August 9, 2005 Mr. Christopher M. Crane, President and Chief Executive Officer AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555

SUBJECT:

CLINTON POWER STATION, UNIT 1 - ISSUANCE OF AN AMENDMENT -

RE: REVISION OF THE APPENDIX B, ENVIRONMENTAL PROTECTION PLAN (NON-RADIOLOGICAL) (TAC NO. MC5462)

Dear Mr. Crane:

The U.S. Nuclear Regulatory Commission (Commission) has issued the enclosed Amendment No. 166 to Facility Operating License No. NPF-62 for the Clinton Power Station, Unit 1, in response to your application dated December 17, 2004. The amendment revises Appendix B, Environmental Protection Plan (non-radiological) of the Clinton Facility Operating License.

A copy of the Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commission's next biweekly Federal Register notice.

Sincerely,

/RA/

Kahtan N. Jabbour, Senior Project Manager, Section 2 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-461

Enclosures:

1. Amendment No. 166 to NPF-62
2. Safety Evaluation cc w/encls: See next page

ML052210029 (Package)

ADAMS ACCESSION NUMBER: ML052210006 (Letter)

ADAMS ACCESSION NUMBER: ML052230073 (Technical Specifications)

OFFICE PM:PD3-2 LA:PD3-2 SC: RLEP(A)

OGC SC:PD3-2 NAME KJabbour PCoates BZalcman AHodgdon GSuh DATE 8/9/05 8/9/05 7/14/05 7/25/05 8-9-05

Clinton Power Station, Unit 1 cc:

Senior Vice President - Nuclear Services AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Vice President Operations Support AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Vice President - Licensing and Regulatory Affairs AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Manager Licensing - Clinton and LaSalle AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Regulatory Assurance Manager - Clinton AmerGen Energy Company, LLC Clinton Power Station RR3, Box 228 Clinton, IL 61727-9351 Director Licensing AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Document Control Desk-Licensing AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Site Vice President - Clinton Power Station AmerGen Energy Company, LLC Clinton Power Station RR 3, Box 228 Clinton, IL 61727-9351 Clinton Power Station Plant Manager AmerGen Energy Company, LLC Clinton Power Station RR 3, Box 228 Clinton, IL 61727-9351 Resident Inspector U.S. Nuclear Regulatory Commission RR #3, Box 229A Clinton, IL 61727 Chief Operating Officer AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 Regional Administrator, Region III U.S. Nuclear Regulatory Commission 801 Warrenville Road Lisle, IL 60532-4351 Senior Counsel, Nuclear AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555 R. T. Hill Licensing Services Manager General Electric Company 175 Curtner Avenue, M/C 481 San Jose, CA 95125 Chairman of DeWitt County c/o County Clerks Office DeWitt County Courthouse Clinton, IL 61727 J. W. Blattner Project Manager Sargent & Lundy Engineers 55 East Monroe Street Chicago, IL 60603 Illinois Emergency Management Agency Division of Disaster Assistance &

Preparedness 110 East Adams Street Springfield, IL 62701-1109

AMERGEN ENERGY COMPANY, LLC DOCKET NO. 50-461 CLINTON POWER STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 166 License No. NPF-62 1.

The U.S. Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by AmerGen Energy Company, LLC (the licensee),

dated December 17, 2004, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Environmental Protection Plan contained in Appendix B, as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-62 is hereby amended to read as follows:

(2)

Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised through Amendment No. 166 are hereby incorporated into this license. AmerGen Energy Company, LLC shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of its date of issuance and shall be implemented within 60 days of the date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Gene Y. Suh, Chief, Section 2 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation

Attachment:

Changes to the Environmental Protection Plan Date of Issuance: August 9, 2005

ATTACHMENT TO LICENSE AMENDMENT NO. 166 FACILITY OPERATING LICENSE NO. NPF-62 DOCKET NO. 50-461 Replace the following pages of Appendix B, Environmental Protection Plan, with the enclosed pages. The revised pages are identified by an amendment number and contain marginal lines indicating the areas of change.

Remove Pages Insert Pages Table of contents Table of contents 1-1 1-1 2-1 2-1 2-2 3-1 3-1 3-2 3-2 4-1 4-1 5-1 5-2 5-2 5-3 5-2

SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 166 TO FACILITY OPERATING LICENSE NO. NPF-62 AMERGEN ENERGY COMPANY, LLC CLINTON POWER STATION, UNIT 1 DOCKET NO. 50-461

1.0 INTRODUCTION

By application dated December 17, 2004, Exelon Generation Company, LLC (EGC) and AmerGen Energy Company, LLC (AmerGen), the licensees, requested changes to Appendix B, Environmental Protection Plan (EPP), for Braidwood Station, Units 1 and 2; Byron Station, Units 1 and 2; Clinton Power Station, Unit 1; LaSalle County Station, Units 1 and 2; Limerick Generating Station, Units 1 and 2; Oyster Creek Nuclear Generating Station; Peach Bottom Atomic Power Station, Units 2 and 3; and Quad Cities Nuclear Power Station, Units 1 and 2.

