ER COVER SHEET ER #: ER-ANO-2002-0534-000 Page 1 of 2 Grade:
Revision #:
CLASSIFICATION AND ENGINEERING RESPONSE Implementation:
Reply Response Type:
Quality Classification:
Evaluate and determine results of the battery performance discharge test conducted under MAI 57320.
Problem/Proposed Solution/Justification: (Attach additional sheets as required)
Sugg. Milestone:___________________
Component ID: 2D-11 Date Required:
System ID: 2D Originator:Meyer,Adrian L Date: 4/23/2002 ORIGINATING DEPARTMENT Ext: 5018585546 Dept:
0 N.0.N.0
Title:
Evaluation of 2D11 Performance Discharge Test REVIEW APPROVAL X
Technical Reviewer Design Verifier Supervisor Engineering Manager PSRC Required PSRC Meeting Number:
4/23/2002 Date:
Date:
Date:
Date:
Dobbs,J G GMPO Date:
Date:
4/23/2002 Meyer,Adrian L Responsible Engineer:
Date:
X LBD Impacted YES NO See Attached Problem Resolution: (Attach additional sheets as required)
ER COVER SHEET REVIEWS Engineering Request ER-ANO-2002-0534-000 Review Results ER:
Revison:
Title:
0 Evaluation of 2D11 Performance Discharge Test Page 1 of 1
ER-ANO-2002-0534-000 Engineering Reply Page 1 of 3
==
Description:==
MAI 57320 conducted a Performance Discharge Test on Unit 2 Red Train battery bank 2D11 in accordance with surveillance procedure OP-2403.001. This test was conducted in support of Tech Spec surveillance requirement 4.8.2.3.E.
Battery 2D11 is a C&D Technologies type LC-31 battery. The manufactures 100% rating for this battery is 258 amps over an 8-hour rate of discharge down to an end of cell voltage of 1.81VPC. Since the bank contains 58 cells, an end of test bank voltage of 105V is used (1.81VPC X 58cells = 105V) as the point at which the bank is considered depleted of all its useful energy.
During performance of this test, equipment problems associated with the Albers unit were encountered that required the battery bank to be unloaded in support of repairs. This Engineering Request will evaluate the data from this test and determine if the battery was capable of demonstrating adequate capacity in accordance with surveillance 4.8.2.3.E.
References:
1.
Unit 2 Tech Specs a.
Surveillance 4.8.2.3.E Perform a Performance Discharge Test every 60 months and verify capacity of bank is 80%.
b.
Surveillance 4.8.2.3.F Perform a Performance Discharge Test every 18 months for any battery showing signs of degradation or reaches 85% of service life. Degradation is defined as the batterys capacity drops by more that 10% from previous test or capacity is < 90%.
2.
OP-2403.001-2D11 - 2D11 Performance Discharge Test 3.
IEEE 450 -1995 & 1972 IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead -Acid Batteries for Stationary Applications 4.
EPRI Guide TR-100248R1 Stationary Batteries - Design, Application and Maintenance 5.
ER-W3-99-0194-00 Engineering Request issued by WF3 to evaluate interruptions of a Performance Discharge Test conducted on Station Battery 3A-S.
6.
Raw Albers Test Data - Data recorded during performance of 2D11 Performance Discharge Test conducted under MAI 57320.
7.
C&D Technologies Memorandum - Memorandum dated March 25, 1999 from C&D Technologies 8.
Non Credited Data - Ablers Unit Report during 61 minute period not credited for bank capacity Evaluation:
In accordance with IEEE 450 a performance discharge test is a test of constant current or constant power capacity test, made on a battery after it has been in service to detect any change in capacity. Per OP-2403.001, the performance test conducted is one of constant current. The Albers Unit, that controls the load on the bank must continuously adjust the load resistance as the banks voltage collapses to maintain a
ER-ANO-2002-0534-000 Engineering Reply Page 2 of 3 steady load current. During performance of this test several equipment problems associated with the Albers unit were encountered.
