ML052290003

From kanterella
Jump to navigation Jump to search

Response to Bulletin 2004-01, Inspection of Alloy 82/182/600 Materials Used in the Fabrication of Pressurizer Penetrations and Steam Space Piping Connections at Pressurized-Water Reactors, Response for the Prairie Island, Units 1 & 2
ML052290003
Person / Time
Site: Prairie Island  Xcel Energy icon.png
Issue date: 08/23/2005
From: Mahesh Chawla
NRC/NRR/DLPM/LPD3
To: Thomas J. Palmisano
Nuclear Management Co
Chawla M, NRR/DLPM, 415-8371
References
TAC MC3502, TAC MC3503
Download: ML052290003 (4)


Text

August 23, 2005 Mr. Thomas J. Palmisano Site Vice President Prairie Island Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Drive East Welch, MN 55089

SUBJECT:

BULLETIN 2004-01, INSPECTION OF ALLOY 82/182/600 MATERIALS USED IN THE FABRICATION OF PRESSURIZER PENETRATIONS AND STEAM SPACE PIPING CONNECTIONS AT PRESSURIZED-WATER REACTORS, RESPONSE FOR THE PRAIRIE ISLAND NUCLEAR GENERATING PLANT, UNITS 1 AND 2 (TAC NOS. MC3502 AND MC3503)

Dear Mr. Palmisano:

On May 28, 2004, the U.S. Nuclear Regulatory Commission (NRC) issued Bulletin 2004-01, Inspection of Alloy 82/182/600 Materials Used in the Fabrication of Pressurizer Penetrations and Steam Space Piping Connections at Pressurized-Water Reactors, to the industry. This Bulletin informed addressees that current methods of inspecting the pressurizer penetrations and steam space piping connections fabricated from Alloy 82/182/600 materials may need to be supplemented with additional measures (e.g., bare-metal visual inspections) to detect pressurizer penetration and steam space piping connection flaws or leakage. The Bulletin requested that these addressees provide the NRC with information related to the materials of construction, the inspections that have been performed, and the inspections which will be performed to verify the integrity of the pressurizer penetrations and steam space piping connections. By letter dated July 27, 2004, Nuclear Management Company, LLC (the licensee) provided its response to Bulletin 2004-01, for the Prairie Island Nuclear Generating Plant Units 1 and 2 (PINGP).

By this letter, the licensee provided its responses to items 1a, 1b, 1c, and 1d of the Bulletin.

These responses described the materials used in the fabrication of pressurizer penetrations and steam space piping connections at PINGP. When describing the materials used in the fabrication of the pressurizer penetrations and steam space piping connections, the licensee reported that none of the materials used in the fabrication of the pressurizer penetrations and steam space piping were Alloy 82/182/600 materials. Therefore, there is no specific inspection program for Alloy 82/182/600 materials for the pressurizer other than meeting the requirements of Section XI of the American Society for Mechanical Engineers, Boiler and Pressure Vessel Code.

Given the licensees response to items 1a, 1b, 1c, and 1d of the Bulletin, the NRC staff no longer requires a specific response for the PINGP for item 2 of the Bulletin, which requested that licensees report the results of their next scheduled inspection of Alloy 82/182/600 pressurizer penetrations and steam space piping connections.

T. Palmisano The NRC staff has completed its activities associated with the review of your response to Bulletin 2004-01, and finds your response acceptable. Please contact me at (301) 415-8371 if you have any questions on this issue.

Sincerely,

/RA/

Mahesh Chawla, Project Manager, Section 1 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-282 and 50-306 cc: See next page

ML052290003 OFFICE PDIII-1/PM PDIII-1/LA PDIII-1/SC NAME MChawla DClarke for THarris LRaghavan DATE 8/18/05 8/16/05 8/23/05

Prairie Island Nuclear Generating Plant, Units 1 and 2 cc:

Jonathan Rogoff, Esquire Vice President, Counsel & Secretary Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 Manager, Regulatory Affairs Prairie Island Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Drive East Welch, MN 55089 Manager - Environmental Protection Division Minnesota Attorney Generals Office 445 Minnesota St., Suite 900 St. Paul, MN 55101-2127 U.S. Nuclear Regulatory Commission Resident Inspector's Office 1719 Wakonade Drive East Welch, MN 55089-9642 Regional Administrator, Region III U.S. Nuclear Regulatory Commission 801 Warrenville Road Lisle, IL 60532-4351 Administrator Goodhue County Courthouse Box 408 Red Wing, MN 55066-0408 Commissioner Minnesota Department of Commerce 85 7th Place East, Suite 500 St. Paul, MN 55101-2198 Tribal Council Prairie Island Indian Community ATTN: Environmental Department 5636 Sturgeon Lake Road Welch, MN 55089 Nuclear Asset Manager Xcel Energy, Inc.

414 Nicollet Mall, R.S. 8 Minneapolis, MN 55401 John Paul Cowan Executive Vice President & Chief Nuclear Officer Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 Craig G. Anderson Senior Vice President, Group Operations Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 November 2004