This amendment addresses the licensees' proposed changes for Clinton Power Station (CPS).

Other amendments will be issued to address the proposed changes for the remaining operating units.

The proposed changes revise the EPP for Clinton Power Station by clarifying a number of items without changing the purpose, by removing the requirement for an annual report, by updating terminology, by deleting obsolete program information, and by standardizing wording in the EPP.

2.0 REGULATORY EVALUATION

The EPP was established during initial plant operation to monitor environmental issues such as potential erosion along the transmission lines and the cooling tower drift impact on vegetation, noise, and cultural resources issues. The regulatory basis for the establishment of the EPP is Section 50.36b of Title 10 of the Code of Federal Regulations (10 CFR), "Environmental conditions." This section authorizes the NRC staff to place conditions on a license to protect the environment. The regulation states that the conditions will identify the "obligations of the licensees in the environmental area, including, as appropriate, requirements for reporting and keeping records of environmental data, and any conditions and monitoring requirement for the protection of the nonaquatic environment" and that the conditions will be derived from the licensees environmental report and NRCs evaluation in the record of decision. However, in the March 12, 1984, statements of consideration for the final rule that created 50.36b, the Commission stated that NRC "may also include additional environmental conditions as appropriate."

3.0 TECHNICAL EVALUATION

Section 1.0 Objectives of the Environmental Protection Plan Requested Action A change is requested to remove the reference to facility construction from Section 1.0. This section contains the objectives of the EPP, which is to provide for protection of the environmental values during operation of the nuclear facility. Construction is complete at CPS and therefore the reference to construction is deleted.

NRC Staff Analysis The facility construction reference was included to cover the impacts related to the latter stages of the construction of the plant. The associated activities were completed many years ago.

Therefore, the staff concludes that removal of the reference is acceptable. The remaining text ensures that impacts related to current and future activities at the plant are considered under the EPP. This administrative change is acceptable.

Section 2.1 Aquatic Issues Requested Action This section of the EPP references the Illinois Environmental Protection Agency as the issuer of the National Pollutant Discharge Elimination System (NPDES) permit. The proposed change will standardize the issuer of the NPDES permit to be the Federal or State permitting authority.

The use of a more generic reference to the permitting authority will prevent future changes in the structure of the state government from creating new inconsistencies.

NRC Staff Analysis The proposed change is administrative in nature and corrects existing inaccuracies. The use of a more generic reference to the permitting authority will prevent future changes in the structure of the state government from creating new inconsistencies. The NRC staff concludes that this change is acceptable.

Section 3.1 Plant Design and Operation Requested Action As discussed below under the analysis for Subsection 5.4.1, the Annual Environmental Operating Report will no longer be required. Therefore, the change requested is to delete the reference to the report in Section 3.1.

NRC Staff Analysis The staffs analysis and conclusion regarding the need for the annual report is discussed in the evaluation for Subsection 5.4.1. Without the annual report, the NRC staff will not receive summaries of the evaluations of changes by the licensees. However, these evaluations will be available for staff review at the plant. In addition, Section 3.1 will still require the licensees to obtain NRC staff approval for any changes that involve an unreviewed environmental question.

Based on this, the staff concludes that the removal of the requirement for annual reporting of the licensees' evaluations for unreviewed environmental questions is acceptable.

Section 3.2 Reporting Related to NPDES Permits and State Certification Requested Action The proposed changes in Section 3.2 are to revise the reporting requirements related to approval or changes to the NPDES permit or State certification.

Currently this section requires that changes and additions to the NPDES permit or the State Certification shall be reported to the NRC. This section also requires that a proposed revision be sent to the NRC at the same time as it is submitted to the permitting agency. The NRC relies on the State regulatory agency to regulate these matters. Changes to the NPDES permit or State Certification will continue to be provided to the NRC within 30 days of approval.

Proposed changes will no longer be provided to the NRC. Information related to environmental permits will continue to be available onsite for NRC review.

