ML050740291

From kanterella
Jump to navigation Jump to search

Technical Specifications, Modification of TS 5.5.12 for Extension of Type a Leakage Rate Test (Tac No. MC3745, MC3746)
ML050740291
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 03/09/2005
From: Ellen Brown
NRC/NRR/DLPM/LPD2
To: Singer K
Tennessee Valley Authority
Brown E, NRR/DLPM, 415-2315
Shared Package
ML050340627 List:
References
TAC MC3745, TAC MC3746
Download: ML050740291 (4)


Text

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.11 Safety Function Determination Program (SFDP) (continued)

A loss of safety function exists when, assuming no concurrent single failure, a safety function assumed in the accident analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:

a. A required system redundant to system(s) supported by the inoperable support system is also inoperable; or
b. A required system redundant to system(s) in turn supported by the inoperable supported system is also inoperable; or
c. A required system redundant to support system(s) for the supported systems (a) and (b) above is also inoperable.

The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

5.5.12 Primary Containment Leakage Rate Testing Program A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50, Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide 1.163, "Performance-Based Containment Leak-Test Program," dated September 1995, as modified by the following exception:

NEI 94 1995, Section 9.2.3: The first Unit 2 Type A test performed after the November 6,1994, Type A test shall be performed no later than November 6, 2009.

(continued)

BFN-UNIT 2 5.0-20 Amendment No. 254, 293

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.12 Primary Containment Leakage Rate Testing Program (continued)

The peak calculated containment internal pressure for the design basis loss of coolant accident, Pa, is 50.6 psig. The maximum allowable primary containment leakage rate, La, shall be 2% of primary containment air weight per day at Pa.

Leakage Rate acceptance criteria are:

a. The primary containment leakage rate acceptance criteria is s 1.0 La.

During the first unit startup following the testing performed in accordance with this program, the leakage rate acceptance criteria are

  • 0.60 La for the Type B and Type C tests, and
  • 0.75 La for the Type A test; and
b. Air lock testing acceptance criteria are:
1) Overall air lock leakage rate
  • 0.05 La when tested at > Pa.
2) Air lock door seals leakage rate is
  • 0.02 La when the overall air lock is pressurized to 2 2.5 psig for at least 15 minutes.

The provisions of SR 3.0.2 do not apply to the test frequencies specified in the Primary Containment Leakage Rate Testing Program. The provisions of SR 3.0.3 are applicable to the Primary Containment Leakage Rate Testing Program.

BFN-UNIT 2 5.0-21 Amendment No. 253,293 2

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.11 Safety Function Determination Program (SFDP) (continued)

A loss of safety function exists when, assuming no concurrent single failure, a safety function assumed in the accident analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:

a. A required system redundant to system(s) supported by the inoperable

-support system is also inoperable; or

b. A required system redundant to system(s) in turn supported by the inoperable supported system is also inoperable; or
c. A required system redundant to support system(s) for the supported systems (a) and (b) above is'also inoperable.

The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

5.5.12 Primary Containment Leakage Rate Testinq Program A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50, Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide 1.163, "Performance-Based Containment Leak-Test Program," dated September 1995, as modified by the following exception:

  • NEI 94 1995, Section 9.2.3: The first Unit 3 Type A test performed after the October 10, 1998, Type A test shall be performed no later than October 10, 2013.

(continued)

BFN-UNIT 3 5.0-20 Amendment No. 244,.252

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.12 Primary Containment Leakage Rate Testing Program (continued)

The peak calculated containment internal pressure for the design basis loss of coolant accident, Pa, is 50.6 psig. The maximum allowable primary containment leakage rate, La, shall be 2% of primary containment air weight per day at Pa.

Leakage Rate acceptance criteria are:

a. The primary containment leakage rate acceptance criteria is < 1.0 La.

During the first unit startup following the testing performed in accordance with this program, the leakage rate acceptance criteria are < 0.60 La for the Type B and Type C tests, and < 0.75 La for the Type A test; and

b. Air lock testing acceptance criteria are:
1) Overall air lock leakage rate < 0.05 La when tested at 2 Pa.
2) Air lock door seals leakage rate is < 0.02 La when the overall air lock is pressurized to 2 2.5 psig for at least 15 minutes.

The provisions of SR 3.0.2 do not apply to the test frequencies specified in the Primary Containment Leakage Rate Testing Program. The provisions of SR 3.0.3 are applicable to the Primary Containment Leakage Rate Testing Program.

BFN-UNIT 3 5.0-21 Amendment No. 242,252