UNITED STATES NUCLEAR REGULATORY COMMISSION REGION IV 611 RYAN PLAZA DRIVE, SUITE 400 444 6' jARLINGTON, TEXAS 76011-4005 May 17, 2004 Randall K. Edington, Vice President-Nuclear and CNO Nebraska Public Power District P.O. Box 98 Brownville, NE 68321
SUBJECT:
SUMMARY
OF CONFIRMATORY ACTION LETTER 5th QUARTERLY INSPECTION EXIT MEETING WITH NEBRASKA PUBLIC POWER DISTRICT REGARDING COOPER NUCLEAR STATION
Dear Mr. Edington:
This refers to the meeting conducted at the Brownville Concert Hall in Brownville, Nebraska, on May 12, 2004. The purpose of this meeting was to present the results of the NRC's Confirmatory Action Letter 5th quarterly inspection conducted at the Cooper Nuclear Station of the Nebraska Public Power District. The attendance list and the NRC's and Nebraska Public Power District's presentation slides are enclosed.
In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice," a copy of this letter and its enclosures will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRC's document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.oov/reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely, Kriss M. Kennedy, Chief Project Branch C Division of Reactor Projects Docket: 50-298 License: DPR-46
Enclosures:
- 1. Attendance List
- 2. NRC Presentation Slides
- 3. NPPD Presentation Slides
Nebraska Public Power District cc:
Clay C. Warren, Vice President-Nuclear Nebraska Public Power District P.O. Box 98 Brownville, NE 68321 John R. McPhail, General Counsel Nebraska Public Power District P.O. Box 499 Columbus, NE 68602-0499 P. V. Fleming, Licensing and Regulatory Affairs Manager Nebraska Public Power District P.O. Box 98 Brownville, NE 68321 Michael J. Linder, Director Nebraska Department of Environmental Quality P.O. Box 98922 Lincoln, NE 68509-8922 Chairman Nemaha County Board of Commissioners Nemaha County Courthouse 1824 N Street Auburn, NE 68305 Sue Semerena, Section Administrator Nebraska Health and Human Services System Division of Public Health Assurance Consumer Services Section 301 Centennial Mall, South P.O. Box 95007 Lincoln, NE 68509-5007.
Ronald A. Kucera, Deputy Director for Public Policy Department of Natural Resources P.O. Box 176 Jefferson City, MO 65101 Jerry Uhlmann, Director State Emergency Management Agency P.O. Box 116 Jefferson City, MO 65102-0116
Nebraska Public Power District Chief, Radiation and Asbestos Control Section Kansas Department of Health and Environment Bureau of Air and Radiation 1000 SW Jackson, Suite 310 Topeka, KS 66612-1366 Daniel K. McGhee Bureau of Radiological Health Iowa Department of Public Health 401 SW 7th Street, Suite D Des Moines, IA 50309 William J. Fehrman, President and Chief Executive Officer Nebraska Public Power District 1414 15th Street Columbus, NE 68601
Nebraska Public Power District-4 Electronic distribution by RIV:
Regional Administrator (11SMIV)
DRP Director (ATH)
DRS Director (DDC)
Senior Resident Inspector (SCS)
Branch Chief, DRP/C (KMK)
Senior Project Engineer, DRP/C (WCW)
Staff Chief, DRPITSS (PHH)
RITS Coordinator (KEG)
Dan Merzke, Pilot Plant Program (DXM2)
RidsNrrDIpm~ipb ADAMS: OfYes J-,
Publicly Available E No Initials:_
E Non-Publicly Available E Sensitive R" Non-Sensitive R:\\ CNS\\2004\\CN5-12-04MS-DRP.wpd 5
1 04 5/11/04 OFFICIAL RECORD COPY T=Telephone E=E-mail F=Fax
ENCLOSURE 1 ATTENDANCE LIST
NRC PUBLIC MEETING ATTENDANCE LICENSEE/FACILITY Nebraska Public Power District DATE/TIME May 12, 2004; 7:00 p.m.
LOCATION Brownville Concert Hall INAME (PLEASE PRINT)
IORGANIZATION
/ es)~eg
~-/6TO-U' (tl\\dfA?/
A
~ V k Y-44j7 Pagel1 of 3
NRC PUBLIC MEETING ATTENDANCE LICENSEE/FACILITY Nebraska Public Power District Cooper Nuclear Station DATE/TIME May 12, 2004; 7:00 p.m.
LOCATION Brownville Concert Hall LNAME (PLEASE PRINT)I ORGANIZATION C--1-Cppt /cgs iii;
~IL/'Lj Page 2 of 3
INRC PULCMEETING ATTENDANCE LICENSEE/FACILITY Nebraska Public Power District Cooper Nuclear Station DATE/TME May 12, 2004; 7:00 p.m.
