Relief Request, ASME Section XI, Subsection Iwf TAC MC0869
ML041460381
Person / Time
Site: Surry 
(DPR-037)
Issue date: 05/18/2004
From: Stephanie Coffin
NRC/NRR/DLPM/LPD2
To: Christian D
Virginia Electric & Power Co (VEPCO)
Monarques, S R, NRR/DLPM, 415-1544
References
TAC MC0869
Download: ML041460381 (7)


Text

May 18, 2004 Mr. David A. Christian Senior Vice President - Chief Nuclear Officer Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Blvd.

Glen Allen, Virginia 23060-6711

SUBJECT:

SURRY POWER STATION, UNIT 2 RE: ASME SECTION XI SUBSECTION IWF, INSERVICE INSPECTION (ISI) PROGRAM RELIEF REQUEST CS-001 (TAC NO.

MC0869)

Dear Mr. Christian:

This letter authorizes the alternative you requested in Relief Request CS-001 for Surry Power Station, Unit 2. By letter dated August 25, 2003, Virginia Electric and Power Company requested an alternative to the requirements of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code,Section XI, with regard to the functional testing of snubbers.

Our evaluation and conclusion are contained in the enclosed Safety Evaluation. The NRC staff has concluded that your proposed alternative provides an acceptable level of quality and safety.

The alternative you requested is authorized pursuant to 10 CFR 50.55a(a)(3)(i) for the fourth 10-year ISI interval.

Sincerely,

/RA/

Stephanie Coffin, Chief, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-281

Enclosure:

As stated cc w/encl: See next page

May 18, 2004 Mr. David A. Christian Senior Vice President - Chief Nuclear Officer Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Blvd.

Glen Allen, Virginia 23060-6711

SUBJECT:

SURRY POWER STATION, UNIT 2 RE: ASME SECTION XI SUBSECTION IWF, INSERVICE INSPECTION (ISI) PROGRAM RELIEF REQUEST CS-001 (TAC NO.

MC0869)

Dear Mr. Christian:

This letter authorizes the alternative you requested in Relief Request CS-001 for Surry Power Station, Unit 2. By letter dated August 25, 2003, Virginia Electric and Power Company requested an alternative to the requirements of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code,Section XI, with regard to the functional testing of snubbers.

Our evaluation and conclusion are contained in the enclosed Safety Evaluation. The NRC staff has concluded that your proposed alternative provides an acceptable level of quality and safety.

The alternative you requested is authorized pursuant to 10 CFR 50.55a(a)(3)(i) for the fourth 10-year ISI interval.

Sincerely,

/RA/

Stephanie Coffin, Chief, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-281

Enclosure:

As stated cc w/encl: See next page Distribution ALee RidsNrrPMSMonarque (Hard copy)

PUBLIC RidsNrrDlpmLpdii RidsNrrLAEDunnington (Hard copy)

PDII-1 R/F RidsOGCRp RidsAcrsAcnwMailCenter G. Hill (2)

RidsRgn2MailCenter KManoly J.S. Walker Adams Accession No.: ML041460381

  • See Safety Evaluation **See previous concurrence OFFICE PDII-1/PM PDII-2/LA EMEB/SC OGC PDII-1/SC NAME SMonarque EDunnington KManoly*

GMLongo**

SCoffin DATE 5/18/04 5/18/04 01/28/04 5/17/2004 5/18/04 OFFICIAL RECORD COPY

Enclosure SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION REQUEST FOR RELIEF CS-001 FOURTH 10-YEAR INSERVICE INSPECTION INTERVAL SURRY POWER STATION, UNIT 2 VIRGINIA ELECTRIC AND POWER COMPANY DOCKET NO. 50-281

