The heat stress has to be considered. Test in accordance with 5.2.

4.9 Air flow rate warning device If an audible warning device is incorporated in the suit system it shall comply to EN 270, except for the sound pressure level which may be in the range 85dB(A) to 90 dB(A) when measured at the ears of the wearer. The frequency range of the warning device shall be between 2,000 Hz to 4,000 Hz.

Five warning devices shall be tested, one of which has to be preconditioned as specified in 5.1.4. Testing according to EN 270.

4.10 Supply valve If a variable continous flow valve is fitted, it shall comply to EN 270. The valve shall permit to adjust the air flow rate in the range from the minimum to the maximum as specified in 4.8. It shall not be possible to close the valve to restrict the air flow below the minimum design air flow rate.

4.11 Exhaust devices The suit shall be provided with exhaust devices which shall continue to work correctly after the testing of the pressure in the suit (see 4.1 2), during the practical performance test (see 5.2) and during the determination of the protection factor (see 5.4). Testing in accordance with 5.6.

4.12 Pressure in the suit The overpressure shall not exceed 1,000 Pa mean and 2,000 Pa peak. A positive pressure shall be maintained. Testing with the maximum air flow rate during the activity sequence as specified in Annex A.

7

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 8 EN 1073-1: 1998 4.13 Carbon dioxide content of the inhalation air The carbon dioxide content of the inhalation air, determined at the minimum air flow rate, shall not exceed an average of 1,0 % (by volume), tested according to EN 270. Two suits shall be tested, one of which has to be pretreated as specified in 5.1.1.

4.14 Noise associated with the air supply to the suit The noise measured in the suit at the ears shall not exceed 80 dB(A) at the maximum manufacturers' design flow rate. Testing in accordance with EN 270. Two suits shall be tested, one of which has to be pretreated as specified in 5.1.1.

5 Test methods 5.1 Test preparations 5.1.1 Pretreatment When the clothing is intended to be reusable the requirements for the materials or the complete clothing shall be proved after five cycles of cleaning and disinfection according to the manufacturer's instructions for use before testing.

5.1.2 Conditioning All material samples shall be conditioned by storage at (20 +/- 2) 'C and (65 +/- 5) % relative humidity for at least 24 h.

Start each of the tests as specified in 5.1.3 and 5.1.4, within 5 min after removal from the conditioning atmosphere.

5.1.3 Visual inspection A visual inspection shall be carried out by the test house prior to the laboratory or the practical performance test. This may entail a certain amount of dismantling of the components of the protective clothing in accordance with the manufacturer's information for maintenance.

5.1.4Preconditioning for the practical performance test If the manufacturer does not state the preconditioning atmosphere for the practical performance test, the complete clothing shall be exposed:

a) for 4 h to a temperature of (-30 +/- 3) 'C and allowed to return to ambient conditions, followed by b) for 4 h to an atmosphere of (60 +/- 3) 'c at 95 % relative humidity. It shall then be allowed to return to ambient temperature.

5.2 Practical performance test 5.2.1 General The tests shall be carried out by two test persons at (20 +/- 5) 'C and a relative humidity of less than 60 %. The test temperature and humidity shall be recorded. The background noise shall not be greater than 75 dB(A). The test persons shall be selected who are familiar with using such or similar protective clothing. The persons will be drawn from those people certified as fit to do so by the medical officer. The necessity of a medical examination before or supervision during the tests shall be at the testing officers discretion. Prior to the test there shall be an examination that the suit is in working-condition and that it can be used without danger. If more than one size of clothing is manufactured the subjects are asked to select the appropriate size. Ensure that the air supply is within the specified parameters. Two suits shall be tested, each being tested on one test person.

After fitting the suit each test person is asked 'Does the suit fit?'. If the answer is 'Yes", continue the test. If the answer is "No", replace the test person or the suit.

5.2.2 Procedure During the test the following activities shall be done in simulation of the practical use of the suit:

a) the test shall be completed within a total working time of 20 min b) walking on the level with regular rate of 5 km/h for 5 min 8

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 9 EN 1073-1: 1998 c) filling a small basket (see figure 1, approximate volume 8 I) with 12 mm chippings (e.g. limestone chippings) or other suitable material from a hopper which stands 1,5 m high and has an opening at the bottom to allow the contents to be shovelled out and a further opening at the top where the chippings may be returned. The person stoops or kneels as he wishes and fills the basket with chippings. He then lifts the basket and empties the contents back into the hopper. This shall be repeated 15 to 20 times in 10 min.

Figure 1: Hopper and basket 5.2.3 Information to be recorded During the practical performance test the clothing shall be subjectively assessed by the wearer and the following shall be recorded:

a) harness comfort (see 5.6);

b) security of fastening and couplings; c) accessibility of controls and pressure gauge (if fitted);

d) clarity and field of vision from the facepiece and/or visor; e) clothing comfort; f) ease of speech transmission; g) any other comments volunteered by the wearer.

5.3 Measurement of minimum and maximum air flow rate Connect the ends of the distribution system collectively to a suitable measuring device. Record the maximum air flow delivered at the manufacturers' specified air supply, if a control valve is fitted, record the maximum delivered air flow and the minimum delivered air flow.

The value of minimum and maximum air flow rate shall be determined under the condition of exercise 6 of Annex A (person standing still).

5.4 Determination of the protection factor The protection factor shall be determined in accordance with prEN 943-1. Sodium chloride test method shall be used. Activity sequences for testing are given in Annex A of this standard. The determination has to be done at the minimum design air flow rate (see 4.8).

9

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 10 EN 1073-1 :1998 On two test subjects four new suits shall be tested. Two suits per test subject.

For each individual test calculate the arithmetic mean over the time period. Calculate the percentage inward leakage (IL) as follows:

IL = C2x 100%

C, where:

C, is the challenge concentration in the test chamber, C2 is the mean concentration in the breathing zone for each exercise. For classification according to table 2, the average value for the four suits shall be taken.

5.5 Join and assemblage pull test Assemble the means of attachment according to the manufacturers' information. If the assembled item (e.g. glove or boot) is itself not strong enough to apply the required pull substitute an item that is.

Securely attach one part to a fixed clamp. Apply the required force longitudinally. Record at which force it parts or state that at the required force it was still complete.

5.6 Exhaust device pull test Mount the suit on to a dummy torso which can be adjusted so that the load can be applied axialiy to the exhaust device. A system of retaining straps or bands is fitted over the suit around the exhaust device so that the load is applied as directly as possible to the fitting of the exhaust device in the suit.

Exert a force of (50 +/- 2,5) N to the exhaust device and hold for 10 s. Repeat 10 times.

Examine the exhaust device for signs of damage or failure.