LOCATION Brownville Concert Hall
[NAME (PLEASE PRINT)
IORGANIZATION i
i i
f Page 3 of 3
ENCLOSURE 2 NRC PRESENTATION SLIDES
U.S. Nuclear Regulatory Commission Region IV Cooper Nuclear Station Inspection Exit Meeting NRC Personnel Mark Satorius Deputy Director Division of Reactor Projects Kriss Kennedy Chief, Branch C Division of Reactor Projects Wayne Walker Senior Project Engineer, Branch C Division of Reactor Projects Scott Schwind Senior Resident Inspector Cooper Nuclear Station Steve Cochrum Resident Inspector Cooper Nuclear Station Nebraska Public Power District Cooper Nuclear Station Introduction Meeting Guidelines Purpose of Meeting
- Meeting with Licensee
- Inform Public of Inspection Findings 1 aMeeting Agenda Provisions of Confirmatory Action Letter (CAL) and The Strategic Improvement Plan (TIP)
Inspection Scope Inspection Findings Nebraska Public Power District Response Questions and Answers
Inspection Team
- Wayne Walker
- Mark Sitek
- Vincent Gaddy Team Leader Resident Inspector Senior Project Engineer Confirmatory Action Letter
- Human Performance
- Material Condition and Equipment Reliability
- Plant Modifications and Configuration Control
- Corrective Action Program, Utilization of Industry Operating Experience, and Self-Assessments
- Implementation of Engineering Programs
" I Inspection Scope
- Six CAL Focus Areas
- NRC Baseline Inspections
- Inspection By Team
- NRC and Cooper Performance Indicators
- Cooper Audits and Self Assessments Inspection Results Team reviewed 34 improvement plan actions Actions were completed as described in the Strategic Improvement Plan A number of the important actions in the Action Plans covered by the CAL have been implemented To date 82 percent of CAL Strategic Improvement Plan Actions have been reviewed by NRC Quality of Improvement Plan Closure Packages
- Closure packages were complete Emergency Preparedness
- Improvement Plan Actions addressed in CAL completed and previously inspected&(June 2003)
- NRC Baseline Inspections
- NRC Performance Indicators - Satisfactory
- CNS Performance Indicators - Satisfactory
Evaluation of Human Performance
- 2 CAL related improvement plan actions reviewed and completed.
- Efforts to improve human performance are having a positive affect. However, a number of human performance errors continue to be identified.
- NRC Baseline inspections
,Evaluation of Human Performance
- CNS Performance Indicators
- 1 of 4 unsatisfactory as defined by NPPD Human performance error rate
- 3 of 4 meeting goals Configuration Control Events OSHA Recordable Injury Rate Human Performance Event Free Days Evaluation of Human Performance (cont) it 11 1- -11..... -.
-. - t..
-.... I
- Licensee assessments reveal continuing problems
- CNS taking additional actions Material Condition and Equipment Reliability
- 19 CAL related improvement plan actions completed as scheduled
- Completed actions have contributed to specific improvements in equipment reliability
- However the plant continues to experience equipment reliability problems Material Condition and Equipment Reliability (continued)
- CNS Performance Indicators
-5 of 19 reviewed were unsatisfactory or not meeting goal
-14 of 19 meeting or exceeding goal
- NRC Performance Indicators Plant Modifications and Configuration Control
- 8 CAL related improvement plan actions reviewed.
- Completed actions have demonstrated acceptable performance
- However actions have not been fully effective in addressing a long-standing problem with the quality of operability determinations
Plant Modifications and Configuration Control (continued)
- CNS Performance Indicators
- 6 of 6 meeting or exceeding goal
- NRC Performance Indicators Corrective Action Program, Utilization 0f Industry Operating Experience and Self-Assessment
- 2 CAL improvement plan actions completed as scheduled
- Issues adequately identified, but problems persist with the evaluation of issues and effectiveness of corrective actions.
- NRC baseline inspections
- CNS Performance Indicators Engineering Programs
- 2 CAL related improvement plan actions reviewed
- NRC baseline inspections
- CNS Performance indicators
- Improving trend has been noted Ni Conclusions
- CAL actions completed on schedule
- Progress continues to be made in each CAL area.
A number of human performance errors continue to be identified both by the licensee and the NRC baseline inspection program.
- More time is necessary to demonstrate sustained improvements in material condition and equipment reliability.
- Implementation issues have continued to be identified in the areas of operability determinations, problem evaluation and effectiveness of corrective actions.
U.S. Nuclear Regulatory Commission Region IV Cooper Nuclear Station Inspection Exit Meeting