ML032020106

From kanterella
Jump to navigation Jump to search
Supplement to STP Commitment to Investigate and Repair Bottom Mounted Instrumentation Penetration Indications
ML032020106
Person / Time
Site: South Texas  
Issue date: 07/17/2003
From: Sheppard J
South Texas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NOC-AE-03001567, STI: 31633106
Download: ML032020106 (3)


Text

Nuclear Operating Company Soth rTe sfroectnea GbaqnStstlon PO. Oar 282 fdWh kw 77483 July 17, 2003 NOC-AE-03001567 U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852 South Texas Project Units 1 & 2 Docket Nos. STN 50-498, STN 50-499 Supplement to STP Commitment to Investigate and Repair Bottom Mounted Instrumentation Penetration Indications

Reference:

Letter, J. J. Sheppard to NRC Document Control Desk, "Additional Information Regarding STP's Commitment to Investigate and Repair Bottom Mounted Instrumentation Penetration Indications," dated July 11, 2003 (NOC-AE-03001557)

As a result of our meeting with the NRC today, this letter confirms that the following statements from the referenced letter are commitments made by STP Nuclear Operating Company:

STPNOC will take the following action to address the long-term management of potential BMI degradation:

Perform volumetric and enhanced visual examinations of the Unit 1 penetrations at the next in-service inspection of the Unit 1 reactor pressure vessel.

Perform ultrasonic examinations of the reactor pressure vessel base metal around the repaired penetrations at future selected Unit 1 refueling outages to confirm there are no indications of pressure vessel wastage from RCS water in the gap area of the repaired penetrations. The details of these examinations will be described in ASME Code relief requests for the repairs.

A#o STI: 31633106

NOC-AE-03001567 Page 2 of 3 Examine Unit 2 penetrations with a volumetric NDE method at the next Unit 2 refueling outage where the core barrel is planned to be removed (currently 2RE II scheduled for 2005).

STPNOC will not commence heat-up of STP Unit 1 to Mode 4 until it receives written confirmation from the NRC that all necessary NRC actions are complete.

If there are any questions regarding this supplemental information, please contact Mr. Mark McBurnett at 361-972-7206 or me at 361-972-8757.

fiJ.

ard President and Chief Executive Officer jtc

NOC-AE-03001567 Page 3 of 3 cc:

(paper copy)

(electronic copy)

Ellis W. Merschoff Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, Texas 76011-8064 U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852 Richard A. Ratliff Bureau of Radiation Control Texas Department of Health 1100 West 49th Street Austin, TX 78756-3189 Cornelius F. O'Keefe U. S. Nuclear Regulatory Commission P. O. Box 289, Mail Code: MN116 Wadsworth, TX 77483 A. H. Guttenman, Esquire Morgan, Lewis & Bockius LLP L. D. Blaylock City Public Service Mohan C. Thadani U. S. Nuclear Regulatory Commission R. L. Balcom Texas Genco, LP A. Ramirez City of Austin C. A. Johnson AEP Texas Central Company Jon C. Wood Matthews & Branscomb C. M. Canady City of Austin Electric Utility Department 721 Barton Springs Road Austin, TX 78704