The test was started at 18:22 on 4/22/02. The discharge current was set at 269 amps based on a temperature correction factor that required the discharge current to be increased from 258amps to account for initial elevated electrolyte temperatures. The Albers unit maintained this load for approximately 5-1/2 hours into the expected 8(+) hour test. However problems developed with the Albers Unit requiring the test to be halted. After approximately 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> with the battery disconnected from both the load and its battery charger, the test was again resumed with a load current of 270amps. However the load current drifted down to 252 amps and attempts to increase the current failed thus requiring the test to again be halted. The total duration of this second discharge period (270 amps - 252 amps) was approximately 61 minutes (See attachment 8). After an additional 1hour of working to re-establish the proper load current (had to replace load banks) the test was again resumed at approximately 0450 on 4/23/02 until completion at approximately 0710. Attachment 1 provides the raw Albers unit data that will be used to credit the capacity of the battery bank. This data does not contain the approximate 260 amp-hours of discharge that the battery was subjected to while its load current drifted from 270amps down to 252 amps. Attachment 8 provides this data (Albers report of the discharge not credited in the calculated battery capacity).
Section 6.4 of reference 3 identifies that the test results of a performance discharge test that has been interrupted may be evaluated by either a second test or by analysis. Per UFSAR section 8.3.2, Unit 2 is licensed to IEEE 450-1972, which does not discuss interruptions of a performance discharge test other than for installation of jumpers around cells that are approaching cell voltage reversal. IEEE 450-1995 provides a discussion on limiting the time for installation of jumpers to 6 minutes and recommends limiting the number of jumpers installed to one. The basis for this is that allowing downtimes may allow the battery to supply higher than its normal capacity (especially during short-duration testing) if the battery is allowed more down times.
Per attachment 7, C&D Technologies provides a discussion on the proper method of analyzing the results of a Performance Discharge Test that contains interruptions. The analysis should credit only that portion of the discharge after an interruption when the batterys terminal voltage returns to its pre-interruption value.
Per reference 5 The effect of the test interruption must be taken into account in order to determine the batterys actual capacity. Without a load applied to the battery, the battery voltage recovers. The voltage recovery is the result of weak (diluted) acid surrounding the battery plates diffusing with the stronger (concentrated) acid further away from the plates. This recovery affects the test results by indicating a higher than actual battery capacity.
Per attachment 1, bank voltage did recover from 111.45V to 114.5V prior to initiation of the second credited discharge test. However the banks voltage returned to 111.45V after a 1minute discharge period on the third load test. Therefore, as discussed above a battery bank will recover its terminal voltage upon interruption of its load but will return back to its pre-interruption bank voltage upon re-application of its load. Per reference 4, a battery converts chemical energy into electrical energy during a discharge and this process can be reversed by the application of a charge current to the battery (conversion of electrical energy to chemical energy). However without applying any energy back into the battery via a battery charger, the banks stored energy is limited and cannot increase. Its terminal voltage can increase as discussed above, however its capacity cannot increase.
Therefore as a conservative approach to calculating the batterys capacity the following was performed:
1.
The approximate 260amp-hour discharge period that contained the load current drifting down from an initial setting of 270 amps to 252 amps will not be credited.
2.
The period of time after subsequent restart of the test at which the batterys terminal voltage is above that voltage at which the test was halted will not be credited Based on the above criteria the following is the calculated capacity of battery 2D11:
1st discharge period duration - 334 minutes
ER-ANO-2002-0534-000 Engineering Reply Page 3 of 3 2nd discharge period duration - 138 minutes Capacity = duration that bank remained 105V / 480minutes X 100%
= (472 minutes / 480 minutes) X 100%
= 98.3%
==
Conclusion:==
Based on the above discussion and attachments to this document battery 2D11s capacity remained above 98% demonstrating that the battery remains between a Superior Performing and Rated Performing battery in accordance with reference 4. In reality, the capacity of the battery is greater than 98% due to the exclusion of the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> discharge as discussed above however this added capacity will not be credited.
Procedure OP-2403.001 will perform the evaluation of this test result to required tech spec surveillances 4.8.2.3.E & 4.8.2.3.F in accordance with step 8.5.4 of OP-2403.001.
TELECOPY TRANSMrnAL This page and the followina (
1 page@) are for:
1,400 Union Meeting Road R O h x 3053 Blue Bell, PA 194224858 Telephone (215) 6 19-2700 Fax (2 15) 619-7W From:
Date:
Subject:
lf you did not receive ail pages, please dl me at (245) 819-7846
MEMORANDUM PATE:
25 M h
1999 A d h Meyar Entetergy Operations, InC.
Arkansas Nudear One FROM:
Graham Walker C&O TechnoWis, Inc.
