ES-401 PWR Examination Outline Form ES-401-2 Facilitv:
R E Ginna Printed: 09/22/2004 Date Of Exam:
11/01/2004 I
I RO WA Category Point!
I SRO-Only Points
- 3. Generic Knwledge And Abilities Categories Note:
- 1. Ensure that at least two topics from every WA category are sampled within each tier of the RO outline (Le., the "Tier Totals" in each WA category shall not be less than two). Refer to Section D.1.c for additional guidance regarding the SRO sampling.
- 2. The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by *1 from that specified in the based on NRC revisions. The final RO exam must total 75 points and the SROonly exam 25 points.
- 3. Select topics from many systems and evolutions; avoid selecting more than two WA topics from a given system unless they relate to plant-specific priorities.
table must total
- 4. Systemslevolutions within each group are identified on the associated outline.
- 5.
The shaded areas are not applicable to the category Aier.
6.' The generic (G)
WAS in Tiers 1 and 2 shall be selected from Section 2 of the WA Catalog, but the topics must be relevant to the applicable evolution or system. The SRO WAS must also be
- 7. On the fdlwing pages, enter the WA numbers, a brief description of each topic, the topics' importance ratings (IR) for the applicable license level, and the point totals for each system and category. Enter the group and tier totals for each category in the columns labeled "K" and "A.
Use duplicate pages for RO and SRO-only exams.
- 8. For Tier 3, enter the WA numbers, descriptions, importance ratings, and point totals on Form
- 9.
Refer to ES-401, Attachment 2, for guidance regarding the elimination of inappropriate WA statements.
linked to 10 CFR 55.43 or an SRO-level learning objective.
.I... -.........
I ES-401-3.
1
PWR SRO Examination Outline Facility:
R E Ginna Imp.
Points Printed: 09/22/2004 0
0 0
X X
X X
X X
X 4
3 AA2.04 - How long PZR level can be 1 maintained within limits 3.8 -
3.8 1
2.1.32 - Ability to explain and apply all system limits and precautions.
a000 151000017 RCP Malfunctions I 4 000022 Loss of Rx Coolant Makeup 12 000026 Loss of Component Cooling Water I 1
AA2.04 - The normal values and upper limits for the temperatures of the components cooled by CC W 2.9*
1 8
2.1.32 - Ability to explain and apply all system limits and precautions.
3.8 1
000027 Pressurizer Pressure Control System Malfunction t 3 000055 Station Blackout / 6 000057 Loss of Vital AC Inst. Bus 16 EA2.06 - Faults and lockouts that must be cleared prior to re-energizing buses 4.1 1
2.4.30 - Knowledge of which events related to system opemtionslstatus should be reported to outside agencies.
3.6 1
EA21 - Facility conditions and selection of appropriate procedures during abnormal and emergency operations 4.4 1
WE05 Inadequate Heat Transfer - Loss of Secondary Heat Sink t 4 W A Category Totals:
Group Poi1 : Total:
7 -
1
PWR SRO Examination Outline Printed 09/22/2004 Facility:
R E GiMa ES - 401 Emergency and Abnormal Plant Evolutions - Tier 1 /Group 2 Form ES-401-2 A1 A2 G KATopic Imp.
X AA2.02 - Verification of automatic and 4.4 manual means of restoring integrity AA2.07 - When demineralizer resin needs to be replaced indications for system operating parameters which are entry-level conditions for emergency and abnormal operating procedures.
system limits and precautions.
procedures and operation within the limitations in the facility's license and amendments 2.7*
X 2.4.4 - Ability to recognize abnormal 4.3 X 2.1.32 - Ability to explain and apply all 3.8 EA2.2 - Adherence to appropriate 3.8 Points 1
I 1
1 1
' Y/APE # / Name / Safety Function IKllK2lK3 do0069 Loss of CTMT Integrity / 5 I I I 000076 High Reactor Coolant Activity 19 WACategoryTotals: I 0 I 0 I 0 0 1 3 1 2 1 Group Point Total:
5 1
Facility:
R E Ginna w.c - Ani Y..,
.Y*
I 9ys/Evol# / Name 004 Chemical and Volume Control K1 K2 K3 K4 K5 K6 A1 A2 A3 A4 G KATopic X 2.1.33 - Ability to recognize indications for system operating parameters which are entry-level conditions for technical specifications.
0 13 Engineered Safety Features X
A2.03 - Rapid Actuation depressurization 022 Containment Cooling X
A2.01 - Fan motor over-current 064 Emergency Diesel Generator X 2.1.33 - Ability to recognize indications for system operating parameters which are entry-level conditions for technical specifications.
P W R SRO Examination Outline Plant Systems - Tier 2 / Group 1 Imp. Points 4.0 1
4.7 1
2.7 1
4.0 1
Printed: 09/22/2004 Form ES-401-2 WACategory Totals:
0 0
0 0
0 0
0 2
0 0
2 Group Point Total:
4 1
Facility:
R E Ginna E'S - An1 K5 K6 A1 0
0 0
P W R SRO Examination Outline Plant Systems - Tier 2 / Group 2 KA Topic A2.01 - Dropped fuel element 2.4.4 - Ability to recognize abnormal indications for system operating parameters which are entry-level conditions for emergency and abnormal operating procedures.
Imp.
4.4 4.3 0
A2 X
0 A3 A4 1
0 0
3ys/Evol## I Name I
K1 K2 Printed 09/22/2004 Form ES-401-2
' 4 3 4 Fuel Handling Equipment 086 Fire Protection WA Category Totals:
0 0
Poinb 1
1 -
2 1
~
~ --
Generic Knowledge and Abilities Outline (Tier 3)
2.3.6 Facilitv
R E Ginna Generic Category Knowledge of the requirements for reviewing and 3.1 1
approving release permits.