6 Marking The marking shall comply with the specifications of EN 340 with the pictogram as given in figure 2.

The level of performance of the inward leakage (IL) shall be marked as:

IL : class x (x = class number according to table 2).

  • S
  • - l.
0.

g Figure 2: Pictogram 7 Information supplied by the manufacturer The information supplied shall be at least in the official language(s) of the country or region of application.

The manufacturers' information shall comply with the specifications of EN 340. The following information shall be supplied additionally:

- instructions for donning, using, fitting, removing and storing;

- application, limitations of use (classification, temperature range etc.);

- tests to be carried out by the wearer before use (if required);

- maintenance and cleaning and decontamination by e.g. showering (if required).

10

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 1 1 EN 1073-1: 1998 The manufacturers shall specify the required supply pressure and flow range necessary to maintain protection.

Warnings (if appropriate) shall be given against problems likely to be encountered, as e.g. heat stress, depending on the air flow rate, work load, environmental atmosphere etc.

Annex A (normative)

Activity sequence for the testing of the protection factor Table A.1: Activity sequence for the testing of the protection factor Time of No Activity sequence for the testing activities min 1

dress person in the suit 2

don boots, gloves etc. as required according to the manufacturers instructions 3

person to enter test chamber, connect tubing to the sample point -

3 no test agent establish background reading at sample point with person standing 3

still - no test agent 5

start test agent and allow to stabilize 3

6 record leakage and pressure at sample point with the person 3

standing still 7

start treadmill 8

walk3 9

record leakage and pressure at sample point with the person walking at about 5 km/h 10 stop treadmill record leakage and pressure at sample point, person moving arms 11 up and down above head height and looking upward, e.g. lifting object (half brick) from desk to shelf level 12 record leakage and pressure at sample point, person doing 3

continuous squats 13 stop test agent and allow to desperse with person in chamber 3

disconnect sample tubes and remove person from test chamber and undress subject NU I E: I ne total trial may vary, all times are approximate and are to staDle conditions.

When doing squats, a slow deliberate action is required, say continuously during about 3s.

Analyse results over final 2 min of each exercise period to avoid carry over of result from one exercise to the other.

Record challenge chemical continuously using a separate detector (if possible). Record the pressure inside the suit over the whole time.

11

Enclosure.2 PG&E Letter DCL-05-112 HBL-05-024 Page 12 EN 1073-1: 1998 Annex ZA (informative)

Clauses of this European Standard addressing essential requirements or other provisions of EU Directives.

This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association and supports essential requirements of EU Directive 89/686/EEC.

WARNING: Other requirements and other EU Directives may be applicable to the product(s) falling within the scope of this standard.

The following clauses of this standard are likely to support requirements of Directive 891686/EEC, Annex II:

EU-Directive 89I6861EEC, Annex 11 clauses of this standard 1.1 Design principles 4.1. 4.2, 4.3, 5.5.1 to 5.6 1.2 Innocuousness of PPE 4. 1, 4.5, 4.14, 5.2 1.3 Comfort and efficiency 4.1, 4.3, 5.2, 5.4, annex A 1.4 Information supplied by the manufacturer clause 7 2.2 PPE 'enclosing' the parts of the body to be protected 4.1.4, 4.5, 4.8, 5.2 2.3. PPE for the face, eyes and respiratory tracts 4.5, 5.2 2.1 2 PPE bearing one or more identification or recognition clause 6 marks directly or indirectly relating to health and safety clause_6 3.9.2.1 Protection against external radioactive contamination clause 4, 5, 6, 7 Compliance with the clauses of this standard provides one means of conforming with the specific essential requirements of the Directive concerned and associated EFTA regulations.

12

Enclosure.3 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.3 PROTECTION FACTOR DETERMINED DURING FIT TEST EXERCISES FOR V4 F1 Total Number of Pages in this

Attachment:

2 (Not Including This Page)

Enclosure.3 PG&E Letter DCL-05-112 HBL 05-024 DPEA/STESRICTH EN/97-599 Page 1/2 Test Results carried out on the full encapsulated suit MURUROA V4F1 ref. 8481X1T For the EC Type Examination Certificate N00073/1 97/162/12/97/0028 You will find below the detailed results taken in account for being able to statue on the conformity of this equipment in accordance with the Essential Requirements of the European Standard pr EN 1073-1. Other results those are non pointed out in this report are already written in the EC TYPE Examination certificate (dated December 1 0th 1997) 1 - Air Flow entering the suit when connected to a 6 bar feeding pressure (paragraph 2.3.2.

of the EC Type Examination Certificate)

Suit number Minimum air flow(l/mn)

Maximum air flow (I/mn) 1 508 1050 2

516 1070 3

508 1050 2 - Carbon dioxide content of the inhalation air when measured at the minimum air flow of 450 I/mn (paragraph 2.3.12. of the EC Examination Type)

Suit number Test N°I C02 contents(%)

Test N02 C02 contents(%)

1 0,86 0,93 2

0,68 0,68 3

0,75 0,82 3 - Noise level associated with the air supply to the suit when tested at the maximum air flow rate at 6 bar (paragraph 2.3.13 of the EC Examination Type)

Suit number Maximum air flow(lUmn)

Noise level (dB) 1 1050 77,2 2

1070 75,1 3

1050 77,6 1

Enclosure.3 PG&E Letter DCL-05-112 HBL 05-024 Page2/2 4 - Inward leakage average - Fit Factor measured at the minimal air flow of 4501/mn (paragraph 2.3.3. of the CE Examination Type)

Suit n' Exercise 1

2 3

Standing still

> 120 000

> 120 000

> 120 000 Walking (5 kmlh) 76 700 90 900 66 000 Moving arms up and down 113 800

> 120 000 113 800 above head Continuous squats 30 000 41 700 50 000 Bending forward 110 000 103 400 91 700 Person twisting at waist

> 120 000

> 120 000

> 120 000 Person crawling 55 000

> 120 000 31 400 5 - Pressure in the suit when measured at the maximum air flow when suit connected under 6 bar feeding pressure (paragraph 2.3.11.of the EC Examination Type)

Suit n 1

2 3

Exercise P min(Pa)

P Max. P min(Pa)

P Max. P min(Pa) P Max.

Standing still 275 280 295 305 275 280 Walking (5 kmlh) 200 800 300 900 600 900 Moving arms up and down 150 400 160 420 250 800 above head Continuous squats 30 900 30 1050 70 1700 Bending forward 80 1550 60 1900 100 1900 Person twisting at waist 140 500 160 420 160 650 Person crawling 160 900 150 850 250 1050 6 - Air supply system (paragraph 4-6 of the pr EN 1073-1)

In accordance with the paragraph 4.6; the connection between the compressed air supply system and the suit has been tested for a steady pull of 250 N. The three suits have been tested successfully. However, it appears a deformation of the fabric, near the regulation air flow device. A reinforced area could certainly avoid this deformation.