1.0 INTRODUCTION

By letter dated August 25, 2003, Virginia Electric and Power Company (the licensee) submitted relief request CS-001 for the fourth 10-year inservice inspection (ISI) interval at Surry Power Station, Unit 2 (Surry, Unit 2). The licensee requested approval to use an alternative to the ISI requirements of Article IWF-5000 of Section XI of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel (B&PV) Code for preservice and inservice examinations and testing of Class 1, 2, and 3 snubbers. The licensees proposed alternative consisted of a combination of the existing Surry, Unit 2, Technical Specification (TS) 4.17, Shock Suppressors (Snubbers), specific paragraphs from ASME OMa Code-1996, Subsection ISTD, Preservice and Inservice Examination and Testing of Dynamic Restraints (Snubbers) in Light-Water Reactor Nuclear Power Plants, and other applicable requirements of Section XI of the ASME Code. This relief would apply for the fourth 10-year interval at Surry, Unit 2, which began on May 10, 2004.

2.0 REGULATORY EVALUATION

The ISIs of the ASME Code Class 1, 2, and 3 components are to be performed in accordance with Section XI, "Rules for Inservice Inspection of Nuclear Power Plant Components," of the ASME Code and applicable addenda as required by Title 10 of the Code of Federal Regulations (10 CFR) Section 50.55a(g), except where specific written relief has been granted by the Commission pursuant to 10 CFR 50.55a(g)(6)(i). Paragraph 50.55a(a)(3) of 10 CFR Part 50 states, in part, that alternatives to the requirements of paragraph (g) may be used, when authorized by the Nuclear Regulatory Commission (NRC), if the licensee demonstrates that:

(i) the proposed alternatives would provide an acceptable level of quality and safety, or (ii) compliance with the specified requirements would result in hardship or unusual difficulty without a compensating increase in the level of quality and safety.

Pursuant to 10 CFR 50.55a(g)(4), ASME Code Class 1, 2, and 3 components (including supports) shall meet the requirements, except the design and access provisions and the preservice examination requirements, set forth in the ASME Code,Section XI, to the extent practical within the limitations of design, geometry, and materials of construction of the components. The regulation requires that inservice examination of components and system pressure tests conducted during the first 10-year interval and subsequent intervals comply with the requirements in the latest edition and addenda of Section XI of the ASME Code incorporated by reference in 10 CFR 50.55a(b) 12 months prior to the start of the 120-month interval, subject to the limitations and modifications listed therein.

Pursuant to 10 CFR 50.55a(g)(5), if the licensee determines that conformance with an examination requirement of Section XI of the ASME Code is not practical for its facility, information will be submitted to the Commission in support of that determination and a request must be made for relief from the ASME Code requirement. After evaluation of the determination, pursuant to 10 CFR 50.55a(g)(6)(i), the Commission may grant relief and/or may impose alternative requirements that are determined to be authorized by law, will not endanger life, property, or the common defense and security, and are otherwise in the public interest, giving due consideration to the burden upon the licensee that could result if the requirements were imposed.

The applicable edition of Section XI of the ASME Code, as proposed by the licensee for the Surry, Unit 2, fourth 10-year ISI interval, is the 1998 Edition with addenda up to and including the 2000 Addenda.

3.0 TECHNICAL EVALUATION

CODE REQUIREMENTS The ASME B&PV Code,Section XI, 1998 Edition with addenda up to and including the 2000 Addenda, paragraphs IWF-5200 (a) and (b) and IWF-5300 (a) and (b), reference the use of ASME/ANSI OM-1987, Part 4, Examination and Performance Testing of Nuclear Power Plant Dynamic Restraints (Snubbers), for the requirements of the preservice and inservice examining and functional testing of Class 1, 2, and 3 snubbers.

PROPOSED ALTERNATIVE TO CODE REQUIREMENTS By letter dated August 25, 2003, the licensee proposed as an alternative to the ASME Code,Section XI requirements, a snubber surveillance program comprised of the following elements:

A.

The continued implementation of the surveillance requirements of TS 4.17, Shock Suppressors (Snubbers), without change; B.

