ML033090427

From kanterella
Jump to navigation Jump to search

Tech Spec Page for Amendment No. 219, Revising TS 5.5.10 to Adopt the Requirements of the American Society for Testing and Materials Standard D3803-1989
ML033090427
Person / Time
Site: Indian Point 
(DPR-064)
Issue date: 10/30/2003
From:
NRC/NRR/DLPM
To:
References
GL-99-002, TAC MB7224
Download: ML033090427 (1)


Text

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.10 Ventilation Filter Testing Program (VFTP)

(continued)

c.

Demonstrate for each system that a laboratory test of a sample of the charcoal adsorber shows the methyl iodide removal efficiency specified below when tested in accordance with ASTM D3803-1989, subject to clarification below, at relative humidity of 95%.

a temperature of 860F and a Methyl iodide ASTh D3803-1989 Ventilation System removal Clarification efficiency Fuel Storage Building 2 90 59 ft/min face velocity Emergency Ventilation System Control Room Ventilation 2 95.5 78 ft/min face velocity System Containment Fan Cooler 2 85 59 ft/min face velocity Units Containment Purge System 2 90 31 ft/min face velocity Note:

For the 1" beds, the Control Room Ventilation System methyl iodide removal efficiency is verified greater than or equal to 93%

rather than 95.5% at a face velocity of 50 ft/min under the above requirements.

This is done prior to fuel movement in Refuel Outage 12 and every 6 months after Refuel Outage 12 until the end of Refuel Outage 13 or the 2" beds are installed.

(continued)

INDIAN POINT 3 5.0 - 24 Amendment 219