EDO Principal Correspondence Control FROM:

DUE: 09/24/04 EDO CONTROL: G20040574 DOC DT: 08/12/04 FINAL REPLY:

Alex Matthiessen Kyle Rabin Riverkeeper Collins/Holian, RI FOR SIGNATURE OF :

Dyer, NRR DESC:

ROUTING:

Seismic Hazard Analysis for the Indian Point Nuclear Power Plant Reyes Virgilio Kane Merschoff Norry Dean Burns/Cyr Collins, NRR DATE: 08/20/04 ASSIGNED TO:

NRR CONTACT:

Dyer SPECIAL INSTRUCTIONS OR REMARKS:

Coordinate response with Region I.

IZ 1Cp:

o I k:~I bDs:

D1I

August 12, 2004 Sam Collins Brian E. Holian Regional Administrator, Region I Deputy Director U.S. Nuclear Regulatory Commission Division of Reactor Projects, Region I 475 Allendale Road U.S. Nuclear Regulatory Commission King of Prussia, PA 19406 475 Allendale Road King of Prussia, PA 19406 Re. Suismic H Analysis fi tho indim t-Nadlear Power Plant

Dear Mr. Collins and Mr. Holian:

We are writing to formally request the Nuclear Regulatory Commission to take immediate action to ensure that a competent and independent authority on seismic research conduct an updated seismic hazard analysis for the Indian Point nuclear power plant, particularly in relation to the high-density spent fuel pools and the proposed dry cask storage facility. Such an analysis should be subjected to peer review and public scrutiny. We arc also requesting that the NRC subject Indian Point, both now and during the license renewal process, to the same stringent criteria applied to companies seeking to build new reactors on existing or new sites.

The NRC's rcquirements of Entergy with respect to seismic monitoring at Indian Point are not apparent. Furthermore, it is not clear at what point the NRC decided to change its requirements regarding seismic monitoring at Indian Point. But it is obvious that the seismic hazard analysis' for Indian Point - which is situated adjacent to the Ramapo fault - clearly needs to be updated.

'Seismic hazard analysis is generally based on a combination of earthquake data, geologic data an active faults, and on tectonic models. In the eastern U.S. there are earthquakes, but only few active faults are known. The Indian Point site is near some of these faults. All earthquake sources over a large area need to be considered since large earthquakes can do damage far away. The analysis is done by an established procedure that accounts for differing opinions and describes the hazard probabilistically: the result is formulated as the probabilities of exceeding a set of specific acceleration values at different frequencies of shaking over a given time. These results can be given for a site or mapped over a region.

From these results engineers can then design to specific required low probabilities of damage or evaluate the probability that an existing structure is damaged.

1 25 Wing & Wing Garrison, NY 10524-0130 Phone: (845) 4244149 Fax: (845) 424-4150 hUpi/www.riverkeeper.org EDO -- G20040574

J.6 In addition, an April 30h letter from Entergy to Riverkeeper contained inaccurate information. The letter, from Kathleen McMullin, Entergy's Communications Manager, made the following declaration: "An earthquake with a peak ground acceleration of 0.15 g is equivalent to a Richter magnitudd of approximately 6.0." The attached statement from Dr. Lynn Sykes of Lamnont-Doherty Earth Observatory explains why this is incorrect and raises concerns about Entergy's lack of understanding on the issue of the seismic hazard threat to Indian Point. Other misinformation is posted to Entergy's website at http://www.safesecurevital.orglarticles/2004/drvcaskfaq/seismichtmI is based on outdated studies.

A great deal more information on earthquakes2 has become available since the hazard analysis that was performed decades ago regarding the risk of damage to Indian Point posed by seismic activity. For example, a sequence of earthquakes that started in August 2003 is being studied by the Lamont-Doherty Earth Observatory near the New Jersey-Pennsylvania border about 75 miles southwest of Indian Point. These earthquakes are particularly pertinent to the potential for earthquakes near Indian Point because they are associated with the same fault system (the Ramapo fault). Furthermore, new research suggests that damaging earthquakes could nucleate at a shallower depth than previously thought. While the probability of a damaging earthquake may be low, damage to various facilities at Indian Point may have dic secondary consequences for the region.

