June 30, 2004 MEMORANDUM TO: James W. Clifford, Chief, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation FROM:

Daniel S. Collins, Senior Project Manager, Section 2 /RA/

Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation

SUBJECT:

HOPE CREEK GENERATING STATION, FACSIMILE TRANSMISSION, DRAFT REQUEST FOR ADDITIONAL INFORMATION (RAI) TO BE DISCUSSED IN AN UPCOMING CONFERENCE CALL (TAC NO. MC2534)

The attached draft RAI was transmitted by facsimile on June 29, 2004, to Mr. Paul Duke, PSEG Nuclear LLC (licensee). This draft RAI was transmitted to facilitate the technical review being conducted by Office of Nuclear Reactor Regulation (NRR) and to support a conference call with the licensee to discuss the RAI. The RAI was related to the licensees submittal dated March 31, 2004, concerning the reactor pressure vessel temperature-pressure limits. Review of the RAI would allow the licensee to determine and agree upon a schedule to respond to the RAI. This memorandum and the attachment do not convey or represent an NRR staff position regarding the licensees request.

Docket No. 50-354

Attachment:

Draft RAI

MEMORANDUM TO: James W. Clifford, Chief, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation FROM:

Daniel S. Collins, Senior Project Manager, Section 2 /RA/

Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation

SUBJECT:

HOPE CREEK GENERATING STATION, FACSIMILE TRANSMISSION, DRAFT REQUEST FOR ADDITIONAL INFORMATION (RAI) TO BE DISCUSSED IN AN UPCOMING CONFERENCE CALL (TAC NO. MC2534)

The attached draft RAI was transmitted by facsimile on June 29, 2004, to Mr. Paul Duke, PSEG Nuclear LLC (licensee). This draft RAI was transmitted to facilitate the technical review being conducted by Office of Nuclear Reactor Regulation (NRR) and to support a conference call with the licensee to discuss the RAI. The RAI was related to the licensees submittal dated March 31, 2004, concerning the reactor pressure vessel temperature-pressure limits. Review of the RAI would allow the licensee to determine and agree upon a schedule to respond to the RAI. This memorandum and the attachment do not convey or represent an NRR staff position regarding the licensees request.

Docket No. 50-354

Attachment:

Draft RAI DISTRIBUTION PUBLIC JClifford DCollins MKhanna PDI-2 Reading Document Name: C:\\ORPCheckout\\FileNET\\ML041820224.wpd Accession Number:

OFFICE PDI-1 PDI-2/PM EMCB-A EMCB-A/SC NAME JHardy DCollins MKhanna MMitchell DATE 06/29/04 06/30/04 06/29/04 06/30/24 OFFICIAL RECORD COPY

DRAFT-REQUEST FOR ADDITIONAL INFORMATION REQUEST FOR CHANGES TO TECHNICAL SPECIFICATIONS - REVISION OF THE REACTOR PRESSURE VESSEL PRESSURE-TEMPERATURE LIMITS HOPE CREEK GENERATING STATION By letter dated March 31, 2004, PSEG Nuclear (the licensee) submitted a proposed amendment to the Technical Specifications for Hope Creek Generating Station. The proposed amendment would revise the Technical Specifications based on a re-analysis of the reactor pressure vessel temperature-pressure limits.

The Nuclear Regulatory Commission (NRC) staff has reviewed the information the licensee provided that supports the proposed Technical Specification changes. In order for the staff to complete its evaluation, the following additional information is requested:

1.

Clarify whether the cooldown curves being are used for both the heatup and cooldown assessments for the P-T limits. If the cooldown curves are not being used for the heatups, then provide the 3/4T assessment.