ML052200497
| ML052200497 | |
| Person / Time | |
|---|---|
| Site: | Fermi |
| Issue date: | 07/26/2005 |
| From: | Detroit Edison |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| Download: ML052200497 (14) | |
Text
%
DETROIT EDISON -
FERMI 2 AUTOMATED RECORD MANAGEMENT DISTRIBUTION CONTROL LIST 07/26/05 To: 00935~
US NRC DOCUMENT CNTRL DESK PAGE 1
WASHINGTON, DC 20555 Media: 8 1/2 X 11 Number Cnt Issue DTC Doc. Serial Number Page Rev Copies Lvl Date Sec Status TMTRM TRM VOL I 75 1
IR 07/26/05 AFC Please destroy or mark all revised, superseded, or cancelled documents as such.
CONTROLLED stamps must be voided by lining through and initialing.
Detroit Edison EF2, C/O Info Mgmt 140 NOC, 6400 North Dixie Highway, Newport MI 48166. (734) 586-4338 OR (734) 586-4061 for questions or concerns.
Ref: cb14612 A°SoI
LICENSING DOCUMENT TRANSMITTAL FERMI 2 TECHNICAL REQUIREMENTS MANUAL - VOL I Revision 75 dated 7/26/05 Immediately, upon receipt of the item(s) below, please insert and/or remove the pages indicated.
Destroy the removed pages. Be sure that Revision 74 has been inserted prior to inserting these pages.
Location Remove Insert In Front of TRM Manual Immediately following Title Pagc 3.12 Fire Protection Title Page Rev 74 2/17/05 List of Effective Pages LEP-1 through LEP-4 Rev 74 2/17/05 Page TRM 3.12-1 Rev 31 Page TRM 3.12-13 Rev 31 Page TRM 3.12-16 Rev 31 Page TRM 3.12-18 Rev 31 Page TRM 3.12-20 Rev 31 Page TRM 3.12-26 Rev 31 Pace TRM 3.12-29 Rev 31 Title Page Rev 75 7/26/05 List of Effective Pages
-LEP-1 through LEP-4 Rev 75 7/26/05 Page TRM 3.12-1 Rev 75 Page TRM 3.12-13 Rev 75 Page TRM 3.12-16 Rev 75 Page TRM 3.12-18 Rev 75 Page TRM 3.12-20 Rev 75 Page TRM 3.12-26 Rev 75 Page TRM 3.12-29 Rev 75 END
Fermi 2 Technical Requirements Manual Volume I Detroit Edison ARMS - INFORMATION DTC: TMTRM l File: 1754 1 DSN: TRM VOL I l Rev: 75 Date 7/26/05 Recipient 9 3 5
t FERMI 2 -
TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES Page Revision Page Revision TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM iviii iv v
Vi 1.0-a 1.0-1 2.0-1 3.0-a 3.0-1 3.0-2 3.0-3 3.0-4 3.1-a 3.1-1 3.2-1 3.3-a 3.3-b 3.3-c 3.3-d 3.3-1 3.3-2 3.3-3 3.3-4 3.3-5 3.3-6 3.3-7 3.3-8 3.3-9 3.3-10 3.3-11 3.3-12 3.3-13 3.3-13a 3.3-14 3.3-15 3.3-16 3.3-17 3.3-18 3.3-19 3.3-20 3.3-21 3.3-22 3.3-23 3.3-24 3.3-25 3.3-26 3.3-27 3.3-28 3.3-29 3.3-30 Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision 31 73 31 34 70 31 31 31 31 31 63 72 54 72 31 31 31 31 31 31 31 34 59 31 31 31 31 31 31 31 31 31 67 74 67 67 31 31 31 52 31 31 59 31 31 31 31 31 31 31 31 31 TRM 3.3-31 TRM 3.3-32 TRM 3.3-33 TRM 3.3-34 TRM 3.3-35 TRM 3.3-36 TRM 3.3-37 TRM 3.3-38 