Blue Bell, PA
SUBJECT:
IEEEQSI) 8attery Perfarmam T d n g Pramdiui'~&
Cell Reversal and Cell Bypassing Refemme:
3121199 *Mail Record of Diiussion I've no major cwrections to our discussion, just an expansion to the three topics you've listed.
As both an ovanriew of our discussion, and a summary, I'd opine that the IEEE-dSO recommendations for bypassing a cell that is approaching reversal need not be applied to nuclear safety related batterhs. f say this because with scheduled outages bmming ever shorter, it is mre impartant to have sufficbt test data ta determine the capacity of the good cells than it is to p m M the Or two weak mils in tfw? battery. In ather words, you are probably going to want to replace the weak cells, but not retest the battery.
So, regarding your itemized iapirs.
- 1. One possible basis for the 6 minute limit is that &ere would be inslrffieient dactrolyte diffusion occurring in this short time period, then the overall impract on calculated capacity is not significant. The limitation of bypassing just one oeU enforces the?
above.
In reality, should a test be interrupted for longer than 6 minutes, C4D would assist you in establishing useable data for juMying the results. (t'm going to fax you the test results of just such an occurrence at omr of ywr sister piants. This graphically shows the improvement due to a 36 minute "downtime", but also that the best results are still usaable.)
2-Since more than one cell may approach reversal, particularly near the end of an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> performance test on acid limited d l s (i.e. jars that are fiUsrd with plates and therefore! exhaust the electrolyte befwe the active material kl the plates), it would be more beneficial to continue testing without ward for any of the weaMremmd cells.
For example, say that during an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> performance test, a 60 cell battery has reached 105 terminal vab (1.75 vpc) well shy of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. This is due to (2) cells falling to approximately zero volts, while the remaining 58 cells are still averaging 1.81 vpc.
25 March 1999 Adfian Meyer Page 2 In order to determine the capacity of these good calls;, the must be ~ntinued until their vdtage averages 1.75 vpc. Note that sin-the two weak cells have not been bypassed, the new cut-@ voltage to be mtinually calculaW from the formula, [ (5Bce?lls x 1.75 volts) - (vo the 2 weak cells) f.
- 3. 1 should not have brwght up the possibility of cells discharging do water. This is not a crediblet event during a discharge test wh6m personnel are available to interrupt or stop the test For the type of tests wa are discussing (typically 4 io 8 b u r performan@ tests), calla that lo into reversal will &titill hwe stme concluetivity remaining in the electrolyte, which is not likely to have been depleted all the way to water. Gialls that have reversed during a 4 to 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> discharge m y have difficulty accepting a charge, but I don't Mieve the Wl would act like a water-stat.
Sincerely, Graham Walker Manager, Nuchr Applications
Battery 3A-S Perfo mnce Test (Co~%r;led)
08:34:15 *************** BCT-2000 LOAD TEST REPORT ************** 04/21/102 REPORT BASED ON 01:00 TIME INTERVAL GENERAL TEST DATA:
TEST LOCATION ANO2 TEST DATE 04/21/102 TEST START TIME 01:08:14 TEST END TIME 02:09:40 BATTERY ID 2D-11 BATTERY MFG & MODEL INSTALLATION DATE 00/00/00 TEST PARAMETERS:
PROGRAMMED LOAD 0269 AMPS PROGRAMMED TEST TIME 12:00:00 TEST MODE SINGLE STRING NUMBER OF CELLS 058 OVERALL VOLTAGE ALARM 108.00 OVERALL VOLTAGE SHUTDOWN 105.00 CELL VOLTAGE ALARM 1.05 CELL VOLTAGE SHUTDOWN 0.75 TEMPERATURE 077 F Degrees RATED BATTERY DISCHARGE TIME 08:00:00 TEST RESULTS ACTUAL DISCHARGE TIME = 01:01:26 RATED DISCHARGE TIME = 08:00:00 OVERALL STRING % CAPACITY = 12.8 THE FOLLOWING CELLS DROPPED BELOW THE ALARM LEVEL:
CELL #
TEST TIME
% CAPACITY IF THE PROGRAMMED ALARM LEVEL REPRESENTS THE TRUE END VOLTAGES FOR THIS TEST THEN - THE FOLLOWING CELLS FAILED THE CAPACITY TEST (BELOW 80%), AND SHOULD BE INVESTIGATED FOR POSSIBLE REPLACEMENT:
TEST ACTIVITY ELAPSED TEST TEST ACTIVITY
- 00:00:00 00:00:00 ----> NEW ALARM LEVELS
> [CELL] ALARM=1.05 SHUTDOWN=0.75
[OV] ALARM=108.0 SHUTDOWN=105.0
- 00:00:00 00:00:00 ----> TEST STARTED
- 00:00:00 00:00:00 ----> PROGRAMMED LOAD [0269 AMPS DURATION= 12:00:00]
- 00:14:56 00:14:56 ----> MANUAL MODE
- 01:01:26 01:01:26 ----> TEST ENDED
TEST DATA
Print 0001 Test Time = 00:00:00 Battery Volts = +115.7 Amps =