2

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.4 CERTIFICATE NO. 0073/197/162/12/97/0028 FOR MURUROA V4 F1 ISSUED BY THE INSTITUTE FOR NUCLEAR PROTECTION AND SECURITY Total Number of Pages in this

Attachment:

12 (Not Including This Page)

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECECr971OM P"q 1(12 INSTITUTE FOR NUCLEAR PROTECTION AND SECURITY Technical Center for Nuclear Equipment Certlflcatlon In accordance wHih the dlroctive 8918eWEEC dated Decomber 211 198l comoarlng eo lawn orf the Staoes Members Legislations relatwe to the Personal Protectie Equbxnen, and the decrees n°92-765. 766 and 768 dated Juy 29 1992 t'ansposhig be diructi Inte Fronich laws.

The organisatkn herbelow mnentioned UIPSN I CTHEN) whoee references are as fclow Addrss: BP. n' 6-92265 Foninay-aux-Rosos Cadox (Franco)

Empo4arod by Ordor of th Mkllnlrbs of Emrploymeorn and Aoriculbure da$

Decewmbor 241 1996.

Identilid under ten' 0073 (publishd In the EEC Offia Pubolebn dd July23Ii 1094>

Assigns the :

ECTYPE EXAMItNAllON CERTIFICATE r 0071197116211219710028 To the following Personal Probxveo Eqpment model:

Destneltbn: Ventlaed ProecttW Sut against Radloacto Contamination pressureed for a singb use only.

Comm'erc1i,foronoox: MURUJRA v4 Pt - wi. 48 1x T.

ManutUrer: DELTA PROTECTION ? REDI-e9 210 Sant-Oe'main-Sur4Abrele Cartffato applizant: DELTA PROTECTION - ZA Do Berrt-30200 Bgncls-Sur-Caze.

Essontiai Roquiremonts Roferonce : EN 143, pr EN 1073-1 (July 1997l pr EN 943-1 (October 1997), EN 270, EN 1146 (April 19974 Data: DecOmber 10d" 1997 J.CORBIEREJ Chif of OTIIEN Nota : Accordlrg tI article R 223-62 of the 'Workig Law, the orpoworod organisallon should be Infroned of any modification made to the matarbil subJect of thE EEC typa oexamnaton cortilcata. as well M of any rnodIfication rmade to the contents of this technical file on which the delivered type cortfkcab3 vs based on (addmss, manufacturer nam. qual ity hIsumrance cort iat ext-act _.

T His cetficalte contalIs 12 pages n 1112 to 12112 1

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC97f 0028 Pip Th12 1-DESCRI1PTION it is a Veisteld Protote Suit against Radioacle Contamination ontllated typo -

resserlSed for e s3ng91 use only, ls name k:

MURUROA V4 F1 - ref. DELTA 84O1X1T Tie T values aro ciafned according to the size of the suit.

The X valbus are delinei according to the pipe btvt (Staubli or CEJN) allocwlng to connec the suit to the bmeaflable compressed air supply system.

The attached list -annr 22-ges all the referces defined by this ECEC.

TiM sult incluos:

Aalr (ghtsulwitwhan Incooratdhtd A suKt fastening systrn locatbd on the back cf the suit A broathablo air low supply system.

Aiar oxhaust device.

Asafety stp or emergency opening locatd on the hood FRONT VIEW BACK VIEW IIrr3&;XIII: IIPU s sn.FS9M.-f;lp

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECrC 97 IOM2 Pq 3r12 11 MAIN MATERIALS Skin of the sult:

PVC90S3-Formiule 1010,201100m m thIckness.

Hood:

PVC Cristl - 301100 mm thickness.

Visor:

PVC (astraglass) MI O0 mm thlokons.

Gloves:

PVC Somporsoft type - Size 9-9112 for all the sizes af the suits.

Boots:

PVC 9013 - formulaon 1010 - 201100 mm Uilkness. reilnfored PMI.

1.2.

COMPONENTS Internal Watition Sysm:

It Includes a tcWal ventlatbn V4 fIted with a vaNve with butt Exhaust:

It Includes two exhaust valves loated on the head and on the back fthe suI.

Fastwing device:

It Includes a double 2Ap fasbener stualod velcalfyon the back of the sUt Qthroornponents:

Tho sult hncludas:

A afely strip for an emergency opening located on the hood.

Aoouotloilnktunnol.

A loop for breathable air supplypipe.

S ral Internal strngthonhg pbces for olbows, knees and Imags.

A transpaent window bo vlsualise the dosimeter.

rfl.

.u-pvpm. t*v_

4%M oft".

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC971 0028 Prq 4R12

2.

CONFORMITY TO REQUIREMENTS 2.1.

REQUIREMENTS FOR THE MATERIALS (except accessories: Goves, slippers...)

(See paragraph 4.2. of the Norm EN 1073-1) 2.1.1. Abrasion Resistance Test according to the Nom EN 530 - method 2 (abrastv pape' 00). The classilcaton Is carriad out according to tha rollowAng dLoram:

Class Number of cycles 0

>2 000 cycolo 5

>1500 cyles 4

I 000 cycles 3 a 500 C)Cles 2

> 100cycles 1

10 cyclas Results: Cass6 for PVC9013-formule 1010-201100mm thcknesa.

CLass6forCristal PVC 301100mm thlckness.

.1.2. FlexerackIng Resistance Test acoording to tho Norm ISO 7854 - moetod B. Tho clasifcaUn is carrLec outaccordIng to the followng diagram:

Class Number of cWles 6

100 000 cydes

> 40 000 cycles 4

> 15 000 cycles 3

> 5 000 cyOls 2

> 2 500 cyles 1

l0OOc Ylee Thb tee( Is not apPIkcable to sJbs for one single use ory.

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 EgEC970028Pptgp Y12 21.3. Puncture Resistance Test accordir to tth Norm EN 863.Thoclasslfkatbn Is carried out acordlrg to tho followAn dlwram:

Class Punclire resistaico 3

> 100 N 2

> 50N I

> ION Results:

Class 2 for PVC Crfltt31 - 30l1100 mm th bknoss.

Class I for PVC 9013-Formule 1010 -20100 mm thIcknass.

2.1.4. Reelstance In blocking Test according to ft Norm EN 25978. The classlncatbn Is carred out according to the fo loaing dkaram:

Class Comment l

2 non sUck I

sthky This test Is not avPN cabfe to nortcostrf materiges 2.1.5. Tear Resistance Test acoordino to te Norm EN 29073-4. Tbo classfljcaon IS acording to te following

diagram, Claee Appiled tength 6

> 150 N 5

> BON 4

> 40N 3

> 2ON 2

> 10N 1

> 2N Results:.

