ML051460425
| ML051460425 | |
| Person / Time | |
|---|---|
| Site: | Point Beach (DPR-024) |
| Issue date: | 03/28/2004 |
| From: | - No Known Affiliation |
| To: | Office of Nuclear Reactor Regulation |
| References | |
| FOIA/PA-2004-0282 RWP 04-104, Rev 0 | |
| Download: ML051460425 (4) | |
Text
Nuclear Power Business Unit RADIATION WORK PERMIT P nn SrDA Revision:
0 RNN'P Number:
04-104 Controlling Work Document:
Various RG 1.16 Class:
2 Estimated Dose:
6.000 Rem Job
Title:
RP Coverage Job Location:
PAB and U-I CTMT Job
Description:
Support Duties for RP.
Radiological Assessment of Work Significant increase in radiation levels is likely?
EjYCs 3No Reason:
Significant increase in contamination levels is likely? [Yes 0No Reason:
Potential for internal dose?
QYCs ZNo Reason:
RWP Tasks Task 1:
RP Outage Activities Task 2:
Task 3:
Task 4:
Task 5:
Task 6:
Task 7:
Task 8:
Task 9:
- Task 10:
Task 11:
Task 12:
RWP Review and Approval Prepared By:
CD Initials 02-24-04 Date ALARA Review By:
Approved By:
Terminated By:
ALARA Review No.:
In nitials Date 123 N/A
[E i-2 Dte Date RP Supervisor RP Supervisor Date 11 eixmt"ns $l ub Fiasco in acw it f~t o~ndkmft Act, enemy tL-z PBF.4031 Revision 12 12!10,'03 HIP 1.10/P6.8 Page 1 of 4
Nuclear Power Business Unit RADIATION WORK PERMIT Revision:
0
( nn P V'4'7OF W 13 U
RNNWP Number:
04-104 TASK 1: RP Outage Activities-Radiation Protection personnel are authorized to suspend work activities in the event of a change in job scope, changes in radiological conditions, or a failure of personnel working under the RWP to abide by the RWP conditions.
Stop Work Dose Rate:
10,000 mRlhr ED Dose Rate Alarm:
804 mR/hr ED Dose Alarm:
100 mrem Radiation Protection Hold Points:
EN/A No entry to areas posted VHRA and areas affected by radiography Personnel entering Locked high radiation areas whose radiation levels are affected by the transfer of spent fuel assemblies during refueling evolutions shall establish radio communications with the core load supervisor or DSS. The core load supervisor or DSS will authorize entry Into the area only when fuel is not being moved through the fuel transfer tube. Personnel will be notified when fuel is to be moved through the fuel transfer tube and must Immediately exit the area until authorized to reenter. Personnel entering the area are to notify the authorizing individual upon job completion and exit from the area.
When accessing an LHRA the key user must notify RP supervision prior to the entry and immediately upon completion of the entry. The key user Is required to have a concurrent check of the gateldoor lock.
Authorized Radiological Work Areas: Any RWVP permits entry into RCA(s), RMA, and RA.
0 HRA D LHRA El VHRA El Ctmt, Reactor Critical ED CA 0D HCA 0D HPCA 0D Airborne Radioactivity Area Expected Radiological Conditions:
Data From El Current Survey C Historical Data 0 Estimated Radiation: GA
< 2 to 4000 mnrem/hr
Contact:
20 to 7000 mrem/hr Contamination:
300 to 320 k dpm'l 00 cm2 Internal Contamination:
300 to
>IE6 dprnV1 00 cr 2 (Z estimated)
Airborne Radioactivity:
<.1 DAC 0 P El 12 03 NG l OH (0D Estimated / E Actual DAC)
RP Job Coverage: El Routine El Direct ED Start of Job
[I System Breach [E Pre-Job Briefing Required Special Instructions:
Provide job coverage in accordance with applicable RP procedures.
PBF-4031 Revision 12 12!10/03 HP 1.1O/P6.8 Page 2 of 4
Nuclear Power Business Unit RADIATION WORK PERMIT Revision:
0
/
j F =:; " \\. //7 1
1
. i
%# r U RNVP Number:
04-104 Radiological Survey Requirements:
A. Radiation:
E] Priorto!StartofWork Dl SystemrBreach 0N Other B. i Special Instructions:
As per RP Contamination:
a1 Prior to/Start of Work El System Breach Special Instructions:
As per RP. Hot Particle checks as necessary.
Airborne:
El Prior tolStart of Work n System Breach 0 Other C. J 0 Other Special Instructions:
As per RP III.
Dose Assessment: TLD and EPD required.
Special Instructions:
Timekeeping required when working in a dose rate >1500 mnR/hr and the worker could receive more than 25 mrem.
IV.
Protective Clothing 0
Coveralls, Booties, Rubber Totes and Rubber Gloves (Minimum requirements for entering CTMIT) 0D Labcoat, Booties, and Rubber Gloves may be used only with RP permission.
a Coveralls, Double Booties or Booties and Rubber ToteslBoots, and Double Rubber Gloves.
E Double coveralls, Double Rubber gloves, Double Booties, Rubber Totes/Boots.'
El Plastic suit, Double Rubber Gloves, Double Booties, Rubber Totes/Boots.'
3 Surgeon's Gloves may be substituted for Rubber Gloves with RP permission.
El Hood and Face Shield required.
0 Other: See Special Instructions
' Safety review may be required for additional coveralls or plastics.
Special Instructions:
Extra outer shoe covers and gloves required for upper cavity, PZR, RCP, and loop areas. Remove outer shoe covers and gloves upon exiting these areas.
Additional protective clothing may be required based on initial surveys.
Work gloves may be substituted for outer rubber gloves.
PBF-403 1 Revision 12 12/10/03 HP 1.10/P6.8 Page 3 of 4
Nuclear Power Business Unit RADIATION WORK PERMIT Revision:
0 6 /~ [~
RatT Number:
04-1 04 V.
Respiratory Protection:
Special Instructions:
Additional requirements as per RP Supervision.
VI.
Engineering Controls: N/A Special Instructions:
I VII.
ALARA Requirements:
LDWA:
Various El See ALARA Review Special Instructions:
Foreign debris found within the refueling cavity, spent fuel pool, S/G Channelhead, or primary systems may be highly radioactive and shall not be handled without RP permis When working in these areas or handling equipment from these areas (such as refueling tools), workers shall monitor at least every two hours.
Contact RP immediately if, during monitoring of protective clothing, the worker discovers >10,000 cpm above bkg using a open window beta instrument.
Contact RP immediately if, during monitoring of skin, personal clothing, or modesty garments any contamination above bkg is discovered.
PBF403 1 Revision 12 1210/03 HP 1.1O0P6.S Page 4 of 4