Tech Spec Page for Amendment No. 52, Source Range Neutron Flux Reactor Trip Function Response Time Test
ML041140453
Person / Time
Site: Watts Bar Tennessee Valley Authority icon.png
Issue date: 04/19/2004
From:
NRC/NRR/DLPM/LPD2
To:
Chernoff, M H, NRR/DLPM, 301-415-4041
References
TAC MC0485
Download: ML041140453 (1)


Text

RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 2 of 9)

Reactor Trip System Instrumentation APPLICABLE MODES NOMINAL OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE TRIP FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE SETPOINT

5.

Source Range 2(d) 2 1, J SR 3.3.1.1 S 1.5 E5 1.0 E5 cps Neutron Flux SR 3.3.1.8 cps SR 3.3. 1.11 3(a) 4(a) S(a) 2 J,K SR3.3.1.1 1.5 E5 1.0 ES cps SR 3.3.1.8 cps SR 3.3.1.11 SR 3.3.1.15 3(e) 4(e) 5(e) 1 L

SR 3.3. 1.1 N/A N/A SR 3.3.1.11

6.

Overtemperature AT 1,2 4

W SR 3.3. 1.1 Refer to Refer to SR 3.3.1.3 Note I Note I SR 3.3.1.6 (Page 3.3-21)

(Page 3.3-21)

SR 3.3.1.7 SR 3.3.1.10 SR 3.3.1.15

7.

Overpower AT 1,2 4

W SR 3.3.1.1 Refer to Refer to SR 3.3.1.7 Note 2 Note 2 SR 3.3.1.10 (Page 3.3-22)

(Page 3.3-22)

SR 3.3.1.15

8.

Pressurizer Pressure

a.

Low IM 4

X SR3.3.1.1 2 1964.8 1970psig SR 3.3.1.7 psig SR 3.3.1.10 SR 3.3.1.15

b.

High 1,2 4

W SR 3.3.1.1 2390.2 2385 psig SR 3.3.1.7 psig SR 3.3.1.10 SR 3.3.1.15 (continued)

(a) With RTBs closed and Rod Control System capable of rod withdrawal.

(d) Below the P-6 (Intermediate Range Neutron Flux) interlocks.

(e) With the RTBs open.

In this condition, source range Function does not provide reactor trip but does provide indication.

(f) Above the P-7 (Low Power Reactor Trips Block) interlock.

Watts Bar-Unit 1 3.3-16 Amendment N o.

5 2