Class 3 for PVC 9013-Formule 1010-2Qf11O mm tiklkness.

Cass 4 for Cuistal PVC - 30/100 mm tIcknoss.

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9J 10028 Psep 612 21Ai Flamrnabilltyof materials, visors, and ancillary parts Tests are caried out according to the Norms EN 1146 - shlgle bumor test (paragraph 7.5.3).

Result: Tost roqulrornont onrftlyfulfled.

22.

REQUIREMENTS FOR THE ACCESSORIES 22-1. Gloves The gloves set on the MURUROA V4 F1 ref. 8481X1T oomply wlth the specft requirements for this typo f Indvidual Proteotion EquIpment, mainly b the Norm EN 421 'Prottlv Gklos against lonitEr radlation and radbac contambatbn.

Thayhavo Spwcil El 2

ramInation CGrlFi tas (ECEC) basod on oortactod tasts 2.2.2. Boots The boees are part and parcel of te sUt and are made of the same consWi d materal.

ConsequenUyl they comply with the requirements.

2.3.

REQUIREMENTS FOR THE PROTECn1VE SUIT 2.3.1. Suit Design: Practcala Performance Test The Practical Porfemance-Test Is caried out acoorling to the Nrm 1073-1 (Paragraph &.2).

The condlUoning is according to the manufacturer dlrections for use.

Parameters Valuations a) Hood cOm fort Almlss b)Securityoffastnings &coLiln; Good C) ACCSsbIItyofl aJustho deV1O0s Goo

0) Clarity of vis13n through Visor Oooo e) SuItcemford Good F) Speaking trarsmisslon fazility Almless g) Other paramnetors No particular rnoce 2.3.3. Airflow supplysystem (project Norm prEN 1073 paragraph 4.8.)

The manulfaurer estimatd air flow rates, for a relatlve air flow isuly pmessure of C bar, with a toleranco

+- 10%, are:

Mlnimal tow rate

30.0 m31hIt (500 Lmnh i)

Maxwnim flon rate

5E,4 m h't (973 Imh i)

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9710026 Pqp t7(12 Noltee: in ordor to take Into account the marufactirer Indlcated toleranrcs, lils ECEC tsts have been carrd out wnder the fdlowigr conditions:

[min = 27,0 m3.h' (450 L.min-1l Dmax - 04,2 m3 n h (1070 I.mnl)

The test concomrnl tie air Rlow rais of th sutl has boon roe1sed accordng to to Norm EN 1073-1 (paragraph 53); For an air suppIy pressure of 6 bar, the air toAw ratb InsdW the suit must notba::

Below the minimum value estmated by the manufacturer (Dmhi). when the valve is on the

'b-top closod position.

Superior to the maximum value csitimated by the manubcturcr (Dmax), when the vlve Is on thron'cp*ned position.

Rasvlte Roqulrements ntlrely Mulled.

22.3. Inward loakago awrago - Fit Factor fparagraph 4.3. of tho project Norm pr ES 1073.1)

The ratio of the awrage Inward leakage (or hs contrary: Fi Factor) has been measured accordinr to the draft Norm pr EN 943-1 (amnex A). Accoordig to the Sodlum Chlodide lethod.

Measurments have been performed under the folliowg condY~ons Quantttyof tested suIts :3 Air fl raWe: Adjusted and maintained on mlrnuimu flow rale (D min) as Inrle4ed In paragraph 2.3.2.

Trahings sequence: Accordhig btte Norm EN 1073-1 Annex A lst Sut prelllinarycondlionkng: According to e adico cf th user manual The ratio of the werage Inward leakage (or Fit Factor) gee the following cla"sallon:

Mtdmu= aocepted Yelues. In %,or the raio of the Ventilated average Inusrd L&.aga insido the hood, prnmurisd calculated on the whole lot olf W"I FIT FACTOR S uit_

classliflCtion For One activity For all actiities 6

0.004 0.002 50000 4

0.010 0o ao 20 000 3

0.020 0.010 10 000 2

0.040 0.020 5 000 1

0.100 0.050 2 000 Rotults: The sUit is classld S.

roN s

tv%

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC9YI 00M Psq 8'12 2.3.4.1.

Seams t Welds (paragraph 4.41 of tie project Norm pr EN 1073-1)

A sample of each typo ofeeanilweld isteested acordhig t the Norm ISO 5082 (annox 2).

The seam performance level Is aocording tbthe fllowing dassffictafi:

CIMs Seam resistance (N) 5

'-30 4

> 125 3

> 75 2

> 50 1

>30 The tests have been applied to the fol lo wing wolds:

Assemblae nohocsiit Asemblage hoo4lsMor Assomblago hood loeal Assemblage bolt level Assemblage of the stngthning pieos (elbow and knoos)

Assomblago at the lovel of the arms, backand silos Results: PJl tho welds are classfled 4.

2.3.4.2.

Joins and Assenblagos (paragraph 4.42. - prolect Norn pr EN 1073-1)

This suit has no rernmable parts. This paragraph Is alniles 2.3.4.3.

Visors (paragraph 4.5. - proJect Norm pr EN 1073-1)

The disorsion of vson is measwoed during the Praitsical Performance Test, by reeing letters on an optloneVkal chart placd at a distance of 5 m; Thr loss of visi must not exced 2 degrees.

Tho mnochankoJ rosistanco test of the visor Is acoording to th Norm EN 146 (paraaraph 6.7.).

Results: Dibrtbn of viabn: Up to roctirement Mechanical resbbnce: up b requirement.

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9710023 Pa" 9!12 22.& 6Airsupply system (paragraph 4.6 of the proet Norm pr EN 107341)

The couplIngs and oonneoctions must comply wih the roqLdromonts of tho paragraphs 6.7.1.,

6.7.2., and 6.11.7. O the Norm EN 270. mT connection botween th comprQssed alr supply yteytmand teultmucresttoe2,5N pull Result rocpiirernent entirely fulfilled.

2.3.7. Breathing Hose (paragraph 4.7. of fthe project Norm pr EN 1073-1)

Tests are peWormned acoording to the Norm 270 (paragraph 7.2. and 7.6). The pipes must rot block the movontsml nor cu3we a rupture of the eli supply during the Pradhal Performanos Test Result No constrait-2.3.8. Air ffow rAu waming device (paragripl 4.9. of the project Norm pr EN 1073-1)

If a warning is fitao, it must comply to the f4orm EN 270 (pamrarh 6.13.3) Thio 1 st must be csrrWd out accdlng to the Norm EN 270 (paragraph 7.12). The sound level must be bween 85 dB(A) and 90 dE(A).