NRC Staff Analysis The EPP requires the licensees to provide the NRC staff with copies of proposed revisions to, or renewals of, the NPDES permits. However, the NRC staff does not have a role in determining the NPDES limits for the plants. This responsibility lies with the appropriate NPDES permitting authority. Therefore, requiring the licensees to submit proposed NPDES permit changes is of little value to the NRC staff. The paragraph that will remain in the EPP will still require the licensees to provide the staff with copies of the approved revised permits. This requirement will allow the NRC staff to remain cognizant of those environmental impacts of plant operations related to the permits. In addition, the EPP will continue to require the licensees to evaluate plant changes for unreviewed environmental questions. This requirement ensures that significant changes to the environmental impacts of plant operation will receive an NRC staff review that is independent of the NPDES review by the permitting authority. While the NRC staff will have no role in setting the limits in the NPDES permit, the staff will consider other impacts (e.g., to threatened and endangered aquatic species) that may not be included in the NPDES review. Based on this information, the staff concludes that the proposed changes are acceptable.

Section 3.3 Changes Required for Compliance with Other Environmental Regulations Requested Action A change is proposed to replace the phrase "required to achieve compliance with" with the phrase "that are either regulated or mandated by." This section exempts those changes that

are regulated or mandated by other Federal, State, and local environmental regulations from the requirements of Section 3.1. An additional sentence has been added to state, "However, if an environmental impact of a change is not evaluated under other Federal, State or local environmental regulations, then this impact is subject to the requirements of Section 3.1." This is an administrative change to improve clarity and understanding and does not change the objective of the original statement.

NRC Staff Analysis The current Section 3.3 applies the exemption from Section 3.1 only to those changes, tests, or experiments that are required to achieve compliance with the regulations of various agencies.

The revision expands this exemption to include environmental impacts that are evaluated by these various agencies. This change has the effect of focusing Section 3.1 on those environmental impacts that will not otherwise receive a review by a cognizant Federal, State, or local agency. Impacts that are the subject of the expansion of the exemption will still be evaluated, but by the appropriate cognizant agency. Therefore, the NRC staff concludes that this change is acceptable.

Section 4.1 Unusual or Important Environmental Events Requested Action A change is proposed that if an event is reportable under 10 CFR 50.72, "Immediate notification requirements for operating nuclear power reactors," then a duplicate immediate report in accordance with the stations EPP is not required. Requirements are provided in the EPP to report Unusual or Important Environmental Events to the NRC within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Unusual and Important Environmental Events are defined as any occurrence of an event that indicates or could result in significant environmental impact causally related to plant operation. Such events shall be recorded and reported to the NRC within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and followed by a written report.

Similarly, 10 CFR 50.72 (b)(2)(xi) states that the licensee shall notify the NRC as soon as practical and in all cases, within four hours of the occurrence of... "any event or situation, related to the health and safety of the public or onsite personnel, or protection of the environment, for which a news release is planned or notification to other government agencies has been or will be made." The change proposed will relieve the administrative burden of making duplicate reports to the NRC for the same event. Follow-up written reports are still required to be submitted in accordance with the EPP.

The change to delete references to telephone, telegraph or facsimile is to align the text of the EPP into conformance with the present methods of reporting events to the NRC.

NRC Staff Analysis In some of the EPPs, specific methods of transmittal (e.g., by telephone, telegraph, or facsimile transmissions) are included. The proposed changes would delete these details. This first change is administrative in nature, bringing the text of the EPPs into conformance with the present methods used to make immediate reports regarding events to the NRC. The second change is a clarification to avoid potential duplicate reporting requirements. Note that at the

time the EPPs were developed, there was no environmental reporting requirement in 10 CFR 50.72. Thus, at that time there was not an issue with the potential for duplicate reporting.

Section 4.2 Environmental Monitoring Requested Action The proposed change will standardize the agencies outside the NRC that provide jurisdiction over the Environmental Monitoring programs to be the Federal or State permitting authority instead of the Illinois Environmental Protection Agency, Illinois Department of Public Health, and Department of Transportation. The use of a more generic reference to the permitting authority will prevent future changes in the structure of the state government from creating new inconsistencies. In addition, the NRC relies on the State and Federal permitting authority to regulate matters in accordance with Section 2.0.

NRC Staff Analysis The NRC staff concludes that the proposed change is administrative in nature and is acceptable.

Section 5.2 Records Retention Requested Action A revision is proposed to change the requirement of log and data retention and retention timeframe from the "life of the plant" to "until the date of termination of the operating license."