TRM 3.3-39 TRM 3.3-40 TRM 3.3-41 TRM 3.3-42 TRM 3.3-43 TRM 3.3-44 TRM 3.3-45 TRM 3.3-46 TRM 3.3-47 TRM 3.3-48 TRM 3.3-49 TRM 3.4-a TRM 3.4-1 TRM 3.4-la TRM 3.4-lb TRM 3.4-2 TRM 3.4-3 TRM 3.4-4 TRM 3.4-5 TRM 3.4-6 TRM 3.4-7 TRM 3.4-8 TRM 3.4-9 TRM 3.4-10 TRM 3.5-1 TRM 3.6-a TRM 3.6-1 TRM 3.6-2 TRM 3.6-3 TRM 3.6-4 TRM 3.6-5 TRM 3.6-6 TRM 3.6-7 TRM 3.6-8 TRM 3.6-9 TRM 3.6-10 TRM 3.6-11 TRM 3.6-12 TRM 3.6-13 TRM 3.6-14 TRM 3.6-15 TRM 3.6-16 TRM 3.6-17 TRM 3.6-18 Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision 31 31 31 31 60 41 72 31 31 56 56 45 62 72 31 31 31 31 31 31 36 71 71 31 31 31 31 31 31 31 31 31 31 70 60 67 31 55 31 33 31 31 66 31 31 31 71 31 31 31 31 31 TRM Vol. I LEP-1 REV 75 7/26/05
FERMI 2 -
TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES Page Revision Page Revision TRM 3.6-19 Revision 31 TRM 3.8-13 Revision 61 TRM 3.6-20 Revision 31 TRM 3.8-14 Revision 46 TRM 3.6-21 Revision 31 TRM 3.8-15 Revision 31 TRM 3.6-22 Revision 31 TRM 3.8-16 Revision 31 TRM 3.6-23 Revision 31 TRM 3.8-17 Revision 43 TRM 3.6-24 Revision 58 TRM 3.8-18 Revision 33 TRM 3.6-25 Revision 31 TRM 3.9-a Revision 31 TRM 3.6-26 Revision 31 TRM 3.9-1 Revision 31 TRM 3.6-27 Revision 31 TRM 3.9-2 Revision 65 TRM 3.6-28 Revision 31 TRM 3.9-3 Revision 31 TRM 3.6-29 Revision 31 TRM 3.9-4 Revision 31 TRM 3.6-30 Revision 31 TRM 3.9-5 Revision 31 TRM 3.6-31 Revision 31 TRM 3.10-1 Revision 31 TRM 3.6-32 Revision 70 TRM 3.11-a Revision 31 TRM 3.6-33 Revision 31 TRM 3.11-1 Revision 31 TRM 3.6-34 Revision 31 TRM 3.12-a Revision 31 TRM 3.6-35 Revision 31 TRM 3.12-1 Revision 75 TRM 3.7-a Revision 73 TRM 3.12-2 Revision 31 TRM 3.7-b Revision 31 TRM 3.12-3 Revision 31 TRM 3.7-1 Revision 60 TRM 3.12-4 Revision 53 TRM 3.7-2 Revision 70 TRM 3.12-5 Revision 53 TRM 3.7-3 Revision 70 TRM 3.12-6 Revision 53 TRM 3.7-4 Revision 73 TRM 3.12-7 Revision 31 TRM 3.7-5 Revision 31 TRM 3.12-8 Revision 57 TRM 3.7-6 Revision 31 TRM 3.12-9 Revision 40 TRM 3.7-7 Revision 31 TRM 3.12-10 Revision 31 TRM 3.7-8 Revision 31 TRM 3.12-11 Revision 49 TRM 3.7-9 Revision 31 TRM 3.12-12 Revision 31 TRM 3.7-10 Revision 44 TRM 3.12-13 Revision 75 TRM 3.7-11 Revision 31 TRM 3.12-14 Revision 31 TRM 3.7-12 Revision 72 TRM 3.12-15 Revision 31 TRM 3.7-13 Revision 31 TRM 3.12-16 Revision 75 TRM 3.7-14 Revision 31 TRM 3.12-17 Revision 31 TRM 3.7-15 Revision 31 TRM 3.12-18 Revision 75 TRM 3.7-16 Revision 31 TRM 3.12-19 Revision 31 TRM 3.7-17 Revision 31 TRM 3.12-20 Revision 75 TRM 3.7-18 Revision 31 TRM 3.12-21 Revision 31 TRM 3.7-19 Revision 31 TRM 3.12-22 Revision 31 TRM 3.7-20 Revision 31 TRM 3.12-23 Revision 31 TRM 3.8-a Revision 31 TRM 3.12-24 Revision 31 TRM 3.8-1 Revision 