1r W-I~LF CREEK

'NUCLEAR OPERATING CORPORATION Kevin J. Moles Manager Regulatory Affairs February 15, 2005 RA 05-0019 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001

Subject:

Docket No. 50-482:'January 2005 Monthly Operating Report Gentlemen:

  • Attached tojthis letter is the January 2005,1 Monthly Operating Report for the Wolf Creek'

.Generating Station. This submittal is being 'made in accordance with the requirements of

..Wolf Creek Generating Station -Technical. -Specification 5.6.4, "Monthly 'Operating Reports." Af.'you,-have any questions regarding this' report, please contact me at (620) 364-4126, or Ms. Diane Hooper at (620) 364-4041 Very truly yours Kevin J.

7 KJM/rIg Attachment cc:

J. N. Donohew (NRC), wla D. N. Graves (NRC), w/a B. S. Mallett (NRC), w/a Senior Resident Inspector (NRC), w/a-

.O. Box 411/ Burlirigt66' KS 668391 Phone: (620) 364-8831.

An Equal Opportunity Employer WF/FHCNET

..A.ttachment to RA 05-0019 r

Page 1of 1 OPERATING DATA REPORT Report Number: 240 DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE REPORTING PERIC 50-482..

I Wolf Creek I February 15, 2005.

D. M. Hooper 620 364-4041

,D:

January 2005 1.

2.

Design Electrical Rating Maximum Dependable Capacity (MWe-Net) 3.

4.

5.

6.

This Month Number of Hours the Reactor was Critical 542.07 Number of Hours Generator On-line 531.98 Reserve Shutdown Hours 0.00 Net Electrical Energy Generated (MWHrs) -

618.685.00 Yr-to-Date 542.07 531.98 0.00 618.685.00 Cumulative 146.999.74 145.724.50 339.80 165.732,582.00 UNIT SHUTDOWNS Type F: Forced Method of S:

Duration.

Shutting Cause & Corrective Action No.

Date Scheduled (Hours)

Reason (1)

Down (2)

Comments The reactor was taken off line due to water leakage in the

-main generator. Leakage

.a inspecti6ns were performed 05-001 11232005 and one high-voltage generator 212.02 bushing was identified as leaking along with a leak in the stator cooling water return line.

All leaks identified have been repaired.

SUMMARY

The unit operated in Mode 1, at or near 100% power, from January 1,2005, untl January 22,2005, when the reactor was taken off line due to water leakage in the main generator.

(1)

Reason:

A Equipment Failure (Explain)

B Maintenance or Test C

Refueling D

Regulatory Restriction E

Operator Training & License Examination (2)

Method:

1 Manual 2

Manual TriplScram 3

Automatic Trip/Scram 4

Continuation 5

Other (Explain)

F G

H Administration Operational Error (Explain)

Other (Explain)

Wolf Creek Generating Station Monthly Operating Report January 2005 Page 1 of 1