The implementation of the other applicable requirements of the ASME Code,Section XI, 1998 Edition with addenda up to and including the 2000 Addenda, unless specific approval has been obtained to do otherwise from the NRC staff pursuant to the requirements of 10 CFR 50.55a and the TS for Surry, Unit 2. This will include using the VT-3 visual examination method in IWA-2213 for preservice and inservice examinations; C.

The preservice examination and testing requirements of paragraph ISTD 4, Preservice Examination, excluding paragraph 4.3, and ISTD paragraph 5, Preservice Operability Testing; and

D.

As an alternative to Subsection ISTD paragraph 4.3, for systems that operate at a temperature greater than 200 degrees F, an additional preservice examination on the affected snubbers during or following the subsequent system heatup and cooldown cycle unless determined unnecessary by evaluation. This examination may be performed during operation of the plant or at the next refueling outage. This is consistent with the requirements of IWF-2200(b). No other requirements of Subsection ISTD will be implemented as part of this alternative.

BASIS FOR PROPOSED ALTERNATIVE The Surry, Unit 2, fourth ISI interval began on May 10, 2004. The incorporation of the ASME Code, 1998 Edition with addenda up to and including the 2000 Addenda, into 10 CFR 50.55a occurred on October 28, 2002. The NRC staff finds the licensees proposed implementation of the ISI program as set forth in the above addenda to be acceptable on the basis of 10 CFR 50.55a(g)(4)(iv).

In its August 25, 2003, submittal, the licensee proposed, as an alternative to the requirements of ASME/ANSI OM-1987, Part 4, to use the existing TS 4.17 for Surry, Unit 2, specific paragraphs from ASME OMa Code-1996, Subsection ISTD, and other applicable requirements of Section XI of the ASME Code for the functional testing of Class 1, 2, and 3 snubbers. The licensee stated that differences exist between the ASME Code (and hence, ASME/ANSI OM-1987, Part 4) requirements and Surry, Unit 2, TS 4.17. Specifically, ASME/ANSI OM-1987, Part 4 contains requirements that were removed from the TS upon the recommendation of Generic Letter (GL) 90-09, Alternative Requirements for Snubber Visual Inspection Intervals and Corrective Actions, dated December 11, 1990. However, ASME Code,Section XI continued to require the restrictive inspection schedule of ASME/ANSI OM-1987, Part 4 for inservice examination of snubbers. A later revision of OM-Part 4, Subsection ISTD of ASME OMa-1996 changed the inspection scheduling requirements to essentially agree with the recommendations of GL 90-09. The rulemaking of September 22, 1999, recognized this fact and included in the rule a provision to allow the use of Subsection ISTD provided the licensee revises the applicable TS.

It is noted that the integration of ASME Code,Section XI and Subsection ISTD into an effective coherent examination and testing program along with the required change to the TS would result in a significant amount of administrative activity without a compensating increase in safety. On this basis, the licensee proposed an alternative approach that would avoid this unnecessary administrative impact and still provide a means to accomplish the examination and testing required by ASME Code,Section XI.

The licensee stated that the current examination and testing requirements of TS 4.17 and the additional visual examination requirements of ASME Code,Section XI have formed the basis of the Surry, Unit 2, snubber inservice examination and testing program for the past ISI interval.

The use of this program was previously approved by the NRC staff and is essentially the same as the program for snubber examination and testing described in Subsection ISTD. Therefore, the licensee believes that the combination of TS 4.17 and ASME Code,Section XI, excluding paragraphs IWF-5200(a) and (b) and IWF-5300(a) and (b), is an alternative that continues to provide an acceptable level of quality and safety for inservice examination and testing of snubbers.

However, to satisfy the preservice examination and testing requirements intended by ASME Code,Section XI, additional examination and testing activity is required beyond the above proposal for inservice activities. As such, the licensee proposes to include the requirements contained in ISTD paragraphs 4 (excluding ISTD paragraph 4.3) and 5, into the current snubber surveillance program in order to provide an alternative that has an acceptable level of safety and quality for the preservice examination and testing requirements. The licensee stated that the inclusion of these requirements into the snubber surveillance program achieves the preservice inspection requirements of ASME Code,Section XI. Since ASME OMa-1996, Subsection ISTD, has been accepted by the NRC staff for the snubber preservice activities, the inclusion of ISTD paragraphs 4 and 5 into the current program is acceptable to the NRC staff.

