Joseph A. Widay Plant Manager 1503 Lake Road Ontario, NewYork 14519-9364 585.771.3000 Constellation Energy R.E. Ginna Nuclear Power Plant, LLC October 18, 2004 Mr. Robert L. Clark Office of Nuclear Regulatory Regulation U.S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D.C. 20555-0001

Subject:

Change in CREATS Modification Control Room HVAC Refrigerant Charge R.E. Ginna Nuclear Power Plant Docket No. 50-244

References:

1. Letter from Robert C. Mecredy (RG&E) to Robert L. Clark (NRC) dated May 21, 2003, License Amendment Request Regarding Revision of Ginna Technical Specification Sections 1.1, 3.3.6, 3.4.16, 3.6.6, 3.7.9, 5.5.10, 5.5.16, and 5.6.7 Resulting From Modification of the Control Room Emergency Air Treatment System and Change in Dose Calculation Methodology to Altemate Source Term.
2. American Society of Heating Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard, ANSI/ASHRAE Standard 15-2001, Safety Standard for Refrigeration Systems.

Dear Mr. Clark:

In Attachment 2 of Reference 1, R.E. Ginna Nuclear Power Plant, LLC (formerly RG&E) stated that "Each new CREATS cooling system circuit will contain s 29.0 pounds of R-22." Subsequent to that submittal, it was determined that each circuit will require a charge of approximately 50 pounds of R-22. This equates to 1.4 pounds per 1000 cubic feet of occupied space, or approximately 15% of the limit shown in Table 1 of Reference 2. Therefore, even with the increased amount of R-22 in the cooling system, the refrigerant charge in the new CREATS cooling system will remain well within the acceptable industry standard. If you have questions regarding the content of this correspondence please contact Mr. Mike Ruby at (585) 771-3572 or Mr. George Wrobel at (585) 771-3535.

Very truly yours, sephA. Widay AC)03

/co'Iqc/

STATE OF NEW YORK

TO WIT:

COUNTY OF WAYNE I, Joseph A. Widay, being duly sworn, state that I am Acting Vice President - R.E. Ginna Nuclear Power Plant, LLC (Ginna LLC), and that I am duly authorized to execute and file this response on behalf of Ginna LLC. To the best of my knowledge and belief, the statements contained in this document are true and correct. To the extent that these statements are not based on my personal knowledge, they are based upon information provided by other Ginna LLC employees and/or consultants. Such information has been reviewed in accordance with company practice and I believe it to be reliable.

Subscribed and sworn before me, a N tary PubliJrjapd fpr the State of New York and County of :LfrL4tn.

,this

/Ž day of J!(

LZ,1 2004.

WITNESS my Hand and Notarial Seal:

AI1O A, 7 Notary Publid SHARON L MILLER N*y PicW0deNewYo0 My Commission Expires:

u M16017755

/R -0 / -0 Date Attachments: None Cc:

Mr. Robert L. Clark (Mail Stop 0-8-C2)

Project Directorate I Division of Licensing Project Management Office of Nuclear Regulatory Regulation U.S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Rockville, MD 20852 Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Inspector

Mr. Peter R. Smith New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 Mr. Paul Eddy NYS Department of Public Service 3 Empire State Plaza, 10' Floor Albany, NY 12223 James M. Petro Jr.

Counsel, Generation - Nuclear Constellation Energy 750 East Pratt Street, 17th Floor Baltimore, MD 21202