In the 1970s, measurements of acceleration came almost exclusively from earthquakes in the western U.S. and Japan and were assumed to be the same for the rest of the U.S. Measurements are Most earthquakes in southern New York and northern Ncw Jersey occur in two belts each about 20 miles wide that are situated within the older rocks of the region. One belt extends from Putnam and Westchester countries to New York City and thence to central New Jersey. The other belt, which extends southwesterly along the Hudson Highlands from Peekslkill NY to near Reading PA, is bounded on the southeast by border faults of the Newark Basin, including the Ramnapo Fault. The two belts merge near Stony Point and Indian Point as the younger rocks of the Newark Basin pinch out. Thus, estimates of earthquake risk to Indian Point need to include possible future earthquakes along these two belts.

2 25 Wing & Wing Garrison, NY 10524-0130 Phone: (845) 424-4149 Fax (845) 4244150 httpi/www.riverkeeper.org

now available for several earthquakes in eastern North America, which indicate that seismic shaking is greater at high frequencies-those from about 3 to 100 Hz (cycles per second) than it is for earthquake of comparable magnitude in California and Japan. Hence, dry casks, critical piping and spent fuel assemblies, arc likely to be more sensitive to shaking at higher frequencies at sites cast of the Rocky Mountains. This information needs to be re-evaluated for Indian Point since the design spectrum used in the 1 970s is likely to be too low and hence not as safe at high frequencies as previously supposed. A key question is why this has not been done already. New data, for example. are now available for the n007 Ai smhle TFhorlAdirondacksd Yshock-,-w-hiech gf similar magnitude to the 1884 New York City earthquake.

It does not take a long feature like the Ramapo Fault to generate a damaging earthquake.

The 1737 and 1884 shocks of M 5.2 probably had rupture lengths of only about 5 miles. An event of that size has occurred historically along the two belts I described about once every 150 years. If spent fuel is stored at Indian Point for the next 40 years (assuming operating licenses for the reactors are extended an additional 20 years), the chance of an earthquake occurring along either of those two belts is about 23%. The lack of more extensive knowledge of earthquakes and active faults in this area should result in conservative judgments about risks to critical structures like nuclear power facilities and their spent fuel storage systems.

It is now obvious that Entergy has not commissioned an up-to-date assessment of the seismic hazard posed to the plant based on the latest research. This is an extremely timely matter given Entergy's interest in seeking a 20-year license renewal from the Nuclear Regulatory Commission that would extend their license to operate Indian Point 2 and 3 to 2033 and 2035, respectively. The NRC must subject Indian Point, both now and during the license renewal process, to the same stringent criteria applied to companies seeking to build new reactors on existing or new sites.

3 25 Wing & Wing Garrison, NY 10524.0130 Phone: (845) 4244149 Fax: (845) 4244ISO htplp/www'v.rivkepmcr.org

Relicensing Criteria for Seismic Hazard For the sake of argument, if Entergy chose to immediately close Indian Point's existing reactors and seek to replace them with new reactors, the new reactors would clearly have to mect the NRC's new and more stringent seismic criteria (10 CFR Part 100.23 deals with geologic and seismic siting criteria). The same stringent criteria pertaining to new reactors should also apply to existing reactors, like those at Indian Point, that are seeking a 20-year license renewal. However, it is unclear whether such stringent criteria are being applied to Indian Point. Recently, the owners of the Clinton, Grand Gulf, and North Anna nuclear plants experienced unexpected difficulty in meeting the new seismic criteria of early site permitting applications (i.e., for a permit from the NRC to build a new reactor on an existing or new site). As a result, these plant operators were forced to delay their application submission for several months.

Funding for Seismic Monitoring Stations that have been Closed Finally, over the years, a few seismic monitoring stations near Indian Point have been closed due to funding cutbacks, thereby resulting in a lack of vital data needed to assess activity of local faults and potential for negatively impacting Indian Point, particularly the spent fuel pools and reactor buildings. We request that the NRC help to ensure that a new source of funding is developed to reopen these monitoring stations. Needless to say, the cost burden associated with more extensive research into the plant's vulnerability to an earthquake should not be placed on the public. Thc public is already subsidizing Entergy's operation of Indian Point in so many different ways.

4 25Wing& Wing Garrison,NY 10524-0130 Phone: (845) 424-4149 Fax: (845) 424.4150 http:llwww.rivekeper.org

We are providing you with the contact information for Dr. Klaus Jacob and Dr. Lynn Sykes at Lamont-Doherty Earth Observatory of Columbia University.