Result Almless (there Is no walning da).

22.9. Air supply valve (paragraph 4.10 of the project Norn pr EN 1073-1)

For the alr swuply pressure specified by the manufaetur., the air supply valve must be able t ac4ust th air flow botwoen the minimum and maxlrnum valmns as indcatod In the technical manual. It must be Impcsstle to close tho valve In ordor t roduce the a flow supply below the minimum flow rato as speclfld by the manufacturer.

Result Requirementooentirely dfilied.

Notice: Tho MURUROAdocs not Include lw air flow Indicator.

2.3.10.Exhaust devices (paragraph 4.11. of the projet Norm pr EN 1073-1)

The eftaust

%40c1xS must wok correctly aftr tho testing of the pressure In Mo Suit, durino tha Pracdlu Performanco Test and during tho dotormninatln of tMo Flt Factor. Test in accordance wlth the Norm 1073-1 (paragraph 5-6.).

Result:

Good valves working.

Pull reslsance Lpeorbr b the fIxed llit r~ YW "VW.rip r+

VW

-4fM

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC 972O PaPA 1(Y12 2.3.11.Pressure in the suit (Paragraph 4.12. of the project Norm pr EN 1073-1)

During tna actMvt sequence as spoctfia, the ov3rpressure shall not okeoed 1000 Pa mean and 2000 Pa peak. A posltMV proesUre shall be maintalred.

Test b performed wvIh maxmum air flow rate D max. as stiplated in paragraph 23.2. on three diferent suits.

Result: Roqironments enirely fulfIled.

2.3.12-Carbon dioxide content of the Inhalation air (paragraph 4.13.-project Norm pr EN 1073-1)

The CO2 coniont of the Inhalation air, delrmInrI at the minknum air flow rats, shall not emceed an avroae of i % (by volume). testea aocdho to the Norm 270 (paragraph 7.1S) with the miuimum alr ilow rat D mki Irilcated In paragraph 2.31. on three dirfeent subs.

Result Roquiremont entl.'ulyfulflllad.

2.3.13. Noise nsoclated witht air supply to the sult (paragraph 4.14.- proecIt Norm pr EN 1073l1)

Testaccordingtothe Norm 270 (paragraph7.16).The rcise moasurod itnthesuiat theare shall not exoeod 80 dB(A) at the mwdmum air fiow rate as inrccted by the manufactumr.Testedatthe madrmum alrflow rate Dmaxas stipulatd In paragraph 2.3.2, on thrwo diffarnt suits.

Reuit Requiirement entirelyful Ilied.

3.

CHECKINGS 3.1.

MARKING (paragraph 6 of the Norm projed prEN 1073-1)

The marking con plies with the rMukenrents of the Norms EN 340 and EN 1073-1. Accrding b the Decree daed February 7 1997 'relative to EEC marklig of the working equiprnent and of the Personal Protectve Eqilpmenr. It Includes the distIncilka numbr of the entitled organisation for the procedure of controls of the manufactured PPE (article 11 of the EEC Diraeiv 89/6 'EEC}

The symbol

'r is hIcludod hI the pictcgram. hI order to show that the manubcturer Ilructbns shoulz to roaa by tho user..

3.2.

MANUFACTURER INFORMATION (Paragraph 7 of the project Nomin pr 1073.1)

Information comply wlth the specficators of the project of Norn pr 1073-1. They Include the Directions ftrruse,thocondtons of use, the specific nims and restraints.

Thes documents wIll be corracW In order to take bti acolunt the tests results as mentlonnod in this ECEC.

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9710028 Ppe 11(12

33.

MAINTENANCE MARKING This Is aimles, the sult bng for onersingle us only.

4.

CONCLUSIONS Upon presenbtbn of the tests rasults, the Vontatd - prossursed for a single use only, NURUROA V4 FP - rWf. S48iXIT Is colefod toenwsr a protobn against radioactt oontamllalon occordin Iho hfollowing specifid lmIg:

Nlnrnumalrow rat&:

27,0 rmth'.

Nsxlnurn airflow raW 64.2 mtht.

The MURUROA V4 Fi s delftred vwlidout low alr flow rab tdtcatr.

Before using IL the user vii hiw. at his disposal the neosary devices to check that the

.ninimum alr flaw rates, as speotfbd by the imanufadurur Is reached or owr reached befor and during te ue of the sult

Enclosure.4 PG&E Letter DCL-05-112 HBL-05-024 ECEC 971028 Paq 12f12 ANNEX I Description and reforences of the equipment crtifed In the EC Type Examination C0tificate The difert mnodels of Oqipment. whose generic appellation Is MURUROA V4 F1 ret. 8481XT. 'and which are the uect of this EEC type exarmninon cortifIcab (ECEC), are only diferent on the followirg polnts:

The ty¶o of pte butt connoctin the oqulipont 1 the broatablo oomprotd fr supW The size.

X Indicates the type of pipa butt according to the following values Typo ofbuff

~Refermnces ct MlJRUROA Referenoes the com pmesed air supply V

las~a

'X=2 Sbunit RBE06 6150 848121 T X=3

$aaIRE6848131 T

X=4

.CON 342 848141 T X=8 StaubllR2EO6OR 8418 T T indlcsW4 the *Ie of th stuit Pccordlng to tho folorwhV volut-

-REFERENCE Hetht ( cm)

Waist nmeasuemeant (cm)

T=O 152-1 50-04' T-1 164-170

644s8 T=2:

170-176 68-72 T=3 176182 72-76 Ti4

-182-188 76-80 T-5 188-200 80-88

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.5 CERTIFICATE NO. 0073/197/162/01/96/0001 ISSUED FOR MURUROA V4 MTH2 BY THE INSTITUTE FOR NUCLEAR PROTECTION AND SECURITY Total Number of Pages in this

Attachment:

9 (Not Including This Page)

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC9s61I W01 Pa1AJ F

INSTITUTE FOR NUCLEAR PROTECTION AND SECURITY 7echnial Centsr for Nuclear Equlprnent Cortifkcation In awordance with the dlrtkW* aO"/EE0 Mod December 21 th 193 comparhig the laws of the States Members l.islallorns rmuia to the Personal Protactlie Equxnents. and the doare n* 92-7E5. 76 and 758 datod Jy 2e 1992 IransposhIg the dlrcalva Int Frorch Laws.

The organlation here below menffoned (lPSN I UTHEN) who referencet ae as follows:

Adduss: B.P. n 6-2265 Fon*ny-aux-Rasos Cedox (France).

Empowored by Ordor of Iho Minisris ro Ernpbyrnont and AgrluIke datd Dconmbor 24' 1998 Iodenled under then' 007 (publhed in tho EEC Ofofi PublcdJon dtd July23 h 1O94 Assins the:

ECTYPE EXAMINATION CERMTFICATE.