31 TRM 3.12-25 Revision 31 TRM 3.8-2 Revision 31 TRM 3.12-26 Revision 75 TRM 3.8-3 Revision 73 TRM 3.12-27 Revision 31 TRM 3.8-4 Revision 31 TRM 3.12-28 Revision 31 TRM 3.8-5 Revision 31 TRM 3.12-29 Revision 75 TRM 3.8-6 Revision 50 TRM 3.12-30 Revision 31 TRM 3.8-7 Revision 50 TRM 4.0-1 Revision 31 TRM 3.8-8 Revision 50 TRM 5.0-a Revision 31 TRM 3.8-9 Revision 50 TRM 5.0-1 Revision 31 TRM 3.8-10 Revision 50 TRM 5.0-2 Revision 31 TRM 3.8-11 Revision 50 TRM 5.0-3 Revision 31 TRM 3.8-12 Revision 31 TRM 5.0-4 Revision 31 TRM Vol. I LEP-2 REV 75 7/26/05
I FERMI 2 -
TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES Page Revision Page Revision TRM TRM TRM TRN TRM TRN TRN TRM TRM TRM TRM TRM TRN TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM 5.0-5 5.0-6 5.0-7 5.0-8 5.0-9 B1.0-1 B2.0-1 B3.0-1 B3.0-2 B3.0-2a B3.0-2b B3.0-2c B3.0-3 B3.0-4 B3.0-5 B3.0-6 B3.0-7 33.1-1 B3.2-1 B3.3.1-1 B3.3.1-2 B3.3.2-1 B3.3.2-2 B3.3.3-1 B3.3.4-1 B3.3.4-2 B3.3.5-1 B3.3.5-2 B3.3.6-1 B3.3.6-2 B3.3.6-3 B3.3.6-4 B3.3.6-5 B3.3.7-1 B3.3.7-2 B3.3.8-1 B3.3.9-1 B3.3.10-1 B3.3.11-1 B3.3.12-1 B3.3.13-1 33.3.14-1 B3.4.1-1 B3.4.1-2 B3.4.1-3 B3.4.1-4 B3.4.1-5 B3.4.2-1 B3.4.3-1 B3.4.4-1 B3.4.5-1 33.4.6-1 Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision 31 31 31 31 31 31 31 63 63 72 72 72 31 31 54 72 72 31 31 31 31 31 31 67 31 31 31 31 31 31 31 31 31 31 31 31 31 56 45 62 31 31 31 71 71 71 71 31 31 31 31 31 TRM TRM TRM TRM TRM TRN TRN TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRN TRM TRM TRM TRM TRM TRM TRM TRM TRM TRN TRN TRM TRM TRM B3.4.7-1 B3.5-1 B3.6.1-1 B3.6.2-1 B3.6.3-1 B3.6.4-1 B3.6.5-1 B3.6.6-1 B3.6.7-1 B3.6.8-1 B3.7.1-1 B3.7.2-1 B3.7.3-1 B3.7.4-1 B3.7.4-2 B3.7.5-1 B3.7.6-1 B3.7.7-1 B3.7.8-1 B3.7.9-1 B3.7.9-2 B3.8.1-1 B3.8.2-1 B3.8.3-1 B3.8.'4-1 B3.8.5-1 B3.8.6-1 B3.9.1-1 B3.9.2-1 B3.9.3-1 B3.9.4-1 B3.10-1 B3.11.1-1 B3.12.1-1 B3.12.2-1 B3.12.3-1 B3.12.4-1 B3.12.5-1 B3.12.6-1 B3.12.7-1 B3.12.8-1 Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision 31 31 31 67 68 31 31 70 31 31 31 31 73 31 31 31 31 31 31 31 31 31 31 31 31 31 43 31 65 31 31 31 31 31 44 31 31 31 31 31 31 TRM Vol. I LEP-3 REV 75 7/26/05
FERMI 2 -
TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES CORE OPERATING LIMITS REPORT COLR 11, Revision 0 Page Revision Notation Page 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
0 10 0
11 0
12 0
13 0
14 0
15 0
16 0
17 0
18 0
19 0
20 0
21 0
22 0
TRM Vol. I LEP-4 REV 75 7/26/05
Fire Detection Instrumentation TR 3.12.1 TR 3.12 FIRE PROTECTION TR 3.12.1 Fire Detection Instrumentation TRLCO 3.12.1 The fire detection instrumentation for each fire detection zone shown in Table TR3.12.1-1 shall be OPERABLE.