This section requires retention of records relative to the environmental aspects of plant operation and modifications determined to potentially affect the continued protection of the environment. A change is proposed to remove the requirement of data and log retention and delete the requirement for preoperational environmental monitoring records, procedures, data and logs. The requirement to maintain all records is maintained. There are no dedicated environmental logs maintained on site. Logs relative to the environment are required to be documented by specific State permits (i.e., NPDES Permit) and EGC and AmerGen environmental administrative procedures. Such entries are maintained as part of station operating logs. The reference to environmental logs has been deleted for clarity but the purpose of the original statements is maintained.

The proposed change in the retention timeframe to the termination of the operating license makes the requirement consistent with similar requirements in other regulations (i.e., 10 CFR 50.59). This change has been proposed to provide clarity but does not change the objective of the requirement.

NRC Staff Analysis The proposed change regarding the types of records retained simplifies the EPP by requiring the retention of records associated with the EPP. The existing reference to data and logs refers to information that would have been collected under the now-completed monitoring programs.

The change to the stated retention period makes the requirement consistent with other similar

requirements in the NRC regulations (e.g., 10 CFR 50.59, "Changes, tests, and experiments").

The NRC staff concludes that this change is acceptable.

Section 5.4.1 Routine Reports Requested Action A change is proposed to delete the entire section relating to Routine Reports. This section requires an annual environmental operating report be submitted to the NRC by May 1 of each year. The report includes a list of EPP noncompliances and the corrective actions taken to remedy them, all changes in the station design or operation, tests, and experiments made in accordance with Section 3.1 involving potentially significant unreviewed environmental issues, a list of nonroutine reports submitted in accordance with Subsection 5.4.2, and a list of any results and/or assessments for the environmental monitoring programs described in Subsection 2.0.

Environmental non-compliances are reported as required by 10 CFR 50.72, "Immediate notification requirements for operating nuclear power reactors," and corrective actions will be included in the Exelon/AmerGen Corrective Action Program (CAP). Design changes are addressed by the EGC and AmerGen implementing procedures associated with 10 CFR 50.59, "Changes, tests and experiments" and Section 3.1 of this EPP. If an environmental evaluation indicates that an activity involves an unreviewed environmental question, or involves a change to the EPP, prior NRC approval must be obtained prior to implementation.

All environmental monitoring programs described in Subsection 2.0 have been completed with the exception of a level of effort monitoring program. The ongoing level of effort monitoring for the Unit 2 excavation is accomplished by the NPDES Permit. Outfall 010 of the NPDES permit is the Unit 2 excavation area and is monitored in accordance with the Storm Water Pollution Prevention Plan. Any issues resulting from the implementation of this plan are documented into the Exelon/AmerGen CAP.

With reporting requirements fully addressed in 10 CFR 50.72, the EGC and AmerGen 10 CFR 50.59 Review Program and Environmental Evaluation Program and the NPDES permit, it is proposed that Section 5.4.1 be deleted in its entirety.

NRC Staff Analysis Monitoring programs are either done, or are monitored by the cognizant State agency. Based on the existing requirements in NRC regulations, the NRC staff concludes that the annual report is not necessary and this requirement can be deleted.

Section 5.4.2 Nonroutine Reports Requested Action A change is proposed to Section 5.4.2 to revise a "non-routine event" to be an "unusual or important environmental event."

Currently this section requires written reports to be sent to the NRC within 30 days of occurrence of a nonroutine event. An administrative change is being made to clarify the

objective of the section to refer to an "unusual or important environmental event" as described in Section 4.1 of Appendix B. This change is also for consistency with all other EGC and AmerGen stations.

With the proposed deletion of Section 5.4.1, it is also proposed to delete the numbering and title of Section 5.4.2, "Nonroutine Reports," and therefore designate the body of Section 5.4.2 under 5.4, "Plant Reporting Requirements." This change provides clarity only and does not delete any content of the existing Section 5.4.2.

NRC Staff Analysis The NRC staff has reviewed the EPP and concludes that the intent of Subsection 5.4.2 was to require a written report for the events described in Subsection 4.1. Therefore, the staff concludes that the proposed change is acceptable.

4.0 STATE CONSULTATION

In accordance with the Commission's regulations, the Illinois State official was notified of the proposed issuance of the amendment. The State official had no comments.

5.0 ENVIRONMENTAL CONSIDERATION

This amendment changes a requirement with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20 or changes a surveillance requirement. The NRC staff has determined that the amendment involves no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendment involves no significant hazards consideration and there has been no public comment on such finding (70 FR 19112). Accordingly, the amendment meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b),

no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendment.

6.0 CONCLUSION

The staff has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.

Principal Contributors: A. Kugler and C. Guerrero Date: August 9, 2005