ML033580462

From kanterella
Jump to navigation Jump to search
SERP Worksheet for SDP-Related Findings
ML033580462
Person / Time
Site: Arkansas Nuclear  
Issue date: 01/23/2003
From:
NRC/OE
To:
References
FOIA/PA-2003-0358, IR-01-006
Download: ML033580462 (1)


Text

SERP Worksheet for SDP-Related SERP Date: January 23, 2003 Cornerstone Affected and Proposed Preliminarv Results:

.,~~~~

=;rN.

'I_

lbit 4 of Aft I This finding affects the Mitigating Systems Comerstone, because It affects the objective to ensure the availability, reliability, and capability of systems that respond to an external event (fire) to prevent undesirable consequences. Specifically, the licensee's ability to achieve and maintain hot shutdown conditions in the event of a fire in Fire Areas 98J and 99M is affected by the lack of separation of redundant trains of safe shutdown systems In accordance with 10 CFR Part 50, Appendix R

_Sc Licensee:

Facility/Location:

Docket No(s):

License No(s):

Inspection Report No:

Date of Exit Meeting:

Issue Sponsor:

Meeting Members:

Issue Sponsor.

Technical Spokesperson:

Entergy Operations, Inc.

Arkansas Nuclear One E.-

50-313 and 50-368 DPR-51, NPF-6 2001-06 August 21, 2001-final exit meeting pen Dwight Chamberlain Dwight Chamberlain NRR Probabilistic Safety Assessment Office Branch Program Spokesperson:

OE Representative:

NRR Inspection Program Branch Jennifer Dixon-Herrity A.

Brief Description of Issue ANO Unit I fire zones for the diesel generator corridor (Fire Zone 98J) and the north electrical switchgear (Fire Zone 99M) room did not meet separation requirements for electrical cables associated with redundant trains of safe shutdown equipment. In addition, the licensee did not have adequate procedures for the manual actions necessary to abhieve-safeisbutdown (Section 1 R05.3 of Referencei..L I

p..L *.

  • .v. ii.tfl 1U 

_________________