0 001= +1.99 002= +1.99 003= +1.99 004= +1.99 005= +1.99 006= +1.99 007= +1.99 008= +1.99 009= +1.99 010= +1.99 011= +1.99 012= +1.99 013= +1.99 014= +1.99 015= +1.99 016= +1.99 017= +1.99 018= +1.99 019= +1.99 020= +1.99 021= +1.98 022= +1.99 023= +1.99 024= +2.00 025= +2.01 026= +1.99 027= +1.99 028= +1.99 029= +1.99 030= +1.99 031= +1.99 032= +1.99 033= +1.99 034= +1.99 035= +1.99 036= +1.98 037= +1.98 038= +1.99 039= +1.99 040= +1.99 041= +1.99 042= +1.99 043= +1.99 044= +1.99 045= +1.98 046= +1.99 047= +1.99 048= +1.99 049= +1.99 050= +1.99 051= +1.99 052= +1.99 053= +1.99 054= +1.99 055= +1.99 056= +1.99 057= +1.99 058= +1.99
Print 0002 Test Time = 00:01:00 Battery Volts = +112.2 Amps =
270 001= +1.94 002= +1.94 003= +1.94 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.95 020= +1.92 021= +1.93 022= +1.93 023= +1.94 024= +1.94 025= +1.95 026= +1.94 027= +1.94 028= +1.94 029= +1.94 030= +1.94 031= +1.94 032= +1.94 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.94 040= +1.93 041= +1.93 042= +1.93 043= +1.95 044= +1.93 045= +1.92 046= +1.93 047= +1.94 048= +1.93 049= +1.94 050= +1.94 051= +1.94 052= +1.94 053= +1.94 054= +1.94 055= +1.94 056= +1.94 057= +1.94 058= +1.94
Print 0003 Test Time = 00:02:00 Battery Volts = +112.2 Amps =
270 001= +1.94 002= +1.94 003= +1.94 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.94 027= +1.94 028= +1.94 029= +1.93 030= +1.94 031= +1.94 032= +1.94 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.94 051= +1.93 052= +1.94 053= +1.94 054= +1.94 055= +1.94 056= +1.94 057= +1.94 058= +1.94
Print 0004 Test Time = 00:03:00 Battery Volts = +112.2 Amps =
270 001= +1.94 002= +1.94 003= +1.94 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.94 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.94 057= +1.93 058= +1.94
Print 0005 Test Time = 00:04:00 Battery Volts = +112.1 Amps =
270 001= +1.93 002= +1.94 003= +1.94 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0006 Test Time = 00:05:00 Battery Volts = +112.1 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0007 Test Time = 00:06:00 Battery Volts = +112.1 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0008 Test Time = 00:07:00 Battery Volts = +112.0 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.93 005= +1.94 006= +1.93 007= +1.93 008= +1.94 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0009 Test Time = 00:08:00 Battery Volts = +112.0 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.93 005= +1.93 006= +1.92 007= +1.93 008= +1.93 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0010 Test Time = 00:09:00 Battery Volts = +111.9 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.93 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.93 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.93 037= +1.93 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0011 Test Time = 00:10:00 Battery Volts = +111.9 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.93 011= +1.93 012= +1.93 013= +1.94 014= +1.92 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.94 034= +1.93 035= +1.93 036= +1.92 037= +1.92 038= +1.94 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0012 Test Time = 00:11:00 Battery Volts = +111.8 Amps =
270 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.93 013= +1.93 014= +1.92 015= +1.94 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.93 041= +1.93 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0013 Test Time = 00:12:00 Battery Volts = +111.8 Amps =
270
001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.93 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0014 Test Time = 00:13:00 Battery Volts = +111.9 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0015 Test Time = 00:14:00 Battery Volts = +111.9 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0016 Test Time = 00:15:00 Battery Volts = +111.9 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0017 Test Time = 00:16:00 Battery Volts = +111.9 Amps =
254
001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0018 Test Time = 00:17:00 Battery Volts = +111.8 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0019 Test Time = 00:18:00 Battery Volts = +111.8 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.94 017= +1.93 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0020 Test Time = 00:19:00 Battery Volts = +111.8 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.93 019= +1.94 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.95 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.94 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0021 Test Time = 00:20:00 Battery Volts = +111.7 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92
