Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.10 Ventilation Filter Testing Program (VFTP)

(continued)

c.

Demonstrate for each system that a laboratory test of a sample of the charcoal adsorber shows the methyl iodide removal efficiency specified below when tested in accordance with ASTM D3803-1989, subject to clarification below, at relative humidity of 95%.

a temperature of 860F and a Methyl iodide ASTh D3803-1989 Ventilation System removal Clarification efficiency Fuel Storage Building 2 90 59 ft/min face velocity Emergency Ventilation System Control Room Ventilation 2 95.5 78 ft/min face velocity System Containment Fan Cooler 2 85 59 ft/min face velocity Units Containment Purge System 2 90 31 ft/min face velocity Note:

For the 1" beds, the Control Room Ventilation System methyl iodide removal efficiency is verified greater than or equal to 93%

rather than 95.5% at a face velocity of 50 ft/min under the above requirements.

This is done prior to fuel movement in Refuel Outage 12 and every 6 months after Refuel Outage 12 until the end of Refuel Outage 13 or the 2" beds are installed.

(continued)

INDIAN POINT 3 5.0 - 24 Amendment 219