The licensee stated that ISTD paragraph 4.3 is not proposed for incorporation into the alternative preservice examination program because it addresses requirements best suited for the initial heatup and cooldown of the plant. If the NRC staff were to impose these requirements on Surry, Unit 2, which is constructed with a sub-atmospheric containment, then it would be a hardship for the licensee. As an alternative to the requirements of ISTD paragraph 4.3, the licensee will follow the guidance of paragraph IWF-2220(b) for systems that operate at a temperature greater than 200 degrees F. Paragraph IWF-2220(b) requires the owner to perform an additional preservice examination on the affected component supports during or following the subsequent system heatup and cooldown cycle unless determined unnecessary by evaluation. On the basis that the above ASME Code,Section XI requirements have been accepted by regulation as providing an acceptable level of quality and safety, the NRC staff finds these requirements acceptable as an alternative preservice examination for the supports.

The NRC staff has reviewed the information provided in the licensees submittal of August 25, 2003, and finds that the above alternative program provides an acceptable level of quality and safety without the burden of administrative changes that add little or no value to quality or safety, and without the hardship of performing snubber assessments under subatmospheric conditions.

4.0 CONCLUSION

Based on the information provided by the licensee, the NRC staff concludes that the licensee has presented an adequate justification for an alternative to the requirements of ASME Code,Section XI, 1998 Edition with addenda up to and including the 2000 Addenda, paragraphs IWF-5200 (a) and (b) and IWF-5300 (a) and (b), with regard to visual examination and functional testing of the Surry, Unit 2, Class 1, 2, and 3 snubbers. The NRC staff concludes that the proposed alternative provides an acceptable level of quality and safety for supports and thus ensures structural integrity of the related systems. Therefore, pursuant to 10 CFR 50.55a(a)(3)(i), the licensee's proposed alternative relating to the fourth 10-year interval of the Surry, Unit 2, ISI program is authorized.

Principal Contributor: J. S. Walker Date: May 18, 2004

Mr. David A. Christian Virginia Electric and Power Company cc:

Ms. Lillian M. Cuoco, Esq.

Senior Counsel Dominion Resources Services, Inc.

Building 475, 5th Floor Rope Ferry Road Rt. 156 Waterford, Connecticut 06385 Mr. Richard H. Blount, II Site Vice President Surry Power Station Virginia Electric and Power Company 5570 Hog Island Road Surry, Virginia 23883-0315 Senior Resident Inspector Surry Power Station U. S. Nuclear Regulatory Commission 5850 Hog Island Road Surry, Virginia 23883 Chairman Board of Supervisors of Surry County Surry County Courthouse Surry, Virginia 23683 Dr. W. T. Lough Virginia State Corporation Commission Division of Energy Regulation P. O. Box 1197 Richmond, Virginia 23218 Robert B. Strobe, M.D., M.P.H.

State Health Commissioner Office of the Commissioner Virginia Department of Health P.O. Box 2448 Richmond, Virginia 23218 Surry Power Station Units 1 and 2 Office of the Attorney General Commonwealth of Virginia 900 East Main Street Richmond, Virginia 23219 Mr. Chris L. Funderburk, Director Nuclear Licensing & Operations Support Dominion Resources Services, Inc.

Innsbrook Technical Center 5000 Dominion Blvd.

Glen Allen, Virginia 23060-6711 Mr. Jack M. Davis Site Vice President North Anna Power Station Virginia Electric and Power Company P. O. Box 402 Mineral, Virginia 23117-0402 Mr. William R. Matthews Vice President - Nuclear Operations Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, Virginia 23060-6711