007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.92 021= +1.92 022= +1.93 023= +1.93 024= +1.94 025= +1.94 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.92 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0022 Test Time = 00:21:00 Battery Volts = +111.7 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.92 022= +1.92 023= +1.93 024= +1.93 025= +1.94 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.93 040= +1.91 041= +1.92 042= +1.93 043= +1.92 044= +1.93 045= +1.92 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0023 Test Time = 00:22:00 Battery Volts = +111.7 Amps =
254 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.92 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.93 027= +1.93 028= +1.93 029= +1.93 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.93 045= +1.91 046= +1.93 047= +1.93 048= +1.93 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0024 Test Time = 00:23:00 Battery Volts = +111.7 Amps =
251 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.93 027= +1.93 028= +1.93 029= +1.92 030= +1.93 031= +1.93 032= +1.93 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0025 Test Time = 00:24:00 Battery Volts = +111.6 Amps =
252 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92
013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.93 028= +1.93 029= +1.92 030= +1.93 031= +1.93 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.93 050= +1.93 051= +1.93 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0026 Test Time = 00:25:00 Battery Volts = +111.6 Amps =
252 001= +1.93 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.93 031= +1.93 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.93 051= +1.92 052= +1.93 053= +1.93 054= +1.93 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0027 Test Time = 00:26:00 Battery Volts = +111.6 Amps =
252 001= +1.92 002= +1.93 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.93 053= +1.91 054= +1.92 055= +1.93 056= +1.93 057= +1.93 058= +1.93
Print 0028 Test Time = 00:27:00 Battery Volts = +111.5 Amps =
252 001= +1.92 002= +1.92 003= +1.93 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.93 057= +1.93 058= +1.91
Print 0029 Test Time = 00:28:00 Battery Volts = +111.5 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92
019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0030 Test Time = 00:29:00 Battery Volts = +111.5 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0031 Test Time = 00:30:00 Battery Volts = +111.5 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.92 005= +1.93 006= +1.92 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0032 Test Time = 00:31:00 Battery Volts = +111.5 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.92 005= +1.93 006= +1.91 007= +1.92 008= +1.93 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0033 Test Time = 00:32:00 Battery Volts = +111.3 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.92 005= +1.92 006= +1.91 007= +1.92 008= +1.92 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93
025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0034 Test Time = 00:33:00 Battery Volts = +111.3 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.92 008= +1.92 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.92 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0035 Test Time = 00:34:00 Battery Volts = +111.3 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.92 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.91 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0036 Test Time = 00:35:00 Battery Volts = +111.3 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.91 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0037 Test Time = 00:36:00 Battery Volts = +111.3 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.92 011= +1.92 012= +1.92 013= +1.93 014= +1.91 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92
031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0038 Test Time = 00:37:00 Battery Volts = +111.2 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.92 013= +1.93 014= +1.91 015= +1.93 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.92 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0039 Test Time = 00:38:00 Battery Volts = +111.2 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.92 013= +1.93 014= +1.91 015= +1.92 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.92 034= +1.92 035= +1.92 036= +1.91 037= +1.92 038= +1.92 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0040 Test Time = 00:39:00 Battery Volts = +111.2 Amps =