Dr. Klaus Jacob Senior Research Scientist Lamont-Doherty Earth Observatory Palisades NY 10964 Tel: 845-365-8440; Fax' 845-365-8150 jacob(i),deo.columbia.edu Dr. Lynn Sykes Professor of Bari Atd EnvironmexAulasxtal Sciensces Lamont-Doherty Earth Observatory Palisades NY 10964 Tel: 845-359-7428; Fax: 845-365-8150

.ykes()ldeo.columbia.edu Dr. Jacob and Dr. Sykes can provide you with additional information. In addition, attached to this letter is a copy of the statement that Dr. Sykes made at the July l5'h public meeting that the NRC held in Peekskill, NY in relation to Entergy's proposed dry cask storage system for Indian Point and the company's lack of understanding on.

We arc interested in meeting with you and officials from Lamont-Doherty to discuss this matter further. Thank you for considering our request and we look forward to hearing back from you soon given the immediacy of this issue.

Sincerely, Alex Matthiessen Hudson Riverkeeper Senior Policy Analyst 5

25 Wing & WVing Garrison, NY 10524-0130 Phone: (845) 424A4149 Fax: (845) 424.4150 http:mlww.rivcrkecper.org

Cc:

The Hon. Charles Schumer, U.S. Senate The Hon. Hillary Rodham Clinton, U.S. Senate The Hon. Eliot L, Engel, U.S. House of Representatives The Hon. Nita M. Lowey, U.S. House of Representatives The Hon. Sue Kelly, U.S. House of Representatives The Hon. Maurice Hinchey, U.S. House of Representatives The Hon. George E. Pataki, Governor of New York State The Hon. Eliot Spitzer, Attorney General of New York State The Hon. Carl Marcellino, NY State Senate, Chair of Environmental Conservation Committee The Hon. Thomas Morahan, NY State Senate The Hon. Thomas DiNapoli, NY State Assembly, Chair of Environmental Conservation Committee The Hon. Richard Brodsky, NY State Assembly, Chair of Corporations, Authorities, and Commissions Committee The Hon. Edward Diana, Orange County Executive The Hon. Robert Bondi, Putnam County Executive The Hon. C. Scott Vanderhoef, Rockland County Executive The Hon. Andrew Spano, Westchester County Executive The Hon. A. Alan Seidman, Orange County Chairman of the Board of Legislators The Hon. Robert McGuigan, Putnam County Chairman of the Board of Legislators TheHon. Salvatore Corallo, Rockland County Chairman of the Board of Legislators The Hon. Bill Ryan, Westchester County Chairman of the Board of Legislators Snr. Project Manager Stephen O'Connor, Spent Fuel Project Office, U.S. Nuclear Regulatory Commission, Reg. I Commissioner Erin M. Crotty, NYS Department of Environmental Conservation 6

25 Wing & Wing Garrison, NY 10524-0130 Phone: (845) 424-4149 Fax: (845) 4244150 httpi/www.riverkccpcr.org

ATTACHMENT EARTHQUAKE RISKS TO SPENT FUEL AT INDIAN POINT A STATEMENT BY Lynn R. Sykes Higgins Professor of Earth and Environmental Scicnces Lamont-Doherty Earth Observatory of Columbia University Palisades NY 10964 MEETING OF U. S. NUCLEAR RE, GULATORY COMMISSION ON INTE RIM STORAGE OF SPENT NUCLEAR FUEL AT INDIAN POINT July 15,2004 cmail svkes(a1deo.co1umbia.cdu I am Lynn Sykes, a professor of Earth and Environmental Sciences at Columbia University. My specific field is earthquake studies. I have worked on earthquakes in New York and New Jersey for more than 35 years. I was an expert witness in the extensive hearings that were held by NRC on the earthquake safety of the Indian Point reactors in 1975 and 1976. I live in nearby Rockland County.

I will address briefly what has been learned since 1976 about earthquake risks and how those findings relate to proposals for spent fuel storage at Indian Point. I find that knowledge about earthquake risks does not seem to have been reviewed thoroughly since 1976.

Older kuowledgc is now outdated. Several of the risks associated with earthquakes are similar to those of terrorism.

7 25 Wing& Wing Garrison, NY 10524-0130 Phone (845) 424.4149 Fax: (845)424-4150 httpd/wmwwriverkeeper.org

Historical Earthquakes: Their Relationship to Indian Point Most earthquakes in southern New York and northern New Jersey occur in two belts each about 20 miles wide that are situated within the older rocks of the region. One belt extends from Putnam and Westchester countries to New York City and thence to central New Jersey.

