March 2004 Monthly Operating Report for Calvert Cliffs, Units 1 & 2
ML041130291
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 04/14/2004
From: Nietmann K
Constellation Energy Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML041130291 (7)


Text

t Kevin J. Nietmann Plant General Manager Calvert Cliffs Nuclear Power Plant Constellation Generation Group, LLC 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410 495-4101 410 495-4787 Fax Constellation I

Energy Group April 14, 2004 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

SUBJECT:

Document Control Desk Calvert Cliffs Nuclear Power Plant Unit Nos. I & 2; Docket Nos. 50-317 & 50-3 18 March 2004 Operating Data Reports The subject reports are being sent to you as required by Technical Specification 5.6.4.

Should you have questions regarding this matter, we will be pleased to discuss them with you.

Very truly yours,

/f//J KJN/CAN/bjd Attachments cc:

J. Petro, Esquire J. E. Silberg, Esquire Director, Project Directorate I-1, NRC G. S. Vissing, NRC H. J. Miller, NRC Resident Inspector, NRC R. I. McLean, DNR J. Wright, INPO K. N. Larson, ANI

 4

Oc-- 6-1

OPERATING DATA REPORT Docket No. 50-317 Calvert Cliffs Unit 1 April 1, 2004 Prepared by Herman 0. Olsen Telephone:(410)495-6734 REPORTING PERIOD DESIGN ELECTRICAL RATING (NET MWe)

MAXIMUM DEPENDABLE CAP'Y (NET MWe)

MARCH 2004 845 825 Year-to-Date Cumulative to Date This month

1. NUMBER OF HOURS REACTOR WAS CRITICAL
2. HOURS GENERATOR ON LINE
3. UNIT..RESERVE SHUTDOWN HOURS
4. NET.:ELECTRICAL ENERGY.GENERATED(MWH) 717.0 2,157.0 194,206.4 708.6 2,148.6 191,034.3 60.062.

0.1,8 5,5 1'.,

5 307

.'.606,062

.1851,5'S92~ -.1 156,551,307.

UNIT SHUTDOWNS DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 50-317 Calvert Cliffs - Ul April 1. 2004 Herman 0. Olsen (410) 495-6734 REPORTING MONTH March 2004 NO.

DATE TYPE DURATION REASON' METHOD OF CAUSE/CORRECTIVE ACTIONS F:

FORCED (HOURS)

SHUTTING S:

SCHEDULED DOWN 2 COMMENTS04-001 040320 F

35.4 B

3 On 03/20/04 at 1340 an automatic trip occurred from 100% power. The reactor tripped due to low Steam Generator water level caused by a short circuit that was created while replacing a recorder in a control panel.

The short circuit affected the voltage to the digital feedwater control system, which caused a feedwater regulating valve to close. The unit was brought to a safe shutdown condition in Mode 3. After the cause was verified and corrected the unit was returned to service on 03/22/04 at 0103. Corrective actions were to make repairs to the impacted portions of the feedwater control system. LER 2004-001 applies.

X Reason:

A - Equipment Failure B - Maintenance or Test C - Refueling D - Regulatory Restriction E -Operator Training & License Examination F - Administrative G - Operational Error H - Other 2 Method:

I - Manual 2 - Manual Scram.

3 - Automatic Scram.

4 - Continued 5 - Other

I DOCKET NO. 50-317 CALVERT CLIFFS - UNIT 1 April 1, 2004

SUMMARY

OF OPERATING EXPERIENCE March 2004 The unit began the month at 100% power.

On 03/20/04 at 1340 an automatic reactor trip occurred due to low steam generator water level. The low level was caused by maintenance which affected the digital feedwater control system, resulting in a loss of feed. Repairs were made to the feedwater control system and the unit was taken critical on 03/21/04 at 1641. The unit was paralleled to the grid on 03/22/04 at 0103 and returned to 100% power at 1315.

On 03/30/04 at 2220 power was reduced to 70.0% as a precautionary measure, due to a fire protection sprinkler actuating in the vicinity of 11 Steam Generator Feed Pump. Repairs were made to the sprinkler and power was returned to 100% on 03/31/04 at 1003.

The unit operated at 100% for the remainder of the month.

I OPERATING DATA REPORT Docket No. 50-318 Calvert Cliffs Unit 2 April 1, 2004 Prepared by Herman 0. Olsen Telephone:(410)495-6734 REPORTING PERIOD DESIGN ELECTRICAL RATING (NET MWe)

MAXIMUM DEPENDABLE CAP Y (NET MWe)

MARCH 2004 845 835 Year-Cumulative to-Date-to'Date This month

1. NUMBER OF HOURS REACTOR WAS CRITICAL
2. HOURS GENERATOR ON LINE
3. UNIT RESERVE SHUTDOWN HOURS
4. NET ELECTRICAL ENERGY GENERATED(MWH) 744.0 744.0 0.0 655,017 2,134.4-186,861.2 :

2,129.6': : 184,967.8 0.0 0.0 1,873,593 152,616,883

DOCKET NO. 50-318 CALVERT CLIFFS - UNIT 2 April 1, 2004

SUMMARY

OF OPERATING EXPERIENCE March 2004 The unit began the month at 100% power.

On 03/14/04 at 0045 Control Element Assembly (CEA) #58 dropped while performing free movement testing per STP-0-29-2. Power immediately dropped to approximately 96%. At 0223 power was further reduced to 68%. The CEA was returned to the normal position and power was returned to 100% at 0910.

On 03/26/04 at 2300 power was reduced to 83% for Main Turbine Valve Testing. Testing was completed and power was returned to 100% on 03/27/04 at 0035.

The unit operated at 100% power for the remainder of the month.

UNIT SHUTDOWNS DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 50-318 Calvert Cliffs-U2 Anril 1. 2004 Herman 0. Olsen (410) 495-6734' REPORT MONTH March 2004 NO.

DATE TYPE DURATION REASON' METHOD OF CAUSE/CORRECTIVE ACTIONS F:

FORCED (HOURS)

SHUTTING S:

SCHEDULED DOWN 2 COMMENTS There were no shutdowns this month.

l l1

-l l

ll X Reason:

A - Equipment Failure B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training & License Examination F - Administrative G - Operational Error H - Other 2 Method:

I -Manual '. -

I,.

2 - Manual Scram 3 - Automatic Scram 4 - Continued 5 - Other