APPLICABILITY:
When equipment protected by the fire detection instrumentation is required to be OPERABLE.
ACTIONS
NOTE-------------------------------------
Separate Condition entry is allowed for each instrument.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more zones with A.1 Restore Function A 14 days
< the total number of instruments) to instruments shown in OPERABLE status.
Table TR3.12.1-1 for Function A, but > one half of the total number of instruments shown in Table TR3.12.1-1 for Function A.
(continued)
TRM Vol. I TRM 3.12-1 REV 75 07/05
Spray and Sprinkler Systems TR 3.12.3 TR 3.12 FIRE PROTECTION TR 3.12.3 Spray and Sprinkler Systems TRLCO 3.12.3 APPLICABILITY:
The spray and sprinkler system shown in Table TR3.12.3-1 shall be OPERABLE.
When equipment protected by the spray and/or sprinkler systems is required to be OPERABLE.
ACTIONS
NOTE-------------------------------------
Separate Condition entry is allowed for each system.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more required A.1
NOTE---------
spray and/or sprinkler Only applicable to systems inoperable.
areas l.a, 1.d, 1.e, 2.a, 2.b, and 2.d.
Establish a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> continuous fire watch with backup fire suppression equipment.
AND A.2
NOTE---------
Only applicable to areas 1.b, l.c, 1.f, 2.c, 3.a, and 4.a.
Establish an hourly l hour fire watch patrol.
TRM Vol. I TRM 3.12-13 REV 75 07/05
CO2 Systems TR 3.12.4 TR 3.12 FIRE PROTECTION TR 3.12.4 CO2 Systems TRLCO 3.12.4 The following low pressure CO2 systems shall be OPERABLE:
- a.
Emergency diesel generators, RHR complex;
- b.
Standby gas treatment system charcoal filters, Auxiliary Building, elevation 677 ft 6 in;
- c.
Cable tray area, Auxiliary Building, elevation 631 ft; and
- d.
Outside Division II switchgear room, Auxiliary Building, elevation 643 ft 6 in.
APPLICABILITY:
When equipment protected by the CO2 systems is required to be OPERABLE.
ACTIONS
NOTE-------------------------------------
Separate Condition entry is allowed for each system.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more of the A.1
NOTE--------
above required CO2 Only applicable to systems inoperable.
systems c and d above.
Establish a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> continuous fire watch with backup fire suppression equipment.
AND A.2
NOTE--------
Only applicable to systems a and b above.
Establish an hourly 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> fire watch patrol.
TRM Vol. I TRM 3.12-16 REV 75 07/05
II Halon Systems TR 3.12.5 TR 3.12 FIRE PROTECTION TR 3.12.5 Halon Systems TRLCO 3.12.5 The following halon systems shall be OPERABLE with the storage tanks of either the main bank or the reserve bank having at least 95% of the main bank or the reserve bank full charge weight and 90% of the main bank or the reserve bank full charge pressure:
- a. Relay room, elevation 613 ft 6 in;
- b.
Cable spreading room, elevation 630 ft 6 in; and
- c.