N 00731197 1162 01 9 1 001 To the lollowlng Personal Proixive Equxipent model:.

Desrnalbn Venglated Protct* Sult against Radlecfe CortamInaMtn Wessuirbd fr a single use only.

Commerda rdbrece: MTH 2-sL. 84 442 T.

Manufctrer: DELTA PROTECTION I REDI-eg 210 5ant-Germain-Sur-Abrsle.

Certlflcato applcant: DELTA PROTECTION - ZA. Do erruet-30200 BagrndSuSr-Coe.

Ess"rblJ Roqulrnenirt Poronce:EN 143, pr EN 1073 (nov. 1995), pi EN 943 (aigust 1995). EN 270, EN 14e.:

Date: January 10" 1996 I3.BRUHL Chif do CTHEN Nota: Acoording to artide R 2234 of the VWorkkig Lad, the empowered, organIsaflon should be Inferned of any modficatlon made batho imatrbil subtactda thb EEC Wae examinaon cerMcale, as wet as or any nmodrcagon made to the *ontens or hlie lechnical 'lle on whish the dellwerd te ceortficab vww basedon (address, manufacurer nanio, qWtdly hisurancecefttlcato extract _.)

This cttlcate contains 12 agxes n' tS lo 9 1

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC "6 I O01 P~gq 2%

11 DESCRIPTION It Is a Venfglad pmrotove Suit against Radkoacibe Contamirntion ventlated We - presrl br a skiglo use only, Is namar-e bs:

MTH2 - ref. DELTA U41 42 T The T values ara dbflrnd according to the siZ of th sumt.

The suit Includs:

AalrtightsultwthanIncorporatedWhcod A SuRt fatnifl sstem locad on trM back ef tvo sut A brthalble S to supply $Sm.

Aalr exhaust device.

Azystip 1rororoncYoPnnire lo9Dd on tho hood r~.

  • w1"w

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 EEC 96 f 0001 P i 3s 11-MAIN MATERIALS Skin do the wult:

White polyethylene: Ethyfuge 2000 Thickness: 24100 mm Hood:

PE Cristal -301100 mm thIckness.

Visor:

PVC (astragiass) 50100 mm thiknoess.

Glovos:

PVC Sempersof type - Slze 9412, and Sempet typ-slze 10-10 %

-Boot.

Poyethylene-24100/mm hcknass, raInforcodwRl PEcristal.

1.2.

COMPONENTS Internal Ventilation System:

It Includes a total vretiaon V4 titled with awate with CEJN (r~f1342J but.

Exhaust:

It Includes two evchaust valvos ocad on tho had and on th back ofitho suit Fastning device:

It Includes a double Alp Iastnor boatd vertically on thm back of the suL.

Qhrcomponents:

The sut kIcludes:

Asafot strip tan e3 ermgencyopenliw located on th hood.

AacoustlcllnktunneL A loop for bathlair supy pipe.

Sevral Inrtrnal strengthenkig pbces for elbows, knees and legs.

A transparent window t visuallse the dosimetr.

2.

CONFORMITY TO REQUIREMENTS

21. REQUIREMENTS FOR THE MATERIALS (eocept aoessories: Gloves, slippers...)

(See paragraph 5.1. oF the prEN 1073) rPE-U W1MW tuW'W_*

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9I6 001 P AMJ 2.1.1. Abraslon Resistance Test acrording to the Nonr EN 53 -

omethod 2 (pbrasWve paper (0). The classhfcaton Is carrI3 out ac0oing to tho follouing diwramr Class

- Number of cycles 6

2 000 e

oycl 5

> 1500 cyces 4

> I ooo cycles 3

> -500 cyes 2

> 100 cycles

.1 10 cycles Resultv Clas efm Ethyfugo 2000O-241100 rmm thiokness.

Class 6for PVC.

.1.2. Flex cracking Resistance Test acoordirs to the Norm ISO 7854-method B. The claslficaton Is carried out accordhng t~otefonouMa9dlagram:

Class N umber of cyckI-s 6

> 100 00Ocycles

> 40 000 cycles a

5 000 cycles 2

2 2500 cydles I

1 lOQ cyclos 2.1.3. Puncture Rosilsano fOWl~N~ dlgam:

Class Puncture ressarce 3

1 00 N 2

-. >.50N

.,.1

--- ' >-10N C-asS 1 for Ehe200-241100 mm thfIrcess.

Class 2 fcr PE crisfal.-

Resulte

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC 961I001 PR 5M 2.1.4. Resistance In blocking Test according to the Norm ISO 5976. Tho silfcaton Is carried out aocording to the f11oioAn0 diwam:

clawe Co 0mmonta 2

I non stkci I

sticky ThIs test Is not applicable to nan-coated materials.

2A1.S. Tear Resistance Test asooding lo the Norm 150 9U73-4. The cdassIftkion Is asoordir to the follovAng diagram:

Class:

Appliedi strenrith 6

150 N

> $ON 4

> 4ON

> 2DN 2

~

1ON I

> 2N Rasults:.

Clas 4 for Eripoo 200 - 24/100 mm thicknoms Classa3 for PE Celstal.

2.11A.Flarnmablilty of mfterIelW, vsisors, arnd aniilllpry parts Tosts are carried out aCririn towe.Normst EN 1`148-' sirpp burnorioSt (l)"arah7.5.3).

Results: Tedt requiremrnls. ernJrelyfunfle~d.

2.2. REQUIREMENTS FOR ThEACCES8ORES The Clovies wet on The MTH2 ref. 841 442 T ozmpl wmh the spectl reuiremenits for thb typ of IncMciual ProjCtion EqUipmentk marily to tne Norm EN A2i -Protctrw Gloves agsinst lonize radiaUon and radieective vcontrmlntion.

They have Spocial EC Examlnatin Cortlifkats (ECEC) based on contractnd tests.

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9410001 Ps5S9P 2.2.2.Boots The boots are part and paroel of the s8tand are mrade of the some consted matedaJ.

Consoquonttytoycoomplyvwithe requIremen 2.3. REQUIREMENTS FOR THE PROTECTIVE SUIT "2.1.

Suit Design: PracticlA Perfonmance Test Trh Practical Performance Test Is carled out acordino to the prEN 1073 (parearaph 6.2).

The conditioning Is accordinD to the manufadurer directions for use.

Paramreers valuamons a) Harnoss comfort b) Socurfy of fastenings & coAIlno c) Accessibility d adjusthig dvices d) Clarlty of vision through visor

) Othr parameters AimlIsS Good Good.