It was the site of one of the two largest earthquakes in the region, that of 1884 of magnitude, M, 5.2, and of the widely felt Ardsley (Westchester) shock of 1985. An event in 1737 of M

.5.2, whiieh is not as well located as the t884 shock, may have eccurrcd in that belt. The other belt, which extends southwesterly along the Hudson Highlands from Peckskill NY to near Reading PA, is bounded on the southeast by border faults of the Newark Basin, including the Ramapo Fault. The second belt includes the Wappinger Falls shock of 1974, M 3.3; the Annsville earthquake near Indian Point, 1980, M 2.9, the Milford NJ event, 2003, M 3.5 and a poorly studied and located shock in 1783 of M 4.9, the third largest in the region.

The two belts merge near Stony Point and Indian Point as the younger rocks of the Newark Basin pinch out. Thus, estimates of earthquake risk to Indian Point need to include possible future earthquakes along the two belts. Known earthquakes are rare beneath the Newark Basin between the two belts and to the west and north in central parts of Pennsylvania and New York State.

Earthquake Desien for Facilities at Indian Point Kyle Rabin of Riverkeeper submitted several written questions to Entergy officials following a briefing on dry casks here on April 27 (which I also attended). A key answer to him in a letter of April 30 from Kathleen McMullin, Manager, Communications, at Indian Point, is wrong. She is correct in stating that the seismic design basis earthquake established in the late 1960s and early 1970s was anchored at a peak ground acceleration, PGA, of 0.15 g 8

25 Wing & Wing Garrison, NY 10524-0130 Phone: (845) 424-4149 Fax: (845) 424A4150 htIp/www.nvcrkeepmr.org

horizontal, where g is the gravitational acceleration at the earth's surface. Her statement "An earthquake with a peak ground acceleration of 0.15 g is equivalent to a Richter.magnitude of approximately 6.0." is quite wrong. In 1975 that value was inferred to be that associated with

  • the M 5.2 shock of 1884. Shallow earthquakes of M 6 often produce much larger accelerations and shaking. During the smaller M 5.0 Leroy OH earthquake of 1986, 0.17g was recorded at the Perry nuclear power plant about 12 miles away (L. Seeber, written communication, June 2001).

In the 1 970s measurements of acceleration came almost exclusively from earthquakes in the western US and Japan and were assumed to be the same for the rest of the US. Measurements are now available for several earthquakes in eastern North America, which indicate that seismic shaking is greater at high frequencies-those from about 3 to 100 Hz (cycles per second) than it is for earthquake of comparable magnitude in California and Japan. Hence, dry casks, critical piping and spent fuel assemblies, are likely to be more sensitive to shaking at higher frequencies at sites east of the Rocky Mountains. This information needs to be reevaluated for Indian Point since the design spectrum used in the 1970s is likely to be too low and hence not as safe at high frequencies as previously supposed. A key question is why has this not been done already? New data, for example are now available for the 2002 Au Sable Forks, Adirondacks NY shock, which was of similar magnitude to the 1884 New York City earthquake.

A colleague and I were surprised to find out at the presentations on April 27 that the dry casts proposed for Indian Point would not be bolted to their foundation. Ms.

McMullin's letter of April 30 states, "Indeed, analyses of similar casks, in areas of 9

25Wing&Wing Garrison,NY 10524-0130 Phonc (845) 4244149 Fax: (845) 424-4150 http:Ilwww.nverkeeper.org

higher seismic risk than Indian Point have shown that in a nearby earthquake, they will not tip over or release radioactive contents." On April 27 an Entergy briefer stated that dry casks are to be bolted to their foundation at the Diablo Canyon reactors in California. While Diablo Canyon is located in an area of higher seismic hazard, shaking at high frequencies may not be as great a problem as at Indian Point. Also, at no point have I read or heard from officials at Entergy or NRC that extra precautions should be taken for Indiin Point since it is located clse to manmrze, people than Diablo Canyon. Bolting dry casts to their foundation is a small matter, would cost little and would yield increased safety.

What Causes our Earthquakes?

We now have a better understanding of the stresses or pressures in the earth that generate earthquakes along the two belts I described. It involves high horizontal compressive forces oriented in an ENE direction much like those found in a broad area of the eastern and central US and in adjacent parts of Canada.

Knowledge of which faults in our region are seismically active is very incomplete.