Computer room, and under floor, elevation 655 ft 6 in.
APPLICABILITY:
When equipment protection by the halon systems is required to be OPERABLE.
ACTIONS
NOTE------------------------------------
Separate Condition entry is allowed for each system.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more of the A.1
NOTE--------
above required Halon Only applicable to systems inoperable.
systems a and b above.
Establish a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> continuous fire watch with backup fire suppression equipment.
AND A.2
NOTE--------
Only applicable to system c above.
Establish an hourly 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> fire watch patrol.
TRM Vol. I TRM 3.12-18 REV 75 07/05
i Fire Hose Stations TR 3.12.6 TR 3.12 FIRE PROTECTION TR 3.12.6 Fire Hose Stations TRLCO 3.12.6 APPLICABILITY:
The fire hose stations shown in Table TR3.12.6-1 shall be OPERABLE.
When equipment in the areas protected by the fire hose stations is required to be OPERABLE.
ACTIONS
_------------------------NOTE-------------------------------------
Separate Condition entry is allowed for each fire hose station.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more fire hose
NOTES------------
stations shown in
- 1. One outlet of the wye shall Table TR3.12.6-1 be connected to the inoperable.
standard length of hose provided for the hose station.
- 2. The second outlet of the wye shall be connected to a length of hose sufficient to provide coverage for the area left unprotected by the inoperable hose station.
- 3. Where it can be demonstrated that the physical routing of the fire hose would result in a recognizable hazard to operating technicians, plant equipment, or the hose itself, the fire hose shall be stored in a roll at the outlet of the OPERABLE hose station.
- 4. Signs shall be mounted above the gated wye(s) to identify the proper hose to use.
(continued)
TRM Vol. I TRM 3.12-20 REV 75 07/.05
Yard Fire Hydrants and Hydrant Hose Houses TR 3.12.7 TR 3.12 FIRE PROTECTION TR 3.12.7 Yard Fire Hydrants and Hydrant Hose Houses TRLCO 3.12.7 APPLICABILITY:
The yard fire hydrants and associated hydrant hose houses shown in Table TR3.12.7-1 shall be OPERABLE.
When equipment in the areas protected by the yard fire hydrants is required to be OPERABLE.
ACTIONS
NOTE-------------------------------------
Separate Condition entry is allowed for each yard fire hydrant.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more of the A.1
NOTE--------
yard fire hydrants or Only applicable if associated hydrant the inoperable fire houses shown in Table hydrant or associated TR3.12.7-1 inoperable.
hydrant hose house is the primary means of fire suppression.
Have additional 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> lengths of 2 % inch diameter hose located in an adjacent OPERABLE hydrant hose house to provide service to the unprotected area(s).
AND A.2
NOTE--------
Only applicable if the inoperable fire hydrant or associated hydrant hose house is not the primary means of fire suppression.
Have additional 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> lengths of 2 % inch diameter hose located in an adjacent OPERABLE hydrant hose house to provide service to the unprotected area(s).
TRM Vol. I TRM 3.12-26 REV 75 07/05
t Fire Rated Assemblies TR 3.12.8 TR 3.12 FIRE PROTECTION TR 3.12.8 Fire Rated Assemblies TRLCO 3.12.8 APPLICABILITY:
All fire rated assemblies, including walls, floor/ceilings, cable tray enclosures and other fire barriers, separating safety related fire areas or separating portions of redundant systems important to safe shutdown within a fire area, and all sealing devices in fire rated assembly penetrations including fire doors, fire dampers, cable, piping and ventilation duct penetration seals and ventilation seals, shall be OPERABLE.
At all times.
ACTIONS
NOTE-------------------------------------
Separate Condition entry is allowed for each fire rated assembly.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more of the A.1 Establish a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> above required fire continuous fire watch rated assemblies on at least one side and/or sealing devices of the affected inoperable.
assembly(s) and/or sealing device(s).
OR A.2.1 Verify the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OPERABILITY of fire
-detectors on at least one side of the inoperable assembly(s) and sealing device(s).
AND A.2.2 Establish an hourly 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> fire watch patrol.