Good Good No paticular notico 2.3.2. FIt Factor (paragraph 6.2.2. of the pr EN 1073)

The protaction facbr Is dtormilrd according b tho PrEN 944 standard (paragraph 8.9) by respocthg the scuences Indlbald h AnnexA dtha PrEN 1073.

The mean leakage value ( or Inerelyt, Ihe protedon Factor) enables a clotting dcasslflc accoding it the following table. The preoonditkonIng acodn bg to t.

I ns*tron for uwo rowanmoindations.

Mrdmum accepted iolun. ln %.,othe ri of 1th Ventilsed ev.ago hwuad Le*sge inkie the hood, prenurised calwlated on the whol lt of suiit FIT FACTOR classlcsalon Fo one activIty-For all actities 0.004:..

0002 50000 4

-0.010

.05 20 000 OD20:

0.010 '

10 000 2

.040 020 -

-000 1

0.100 '0.50 2000 R46ult:s The sult Is classzlfd 5.

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC"9 1 O01 PW J79 23.3.1.

Seams, Joins and Assemblages pull test resistance 2.3.3.1.

SmPs Welds (paragraph S.2.3.1 of the pr EN 1073)

A aple of each t1YD seawe d sted accordhig btheNorm lS0,082 (annex2).

The seam perfornanoe level Is accordingrb Ithe followir dassif catl; Class Seam resistam (N) 5

>>300 4

> 125 3

> 75 2

> 60 1

>30 The lots have been applied to the folowing welds:

Elbow and knee reinforcmlnent Crotch assembly

-Beltassembly

-Boos assembly Results: Al the welds me clas5 Vied 3.

2.3.3.2.

Joins and Assemblages. (paragraph 5.2..3Z-prEN 1073)

This suit has no romcuable pads. This paragraph Is aleslos 2.3.4 Gas tight (rWagraph 52A. of piEN 1073.

Tlw tast was carried out accing IO tonthe EN 484 standCd -The oss of pressure shall not be

-reato than 4 Mbar It h minn::s.

Remlts Test not ucerlaken as the clthhg is not conskiered as an gastight suIL 2.3.5.

Visors (pOragraph 5.2.5. of prEN 1073)

The distortion d vision Is measured. durbg the Practical Performanoe. The mechanlcal resno est of the visor accordng t the Norm EN 146 (paragraph.BO and 6.7.).

Result: D;brtbn of vfrn: Up to roqiremen-t-Moecanial resistance: up to roquiremont.

rN-cs U1-

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC 9610001 P SSa 2.3.6. Ar supply system (paragraph 2.6. of the pr EN 10)

ThO couplings ana connectons must oomPly wmh the roqwremts of tno paragras 6.7.81.,

6.72, and S.11.7. of to EN 270. Tho onnoctln bewon toCm xOpress ai SLWySystom arnd esuttmustresisttoa2SON pul.

Result roeptrmnant entiely ulfilld.

2A.3L Breathing Hose (paragraph 52.7. of the pr EN 1073)

-Tests are peorned according to the EN 270 (paraaph 7.2. and 7.0). Th1 pli must not block the movemenis nor cause a rupture of the ai supply during the Pracdcl PWerformanre

-Test Rosult No constaint.

-2.3.7. Air k uppy flow rate fps reg h 52D. onihe PrEN 1073)

The btst Is carred cut according to the PrEN 1073 sbndard (paragraph 6.3).

MAinimal tow rato30 m9.h 1 (500 min i

1) for a6 Bar supply pressure N~axknal flow rate66 n 3.h1 (1100 umint for a 5.5 Bar supply possurG 243.0. Air flow rate waming device (perg wph 52.9. of tihe pr EN 1073) if a warning is 1ad. it must conmpy to the EN Z27 (paragraph 6.13)3). The lest must be carrbd out according to the EN 270 (paragph 7.14, The sound Wll must be hiher than 85 dB(A).

Result Aimless (thore Is no sonkc warnhg devlc).

2.3.9. Alrsupply Valve (poragrah 5.2.10 of the pr EN 1073).

Whero present, the coitrol valvw should enable a varbtion of flow rate bebveen the minimum and maximum specifed values whDutthe possbilllyof Gcotsur Result RequirOernots entirely lIleW.

223.11.EXhausl devicOs (pararapt 5.2.11.of tho pr EN 1073)

The euhaust deicfes must wodc oorrely after the testing of the pressure In the sui[t during the Practical Prformance Teot and during the dolermlnatbn of the Fit Factor. Test In a

rdanc with the EN 1073 (aragraph 0.0.

Results:

Good valws working.

Pull ristane superboro Itse bd IROl r"

evwvst>"-#oot"-

Enclosure.5 PG&E Letter DCL-05-112 HBL-05-024 ECEC%. 10001 PSW VAX 2..12.Pusure In tlhe sult Durign the actkW sequenoe as epeciffld, the o ressure shall not exceed 1010 Pa mean arn 2000 Pa pealk. A pOSWV pre35ur shma be maIntainr.

IRelt Requirements enirely f[lil W.

2.3.13.Carbon dioxido content of tho Inhalation air The CO, ontAWnt of he Inhalation air. deahrnined at the minimum air flow rat, shall not axle an average of l % (byvolunie), tesd according t the EN 270 (paragraph 7.15).

Reut Requirement entirely fli led.-

24.14 Nots assoclatod withthe airosuppty toThe sult (paragraph 5.14 - pr EN 1073)

Test acwcodng b the EN 270 (Gagraph 7.16). The noise measured In the sut at the ears shall not eroeed 80 dB(A) at the nmaxknum *i flcNmte as IndtaWe by t'e manufadufer.

Rewlt Requirement entlrelyfulfilled..-

-3 CHECKINGS 3.1.

MARCING (paragraph 7 of lhe pr EN 1073)

-The markhig Is satisfies the requlrements of arkle 7 In the EN 340.

3.2.

MANUFACTURER INFORMATION (Paragraph 8 of the pr 1073}

The manufacturers Inforwnaton xonplien with the speflcailons in paraoraph 8 of the EN 340.

They contaln the Insl ctlois for se, Vie usage condtlons and the specikc EmIts and

-msthahits.

3Z3.