Activity in the second belt I described broadly parallels the Ramapo Fault and.many small earthquakes have occurred on or close to it. Opinions differ about the orientation of faults that were active in those events--do they splay off from the Ramapo Fault or do some involve motion on the master fault itself (see http:/Iwww.ldeo.columbia.edulnews/2004/04_30_04.htm).

The ENE direction of maximum compressive stress in our region is such that either faults of either orientation could rupture in significant earthquakes.

It does not take a long feature like the Ramapo Fault to generate a damaging earthquake.

The 1737 and 1884 shocks of M 5.2 probably had rupture lengths of only about 5 miles. An 10 25 Wing&Wing Garrison, NY 10524.0130 Phone: (845) 424A 149 Fax: (845) 424-4150 http:/hvww.rivakecper.org

event of that size has occurred historically along the two belts I described about once every 150 years. If spent fuel is stored at Indian Point for the next 40 years (assuming operating licenses for the reactors are extended an additional 20 years), the chance of an earthquake occurring along either of those two belts is about 40/150 = 27%. Our relatively poor knowledge of earthquakes and active faults in this area should result In conservative judgments about risks to critical structures like nuclear power facilities.

Ea rthquake Monitoringm In the 1970s and early 1980s NRC supported a number of university and state efforts to monitor and study earthquakes in regions east of the Rocky Mountains, the sites of most of the power reactors in the US. When license applications for new reactors ceased 25 years ago, NRC halted that support. The requirements set.by NRC for earthquake monitoring near Indian Point appear to have been dropped several decades ago. The letter from Ms. McMullin indicating that "we continuously monitor seismic activity at Indian Point... the monitors have yet to go off ' indicates that an instrument sensitive to only very strong shaking is being operated. Several factors argue for greater monitoring and study:

1. 19 reactor licenses in the US have been extended for an additional 20 years; more applications are likely, including those for Indian Point 2 and 3.
2. Earthquake risks to spent fuel pools were not considered in the 1975-1976 Indian Point hearings. It was assumed that spent fuel would be shipped offsitc either for reprocessing or disposal.
3. NRC has permitted operators to increase the density of used nuclear fuel assemblies in spent fuel pools by about a factor of 4, leading to greater risks from earthquake shaking (and terrorism).

11 25Wing&Wing GarrisonNY 10524-0130 Phone: (845) 424-4149 Fax: (845) 4244150 http://www.riverkcpcr.org

4. With delays in the opening of the Yucca Mountain facility for high-level radioactive waste, spent fuel assemblies are likely to remain on site at Indian Point either in pools or in dry casks for at least another 15 years and longer if licenses are extended for an additional 20 years beyond 2013 and 2015.
5. Existing reactors are aging.
6. New reactors and sites are again being considered.

Thank you. See my article "Indian Point: Critical Decisions Ahead" which is available on the web site for Riverkeeper.

12 25Wing&Wing Garrison,NY 10524-0130 Phonc: (845) 4244149 Fax (845) 424-4150 httpil/www.riverkeeper.org

Ca' thy. aege~rS, 08-12-04 Riverkeeper Letter to the NRC regrding Seismic Hazard Threatto Indian Point Page 1 From:

To:

Date:

Subject:

Point Kyle Rabin <krabin~riverkeeper.org>

<sjc~nrc.gov>, <beh~nrc.gov>

8112104 12:59PM 08-12-04 Riverk~eper Letter to the NRC regarding beigmic Hazard Threatto Indian Mr. Collins and Mr. Holian:

Good afternoon.

I have attached a copy of a letter Riverkeeper mailed out today to the NRC on the matter of the seismic hazard threat to Indian Point.

Before going into more detail on the seismic hazard threat issue, the letter formally requests that:

1) the Nuclear Regulatory Commission take immediate action to ensure that a competent and independent authority on seismic research conduct an updated seismic hazard analysis for the Indian Point nuclear power plant, particularly in relation to the high-density spent furl pools and the proposed dry cask storage facility. Such an analysis should be subjected to peer review and public scrutiny.
2) the NRC subject Indian Point, both now and during the license renewal process, to the same stringent criteria applied to companies seeking to build new reactors on existing or new sites.

Attached to the letter is a statement submitted by Dr. Lynn Sykes from Lamont-Doherty Earth Observatory at the July 15, 2004 NRC meeting on the dry cask storage proposal for Indian Point.

Thank you for taking the time to consider this matter. We look forward to hearing back from you.

Kyle Rabin Senior Policy Analyst

& Campaign Director Riverkeeper, Inc.