November 10, 2003 Mr. Michael R. Kansler, President Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601

SUBJECT:

INDIAN POINT NUCLEAR GENERATING UNIT NO. 2 RE: FINAL ACCIDENT SEQUENCE PRECURSOR ANALYSIS OF JULY 2002 OPERATIONAL EVENT

Dear Mr. Kansler:

Enclosed for your information is the final Accident Sequence Precursor (ASP) analysis of an adverse condition which was identified at Indian Point Nuclear Generating Unit No. 2 in July 2002. The condition involved a moderate degradation of a control room wall fire barrier and was described in Nuclear Regulatory Commission (NRC) Inspection Report 50-247/02-010, dated July 19, 2002. The degraded fire barrier was determined to be of low to moderate safety significance (White) in accordance with the Significance Determination Process (SDP) as documented in the final significance determination for this issue, dated November 8, 2002. The results of the final ASP analysis indicate that this condition is an accident precursor (i.e., a condition which results in a change in conditional core damage probability (CCDP) > 1E-6).

For the July 2002 event, the findings in the ASP analysis (change in CCDP and dominant risk contributors) are consistent with those in the SDP. Since this ASP analysis confirms the results of the final significance determination, which has been reviewed by the NRC staff and Entergy Nuclear Operations, Inc., it is being issued as a final product for information only. In the past, preliminary versions of all ASP analyses were issued for internal peer review by the NRC staff and for external peer review by the licensee. Comments received from these reviews were then resolved as part of the final analysis. To increase efficiency, we are now issuing the non-controversial ASP analyses as final documents.

The NRC staff is continuing to review the appropriate classification of these documents within our records management program, considering changes in our practices following the events of September 11, 2001. Pending a final determination, the enclosed analyses have been marked as "Sensitive Information" in accordance with Section 2.790(d) of Title 10 of the Code of Federal Regulations. Therefore, the staff has not made it publicly available. Please control the document accordingly (i.e., treat the document as if you had determined that it contained trade

M. Kansler secrets and commercial or financial information that you considered privileged or confidential).

We will inform you if the classification of the document changes as a result of our ongoing assessments.

If you have any questions regarding the analysis, please contact me at 301-415-1457.

Sincerely,

/RA/

Patrick D. Milano, Sr. Project Manager, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-247

Enclosure:

As stated (Sensitive - Not for Public Disclosure) cc w/o encl: See next page

M. Kansler secrets and commercial or financial information that you considered privileged or confidential).

We will inform you if the classification of the document changes as a result of our ongoing assessments.

If you have any questions regarding the analysis, please contact me at 301-415-1457.

Sincerely,

/RA/

Patrick D. Milano, Sr. Project Manager, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-247

Enclosure:

As stated (Sensitive - Not for Public Disclosure) cc w/o encl: See next page DISTRIBUTION w/enclosure:

PD I-1 R/F R. Laufer P. Milano C. Bixler, R-I D. Lew, R-I J. Houghton, RES ACRS DISTRIBUTION without enclosure:

PUBLIC C. Holden S. Little L. Marsh S. Newberry, RES M. Harper, RES J. Golla W. Reckley OGC ACCESSION NO.: ML033140263

Enclosure:

ML031920545

  • See previous concurrence OFFICE PDI-1/PM PDI-1/LA DRP/R-I PDI-1/SC NAME PMilano CRaynor for SLittle TWalker by phone TColburn for RLaufer DATE 11/07/ 03 11/ 07/03 11/03/03 11/10/03 OFFICIAL RECORD COPY

Indian Point Nuclear Generating Unit No. 2 cc: w/enclosure:

Mr. Gary Taylor Chief Executive Officer Entergy Operations, Inc.

1340 Echelon Parkway Jackson, MS 39213 Mr. John Herron Senior Vice President and Chief Operating Officer Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Mr. Fred Dacimo Vice President, Operations Entergy Nuclear Operations, Inc.

Indian Point Energy Center 295 Broadway, Suite 2 P.O. Box 249 Buchanan, NY 10511-0249

Indian Point Nuclear Generating Unit No. 2 cc w/o enclosure:

Mr. Christopher Schwarz General Manager, Plant Operations Entergy Nuclear Operations, Inc.

Indian Point Energy Center 295 Broadway, Suite 2 P.O. Box 249 Buchanan, NY 10511-0249 Mr. Dan Pace Vice President Engineering Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Mr. Randall Edington Vice President Operations Support Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Mr. John Kelly Director, Nuclear Safety Assurance Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Ms. Charlene Faison Manager, Licensing Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Director of Oversight Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Mr. James Comiotes Director, Nuclear Safety Assurance Entergy Nuclear Operations, Inc.

Indian Point Energy Center 295 Broadway, Suite 2 P.O. Box 249 Buchanan, NY 10511-0249

Mr. John McCann Manager, Licensing Entergy Nuclear Operations, Inc.

Indian Point Energy Center 295 Broadway, Suite 2 P. O. Box 249 Buchanan, NY 10511-0249 Mr. John M. Fulton Assistant General Counsel Entergy Nuclear Operations, Inc.

440 Hamilton Avenue White Plains, NY 10601 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector, Indian Point 2 U. S. Nuclear Regulatory Commission 295 Broadway, Suite 1 P.O. Box 38 Buchanan, NY 10511-0038 Mr. Peter R. Smith, Acting President New York State Energy, Research, and Development Authority Corporate Plaza West 286 Washington Avenue Extension Albany, NY 12203-6399 Mr. J. Spath, Program Director New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 Mr. Paul Eddy Electric Division New York State Department of Public Service 3 Empire State Plaza, 10th Floor Albany, NY 12223

Indian Point Nuclear Generating Station, Unit No. 2 cc w/o enclosure:

Mr. Charles Donaldson, Esquire Assistant Attorney General New York Department of Law 120 Broadway New York, NY 10271 Mayor, Village of Buchanan 236 Tate Avenue Buchanan, NY 10511 Mr. Ray Albanese Executive Chair Four County Nuclear Safety Committee Westchester County Fire Training Center 4 Dana Road Valhalla, NY 10592 Ms. Stacey Lousteau Treasury Department Entergy Services, Inc.

639 Loyola Avenue Mail Stop: L-ENT-15E New Orleans, LA 70113 Mr. William DiProfio PWR SRC ConsultaNT 139 Depot Road East Kingston, NH 03827 Mr. Dan C. Poole PWR SRC Consultant 20 Captains Cove Road Inglis, FL 34449 Mr. William T. Russell PWR SRC Consultant 400 Plantation Lane Stevensville, MD 21666-3232 Alex Matthiessen Executive Director Riverkeeper, Inc.

25 Wing & Wing Garrison, NY 10524

Paul Leventhal The Nuclear Control Institute 1000 Connecticut Avenue NW Suite 410 Washington, DC, 20036 Karl Copeland Pace Environmental Litigation Clinic 78 No. Broadway White Plains, NY 10603 Jim Riccio Greenpeace 702 H Street, NW Suite 300 Washington, DC 20001 Mr. Robert D. Snook Assistant Attorney General State of Connecticut 55 Elm Street P.O. Box 120 Hartford, CT 06141-0120