252 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0041 Test Time = 00:40:00 Battery Volts = +111.2 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91
037= +1.91 038= +1.91 039= +1.92 040= +1.91 041= +1.92 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0042 Test Time = 00:41:00 Battery Volts = +111.1 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.93 017= +1.92 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.92 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.91 041= +1.91 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0043 Test Time = 00:42:00 Battery Volts = +111.1 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.93 017= +1.91 018= +1.92 019= +1.93 020= +1.91 021= +1.91 022= +1.91 023= +1.92 024= +1.93 025= +1.94 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.90 041= +1.91 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0044 Test Time = 00:43:00 Battery Volts = +111.1 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.91 021= +1.91 022= +1.91 023= +1.91 024= +1.93 025= +1.93 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.90 041= +1.91 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0045 Test Time = 00:44:00 Battery Volts = +111.1 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.93 025= +1.93 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.90 041= +1.91 042= +1.92
043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0046 Test Time = 00:45:00 Battery Volts = +111.0 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.92 027= +1.92 028= +1.92 029= +1.92 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.90 041= +1.91 042= +1.92 043= +1.92 044= +1.92 045= +1.91 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0047 Test Time = 00:46:00 Battery Volts = +111.0 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.92 027= +1.92 028= +1.92 029= +1.91 030= +1.92 031= +1.92 032= +1.92 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.90 041= +1.91 042= +1.92 043= +1.92 044= +1.92 045= +1.90 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0048 Test Time = 00:47:00 Battery Volts = +111.0 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.92 028= +1.91 029= +1.91 030= +1.92 031= +1.92 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.92 040= +1.90 041= +1.91 042= +1.91 043= +1.92 044= +1.92 045= +1.90 046= +1.92 047= +1.92 048= +1.92 049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0049 Test Time = 00:48:00 Battery Volts = +111.0 Amps =
251 001= +1.92 002= +1.92 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.92 028= +1.91 029= +1.91 030= +1.92 031= +1.92 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.92 048= +1.91
049= +1.92 050= +1.91 051= +1.92 052= +1.92 053= +1.91 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0050 Test Time = 00:49:00 Battery Volts = +111.0 Amps =
251 001= +1.92 002= +1.91 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.92 050= +1.91 051= +1.91 052= +1.92 053= +1.90 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0051 Test Time = 00:50:00 Battery Volts = +110.9 Amps =
251 001= +1.91 002= +1.91 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.92 050= +1.91 051= +1.91 052= +1.92 053= +1.90 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0052 Test Time = 00:51:00 Battery Volts = +110.9 Amps =
251 001= +1.91 002= +1.91 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.92 050= +1.91 051= +1.91 052= +1.92 053= +1.90 054= +1.92 055= +1.92 056= +1.92 057= +1.92 058= +1.91
Print 0053 Test Time = 00:52:00 Battery Volts = +110.9 Amps =
251 001= +1.91 002= +1.91 003= +1.92 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91
055= +1.91 056= +1.92 057= +1.92 058= +1.91
Print 0054 Test Time = 00:53:00 Battery Volts = +110.9 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.91 005= +1.92 006= +1.91 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.92 057= +1.92 058= +1.90