MAINTENANCE MARKING This is aimloss, tho sult boleng r one tingle use orfly

4. CONCLUSIONS Upon presntaon of the lts results, tho Vonilatod sult-pressurleod for a sIngle Lso only, NTH 2-ref. 41 442 T Is certified to ensure a proteciln agaInst radioacie contamination oordling the following eoe~fied lnlit:

lniknumairflowste 30 n9.h4 (500 Lmit)

Nxitimum Sirflow rated 6 m.ht.(1100 LmIn')

r

_-~s

'4

-A

Enclosure.6 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.6 PROTECTION FACTOR DETERMINED DURING FIT TEST EXERCISES FOR THE MURUROA V4 MTH2 Total Number of Pages in this

Attachment:

3 (Not Including This Page)

Enclosure.6 PG&E Letter DCL-05-112 HBL-05-024 DPEAISTESR/CTHEN/02-642 Page 1/3 Test Results carried out on the full encapsulated suit MTH2 ref. 841442T For the EC Type Examination Certificate N00073/197/162/01/96/0001 You will find below the detailed results for this equipment in accordance with the Essential Requirements of the European Standard pr EN 1073-1 (revision Nov 1995). Other results that are not pointed out in this report are already written in the EC TYPE Examination certificate (dated December 10t 1997) 1 - Air Flow entering the suit when connected to a 6 bar feeding pressure (paragraph 5.2.8.

of the EC Type Examination Certificate)

Suit Air flow feeding pressure air flow (m3lh /

number Entrance valve position Bar / psig I/mn! cfm) 1 Fully open 5,5 / 77 66/1100/ 38 I

Closed 6,0 / 87 30/500 /17 2

Fully open 5,5 / 77 65 /1080 37,8 2

closed 6,0 /87 31 /516 /18 2 - Carbon dioxide content of the inhalation air when measured at the minimum air flow (paragraph 5.2.13. of the EC Examination Type)

Suit Feeding pressure Air flow C02 contents(%)

number Bar / psig M3/h I cfm 1

6 /87 30 /17 0,85 2

6 /87 31 / 18 0,80 3 - Noise level associated with the air supply to the suit when tested at the maximum air flow rate (paragraph 5.2.14 of the EC Examination Type)

Suit Feeding pressure Air flow Noise level (dB) number Bar / psig M3Ih; cfm I

1 5,5 / 77 66 /38 76,8 2

5,5/77 65/37,8 78,5 1

Enclosure.6 PG&E Letter DCL-05-112 HBL-05-024 Page2/3 4 - Inward leakage average - Fit Factor measured at the minimal air flow of 4501/mn (paragraph 2.3.3. of the CE Examination Type)

Suit no 1

2 Exercise Air flow m3lhl I/mn I cfm 30 / 500 / 17 31 / 516 /18 Standing still 130 000 130 000 Walking (5 km/h) 59 500 50 000 Moving arms up and down 125 000 125 000 above head Continuous squats 65 000 81 250 Bending forward 100 000 92 850 Person twisting at waist 115 000 130 000 Standing still 130 000 130 000 Average 103 500 103 440 5 - Pressure in the suit when measured at the maximum air flow when suit connected under 5,5 bar (77psig) feeding pressure (paragraph 4.12.of the EC Examination Type)

Suit n0 1

P Exercise P avel P min/ Pmax daPa.

daePan Max.

Standing still 40 38 Walking (5 km/h) 40 23 74 100 61 128 Moving arms up and down 40 17 62 46 18 72 above head Continuous squats 42 4

86 56 3

110 Bending forward 52 3

104 74 0

162 Person twisting at waist 38 18 58 46 20 110 Person crawling 37 40 For Information: Both overboots are breaked at the end of the test 2

Enclosure.6 PG&E Letter DCL-05-112 HBL-05-024 Page3/3 6 - Over pressure and fit factor when person crawling on the floor as indicated in paragraph 4.12 and 5.2.2 of the pr EN 1073-1 dated 1995 Crawling exercise Suit number Average DP Minimum DP Maximum DP Fit Factor daPa daPa j daPa 1

52 12 90 110 000 2

65 3

102 105 000 7 - Screen:( paragraph 5.2.5 )

- Distortion of the vision: none

- Mechanical resistance: no incidence on the screen.

3

Enclosure.7 PG&E Letter DCL-05-112 HBL-05-024 ATTACHMENT 5.7 INSTRUCTIONS FOR USE Total Number of Pages in this

Attachment:

1 (Not Including This Page)

NO/841 442T Enclosure INDICE: e Mururoa V4F1 and MTH2-V4.7 DATE: 12/00 PG&E Letter DCL-05-112 PAGE:1/1 HBL-05-024 INSTRUCTIONS FOR USE Preliminary remarks This clothing is to be used under the authority of the person responsible for issuing the equipment for its dedicated use:

- the clothing offers the necessary protection for it's intended use.

- Breathable air *network, hoses with connectors compatible with that of the clothing, are actually available on site and that they are capable of supplying a sufficient quantity of air:

minimum flow rate 600 liters/min. +1 0% at 6 Bars; (20 cfm at 85 psig) maximum flow rate 1200 liters/min. +1-10% at 6 Bars ; (40dfm at 85 psig)

DRESSING

- The wearer, with a helper, visually Inspects the condition of the garment and its components, then removes the shipping protection (cardboard on the visor and inside the garment, and removable plastic protection from the visor).

- He enters through the rear opening of the garment and insures that his legs are in the garment.

- Connects to the breathable air network by passing the supply line through the loop at the rear of the garment, at the same height as the supply valve.

- Connects,a communication device, if applicable, through the safety loop and communication loop and finishes dressing.

- The helper zips up the dual zipper system and applies a large strip of adhesive tape to the upper extremity of the second zipper at the top to ensure air tightness. He then, ties the over boot laces around the ankles.

- The wearer can control the air supply by turning the adjustment knob. The correct functioning of the supply flow valve and the over pressure valves can be verified by crouching down rapidly a few times.

- He then is free to enter the work zone.

UNDRESSING

- Undressing may be done in the following manner. While the garment is still being supplied with air. the helper pulls on the orange undressing strip, which runs from one wrist to the other over the hood. Once the undressing strip is removed, the helper can split the suit shell by pulling on the hooded area and separating the suit into two identical pieces. The helper rolls up the front and rear parts in a way that traps the contamination and avoids all contact with the wearer of the garment. (Please consult our video for detailed undressing techniques).

IMPORTANT

- Leave the work zone immediately if the clothing deflates during the work phase evolution.If the helmet fogs, or if the person has a feeling of excessive warmth.

- Remember that the clothing remains pressurised for a few minutes in case of an air supply failure STORAGE In the original packaging; out of the light; between + 5'C and + 45'C.( 41'F and 11 3F)

USAGE The air supply should be between + 15-C and + 45-C. ( 59'F and 113'F)

EXPIRY DATE The clothing should be used by the third year from the date of manufacture.

CLEANING Not necessary for this type of equipment which is for a single use only.

EMERGENCY FEATURES

- Air outside of the garment can be breathed by removing the safety strip at the front of the helmet/hood.

- The undressing strip, removed by the wearer, enables the wearer to self escape t in less than 5 seconds.

  • Breathable air: see the EN 132 standard.

1