Conduct of Operations 2.3.9 Equipment Control Knowledge of the process for performing a 3.4 1
containment purge.
Printed: 09/22/2004
._._ Emergency ProceduredPlan Form ES-401-3 2.4.28 Knowledge of procedures relating to emergency 3.3 1
Category Total:
1 response to sabotage.
KA KA ToDic Imp. Points Category Total:
2 2.2.20 2.2.23 Knowledge of the process for managing troubleshooting activities.
Ability to track limiting conditions for operations.
3.8 Cateeorv Total:
2 Radiation Control r I
I I
1 Generic Total:
7 1
ES-401 Record of Rejected WAS Form ES-401-4 Tier 1 Group 3
3 Randomly Selected WA 2.1.22 2.4.33 Reason for Rejection Replaced 2.1.22 Reason: Ability to determine Mode is an RO level KA. Replaced with 2.1.14. Replacement transferred from a second randomly generated outline, same Tier and Group.
Replaced 2.4.33 Reason: This is not an SRO level topic. Replaced with 2.4.28. Replacement transferred from a second randomly generated outline, same Tier and Group.
ES-301 Administrative Topics Outline Form ES-301-1 Administrative Topic TY Pe (see Note)
Code*
Conduct of Operations Dj c Conduct of Operations N y C L-L-
Describe activity to be performed JAOOI.008 Calculate SDM for an Operating Reactor with an Untrippable Rod (2.1.7)
JS341.002 Requirements for Confined Space Entry (2.1.26)
JS343.002 A52.4 Control of Limiting Conditions for Facility: R. E. Ginna Examination Level (circle one): SRO Radiation Control Emergency Plan Date of Examination:ll/1/2004 Operating Test Number:=
JS340.019 Implement EPlP 1-13 Local Radiation Nl c Emergency. (2.3. IO)
JS340.020 Event Classification. (2.4.41)
N, S Equipment Control II Dv c Operation. (2.2.23) 1 I
- Type Codes & Criteria:
(C)ontrol room (D)irect from bank (s 3 for ROs; 5 4 for SROs & RO retakes)
(N)ew or (M)odified from bank ( 2 1)
(P)revious 2 exams (I; 1; randomly selected)
(S)im ulator
ES-301 Control Roomlln-Plant Systems Outline Form ES-301-2 Type Code*
Safety Function Facility: R. E. Ginna Exam Level (circle one): SRO-U Control Room Systems@ (8 for RO; 7 for SRO-I; 2 or 3 for SRO-U)
Date of Examination: 11/1/2004 Operating Test No.: 04-2 System / JPM Title
- Type Codes a.JR076.001 Perform Attachment No Service Water Pumps b.JR062.026 Restore power to one train from the B D/G per ER-ELEC.3 Criteria for RO I SRO-I I SRO-U 11 c.JR026.001 Secure CNMT Spray ll h-In-Plant Systems@ (3 for RO; 3 for SRO-I; 3 or 2 for SRO-U)
A, Nl Sl L I 4
5 I
i.JCOO6.010 Transfer Water from the SFP to the RWST during Loss of Emergency Coolant Recirculation 8
j.JCO62.023 Dilute the BAST following a Loss of All AC 1
- k.
I I
All control room (and in-plant) systems must be different and serve different safety functions; in-plant systems and functions may overlap those tested in the control room.
I (A)lternate path (C)ontrol room (D)irect from bank (E)mergency or abnormal in-plant (L)ow-Power (N)ew or (M)odified from bank including 1(A)
(P)revious 2 exams (R)CA (S)imulator 4-6 14-6 12-3 I; 911; 8 1 s 4 L I I L I I L 1
> 1 1 2 112 1
> Z I 2 2 1 2 1
< 3 I < 3 I < 2 (randomly selected)
L 1 1 2 l l > I
Appendix D Scenario Outline Form ES-D-I Event Malf. No.
Event No.
Type*
1 N
2 PZR02D I
3 EDS04B C
4 cvc12A C
5 STMOSNB M
STM03 Facility: R. E. Ginna Scenario No.: 1 Op-Test No.: 04-2 Event Description Start the Second MFW Pump PT-449 Fails High causing full PRZR Spray (Tech. Specs.)
Bus 16 Fault (Loss of a Safeguards Bus) (Tech. Specs.)
Trip of A Charging Pump. Loss of All Charging Main Steamline Rupture, Both MSlVs stuck open Examiners:
Operators:
- (N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor I'
L Event Malf. No.
1 PZR03B No.
Appendix D Scenario Outline Form ES-D-1 Event Event Type*
Description I
PRZR Level transmitter LT-427 Fails low causing Letdown Isolation (Tech. Spec.)
Facility: R. E. Ginna Scenario No.: Backup Op-Test No.: 04-2 2
3 4
5 6
Examiners:
Operators:
CLG03 RCS I OB TUROSE N
High Turbine Vibration requires Load reduction RCS02B M
Non-Regen Hx Tube Leak causes RCS leakage into the CCW system (Upon restoration of Letdown)
RCS flow transmitter fails low (Tech. Spec.)
C A RHR Pump trips resulting in a loss of Emergency Coolant Recirc.
Initial Conditions:lOO% Power MOL core conditions. B RHR pump 00s due to a Seal Cooler Leak. CNMT Fan Cooler B is 00s due to a Motor Cooler SW leak.
~~
~
~
~~
~
~~
~
- (N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor