March 2005 Monthly Operating Report for Limerick Generating Station, Units 1 and 2
ML051050458
Person / Time
Site: Limerick  
Issue date: 04/15/2005
From: Bryan Hanson
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GL-97-002
Download: ML051050458 (3)


Text

T.S. 6.9.1.6 April 15, 2005 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Limerick Generating Station, Units 1 and 2 Facility Operating License Nos. NPF-39 and NPF-85 NRC Docket Nos. 50-352 and 50-353

Subject:

Monthly Operating Report for March 2005 Attached is the monthly operating report for Limerick Units 1 and 2 for the month of March 2005 forwarded pursuant to Technical Specification 6.9.1.6 and the guidance of NRC Generic Letter 97-02. The attached monthly operating report data has also been entered into the INPO Consolidated Database for the month of March 2005 for Units 1 and 2.

If you have any questions or require additional information, please do not hesitate to contact us.

Sincerely, Original signed by Bryan C. Hanson Plant Manager-LGS Exelon Generation Company, LLC Attachments cc:

S. Collins, Administrator, Region I, USNRC S. Hansell, LGS USNRC Senior Resident Inspector

Unit:

Limerick 1 Docket No:

50-352 Date:

4/15//05 Completed by: Greg Lee Telephone:

(610) 718-3707 A.

OPERATING DATA REPORT REPORTING PERIOD-March 2005 Design Electrical Rating (MWe-Net) 1191.00 Maximum Dependable Capacity (MWe-Net) 1134.00 Month Year to Date Cumulative Hours Reactor Critical (Hours) 744.00 2,109.13 149,064.77 Hours Generator On-Line (Hours) 744.00 2,082.42 147,009.00 Unit Reserve Shutdown Hours (Hours) 0.00 0.00 0.00 Net Electrical Energy (MWh) 873,377.00 2,420,626.00 153,785,971.00 B.

UNIT SHUTDOWN No.

Date (yymmdd)

Type Generator Off-line Duration (hrs)

Reason Method Corrective Actions/Comments None during the month of March 2005

SUMMARY

Unit 1 began the month of March 2005 at 100% of rated thermal power (RTP).

There were no power changes during the month of March 2005.

Unit 1 ended the month of March 2005 at 100% RTP.

Type Reason Method F-Forced A-Equipment Failure (Explain) 1-Manual S-Scheduled B-Maintenance or Test 2-Manual Trip/Scram C-Refueling 3-Automatic Trip/Scram D-Regulatory Restriction 4-Continuation E-Operator Training/License Examination 5-Other (Explain)

F-Administrative G-Operational Error (Explain)

H-Other (Explain)

C.

SAFETY/RELIEF VALVE OPERATION Date Valves Actuated No. & Type of Actuation Plant Condition Description of Event None During March 2005

Unit:

Limerick 2 Docket No:

50-353 Date:

4/15/05 Completed by: Greg Lee Telephone:

(610) 718-3707 A. OPERATING DATA REPORT REPORTING PERIOD-March 2005 Design Electrical Rating (MWe-Net) 1191.00 Maximum Dependable Capacity (MWe-Net) 1134.00 Month Year to Date Cumulative Hours Reactor Critical (Hours) 256.25 1,662.32 124,865.55 Hours Generator On-Line (Hours) 176.10 1,582.10 123,003.84 Unit Reserve Shutdown Hours (Hours) 0.00 0.00 0.00 Net Electrical Energy (MWh) 137,948.00 1,692,849.00 132,666,216.00 B. UNIT SHUTDOWN No.

Date (yymmdd)

Type Generator Off-line Duration (hrs)

Reason Method Corrective Actions/Comments 1

050301 S

420.42 C

4 2R08 refueling outage continuing 2

050320 S

147.48 B

1 2F33 turbine bearing repair

SUMMARY

Unit 2 began the month of March 2005 at 0% of rated thermal power (RTP).

On March 17th at 07:24 hours, reactor criticality was achieved.

On March 18th at 05:27 hours, the main generator was synchronized to the grid at 23.1% RTP. At 09:37 hours, the main generator was tripped at 20.4% RTP for voltage and overspeed testing. At 12:26 hours, the main generator was resynchronized to the grid at 23.9% RTP.

On March 20th at 09:50 hours, reactor power was reduced from 60.7% to 19.3% RTP due to high temperature and vibration on the #3 turbine bearing. At 11:30 hours, the main turbine was manually tripped at 19.6% RTP.

On March 21st at 03:16 hours, the reactor was manually scrammed at 21.3% RTP for repairs to the turbine bearing and SRV maintenance.

On March 25th at 03:37 hours, reactor criticality was achieved.

On March 26th at 14:59 hours, the main generator was synchronized to the grid at 19.1% RTP.

On March 28th at 08:20 hours, the reactor was restored to 100% RTP. At 22:02 hours, reactor power was reduced from 97.7% to 60.1% RTP for rod pattern adjustment.

On March 29th at 19:37 hours, reactor power was restored to 99.8% RTP.

Unit 2 ended the month of March 2005 at 100% RTP.

Type Reason Method F-Forced A-Equipment Failure (Explain) 1-Manual S-Scheduled B-Maintenance or Test 2-Manual Trip/Scram C-Refueling 3-Automatic Trip/Scram D-Regulatory Restriction 4-Continuation E-Operator Training/License Examination 5-Other (Explain)

F-Administrative G-Operational Error (Explain)

H-Other (Explain)

C. SAFETY/RELIEF VALVE OPERATION Date Valves Actuated No. & Type of Actuation Plant Condition Description of Event None during March 2005