ML040360416

From kanterella
Jump to navigation Jump to search
Phase 3 SDP Analysis
ML040360416
Person / Time
Site: Arkansas Nuclear 
(DPR-051)
Issue date: 01/14/2004
From:
NRC Region 4
To:
References
FOIA/PA-2003-0358
Download: ML040360416 (1)


Text

Phase 3 SDP Analysis Performance Deficiency ANO Unit 1 fire zone 99-M (North Electrical Switchgear Room) did not meet regulatory requirements for separation of electric cables and equipment of redundant trains of systems necessary to achieve post-fire safe shutdown, and there was lack of adequate procedures for manual actions to achieve post-fire safe shutdown following a fire in fire zone 99-M (or other identified fire zones equivalent to 99-M)

Assumptions Red train cables are not protected with one-hour rated barrier, and are not separated from the Green train cables by a minimum of 20 feet distance free of intervening combustibles No automatic fixed fire suppression system Ionization detection system provides alarm in Main Control Room w

Credit for fire brigade response and arrival at fire zone 1 00-N, which is adjacent to fire zone 99-M Heat release rates of 200-500 kW in fire modeling of duration and severity I.),- -

r L