Print 0055 Test Time = 00:54:00 Battery Volts = +110.8 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.91 005= +1.92 006= +1.90 007= +1.91 008= +1.92 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0056 Test Time = 00:55:00 Battery Volts = +110.8 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.91 005= +1.91 006= +1.90 007= +1.91 008= +1.91 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0057 Test Time = 00:56:00 Battery Volts = +110.8 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.91 005= +1.91 006= +1.90 007= +1.91 008= +1.91 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.91 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0058 Test Time = 00:57:00 Battery Volts = +110.8 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.90 005= +1.91 006= +1.90 007= +1.90 008= +1.91 009= +1.91 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.90 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0059 Test Time = 00:58:00 Battery Volts = +110.8 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.90 005= +1.91 006= +1.90 007= +1.90 008= +1.91 009= +1.90 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.90 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0060 Test Time = 00:59:00 Battery Volts = +110.8 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.90 005= +1.91 006= +1.90 007= +1.90 008= +1.91 009= +1.90 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.90 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0061 Test Time = 01:00:00 Battery Volts = +110.7 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.90 005= +1.91 006= +1.90 007= +1.90 008= +1.91 009= +1.90 010= +1.91 011= +1.91 012= +1.91 013= +1.92 014= +1.90 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0062 Test Time = 01:01:00 Battery Volts = +110.7 Amps =
251 001= +1.91 002= +1.91 003= +1.91 004= +1.90 005= +1.91 006= +1.90 007= +1.90 008= +1.91 009= +1.90 010= +1.90 011= +1.90 012= +1.91 013= +1.92 014= +1.90 015= +1.92 016= +1.92 017= +1.91 018= +1.91 019= +1.92 020= +1.90 021= +1.90 022= +1.91 023= +1.91 024= +1.92 025= +1.93 026= +1.91 027= +1.91 028= +1.91 029= +1.91 030= +1.91 031= +1.91 032= +1.91 033= +1.91 034= +1.91 035= +1.91 036= +1.91 037= +1.91 038= +1.91 039= +1.91 040= +1.90 041= +1.91 042= +1.91 043= +1.91 044= +1.91 045= +1.90 046= +1.91 047= +1.91 048= +1.91 049= +1.91 050= +1.90 051= +1.91 052= +1.91 053= +1.90 054= +1.91 055= +1.91 056= +1.91 057= +1.91 058= +1.90
Print 0063 Test Time = 01:01:26 Battery Volts = +110.6 Amps =
250 001= +1.91 002= +1.90 003= +1.91 004= +1.90 005= +1.90 006= +1.90 007= +1.90 008= +1.90 009= +1.90 010= +1.90 011= +1.90 012= +1.90 013= +1.91 014= +1.90 015= +1.91 016= +1.91 017= +1.90 018= +1.91 019= +1.91 020= +1.90 021= +1.90 022= +1.90 023= +1.91 024= +1.91 025= +1.92 026= +1.91 027= +1.90 028= +1.90 029= +1.90 030= +1.91 031= +1.90 032= +1.91 033= +1.90 034= +1.90 035= +1.90 036= +1.90 037= +1.90 038= +1.91 039= +1.91 040= +1.90 041= +1.90 042= +1.90 043= +1.91 044= +1.90 045= +1.90 046= +1.90 047= +1.90 048= +1.90 049= +1.90 050= +1.90 051= +1.90 052= +1.90 053= +1.90 054= +1.90 055= +1.90 056= +1.90 057= +1.91 058= +1.90
l--------l--------l--------l--------l--------l--------l--------l--------l l
INTERTIER CELL NUMBERS l
l--------l--------l--------l--------l--------l--------l--------l--------l l
019-l 039-l 000-l 000-l 000-l 000-l 000-l 000-l l
020 l
040 l
000 l
000 l
000 l
000 l
000 l
000 l
l--------l--------l--------l--------l--------l--------l--------l--------l l
END OF TEST INTERTIER VOLTAGE DROPS l
l--------l--------l--------l--------l--------l--------l--------l--------l l +0.010 l +0.004 l +0.000 l +0.000 l +0.000 l +0.000 l +0.000 l +0.000 l l--------l--------l--------l--------l--------l--------l--------l--------l
2Dl I Bank Voltage Performance Discharge Test - 2R15 125 124 Temperature Corrected Manufacturer's Rating - 269amps @ 8Hr Dischar I
1 Failure period that resulted in I
losses greater than 251 amp-hours I
of the battery bank. These losses I
i were not credited.
I - Bank Voltage Total Credited Discharge Period of 472 minutes, producing a capacity factor of 98.3%.
4/22/02 4/22/02 4122102 4/22/02 4/22/02 4/22/02 4/23/02 4/23/02 4/23/02 4/23/02 4/23/02 4/23/02 4/23/02 4/23/02 16:48 18:OO 19:12 20:24 21:36 22:48 0:00 1:12 2:24 3:36 4:48 6:00 7:12 8:24 Time
Time 4/22/02 18:22 4/22/02 1 8:23 4/22/02 18:24 4/22/02 18:25 4/22/02 18:26 4/22/02 18:27 4/22/02 18:28 4/22/02 18:29 4/22/02 1 8:30 4/22/02 l8:3l 4/22/02 18:32 4/22/02 l8:33 4/22/02 18:34 4/22/02 18:35 4/22/02 18:36 4/22/02 18:37 4/22/02 18:38 4/22/02 18:39 4/22/02 18:40 4/22/02 18:41 4/22/02 18:42 4/22/02 18:43 4/22/02 18:44 4/22/02 1 8:45 4/22/02 18:46 4/22/02 18:47 4/22/02 18:48 4/22/02 18:49 4/22/02 18:50 4/22/02 1 8:51 4/22/02 l8:52 4/22/02 18:53 4/22/02 1 8:54 4/22/02 18:55 4/22/02 l8:56 4/22/02 l8:57 4/22/02 l8:58 4/22/02 18:59 4/22/02 1 9:OO 4/22/02 19:Ol 4/22/02 19:02 4/22/02 l9:O3 4/22/02 l9:O4 4/22/02 l9:O5 4/22/02 19:06 4/22/02 19:07 4/22/02 19:O8 4/22/02 19:09 4/22/02 l9:lO 4/22/02 1 9: 1 1 4/22/02 l9:l2 4/22/02 1 9: 1 3
Highlighted areas are excluded for the overall capacity.
58 Bank Voltage Limit