ML031690063

From kanterella
Jump to navigation Jump to search
May 2003 Monthly Operating Report for Calvert Cliffs, Units 1 & 2
ML031690063
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 06/13/2003
From: Nietmann K
Constellation Energy Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML031690063 (7)


Text

Kevin J. Nietmann Plant General Manager Calvert Cliffs Nuclear Power Plant Constellation Generation Group, LLC 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410 495-4101 410 495-4787 Fax Constellation I

Energy Group June 13, 2003 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

SUBJECT:

Document Control Desk Calvert Cliffs Nuclear Power Plant Unit Nos. 1 & 2; Docket Nos. 50-317 & 50-3 18 May 2003 Operating Data Reports The subject reports are being sent to you as required by Technical Specification 5.6.4.

Should you have questions, please contact Mr. Thomas S. O'Meara at (410) 495-6940.

Very truly yours, A

KJN/CAN/bjd Attachments cc:

J. Petro, Esquire J. E. Silberg, Esquire Director, Project Directorate I-1, NRC G. S. Vissing, NRC H. J. Miller, NRC Resident Inspector, NRC R. I. McLean, DNR J. Wright, INPO K. N. Larson, ANI

e?-"

OPERATING DATA REPORT Docket No. 50-317 Calvert Cliffs Unit 1 June 4, 2003 Prepared by Herman 0. Olsen Telephone:(410)495-6734 REPORTING PERIOD DESIGN ELECTRICAL RATING (NET MWe)

MAXIMUM DEPENDABLE CAP'Y (NET MWe)

MAY 2003 845 825 This month Year -

to-Date Cumulative to Date

1. NUMBER OF HOURS REACTOR WAS CRITICAL
2. HOURS GENERATOR ON LINE
3. UNIT RESERVE SHUTDOWN HOURS
4. NET ELECTRICAL ENERGY GENERATED(MWH) 744.0 3,623.0 744.0 3,623.0 0.0 0.0 644,534 3,147,509 186,912.4 183,748.7 0.0 150,314,772

UNIT SHUTDOWNS DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 50-317 Calvert Cliffs - U1 June, 2003 Herman 0. Olsen (410) 495-6734 REPORTING MONTH May 2003

' Reason:

A - Equipment Failure B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training & License Examination F - Administrative G - Operational Error H - Other 2

Method:

I - Manual 2 - Manual Scram.

3 - Automatic Scram.

4 - Continued

- Other NO.

DATE TYPE DURATION REASON' METHOD OF CAUSE/CORRECTIVE ACTIONS F:

FORCED (HOURS)

SHUlTING S:

SCHEDULED DOWN 2 COMMENTS There were nio shutdowns this month.

DOCKET NO. 50-317 CALVERT CLIFFS - UNIT 1 June 5, 2003

SUMMARY

OF OPERATING EXPERIENCE May 2003 The unit began the month at 100% power.

Power was reduced to approximately 86% on 05/02/03 at 2200 for Main Turbine Valve Testing. Testing was completed and the unit was returned to 100% power on 05/03/03 at 0210.

The unit operated at 100% power for the remainder of the month.

OPERATING DATA REPORT Docket No. 50-318 Calvert Cliffs Unit 2 June 4, 2003 Prepared by Herman 0. Olsen Telephone:(410)495-6734 REPORTING PERIOD DESIGN ELECTRICAL RATING (NET Me)

MAXIMUM DEPENDABLE CAP'Y (NET MWe)

MAY 2003 845 835 This month

1. NUMBER OF HOURS REACTOR WAS CRITICAL
2. HOURS GENERATOR ON LINE
3. UNIT RESERVE SHUTDOWN HOURS
4. NET ELECTRICAL ENERGY GENERATED(MWH) 716.9 712.5 0.0 613, 526 Year-Cumulative to-Date to Date 2,030.0 1,996.5 0.0 1,707,408 179,589.8 177,701.2 0.0 146,293,838

UNIT SHRTDOWNS DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 50-318 Calvert Cliffs-U2 June 5, 2003 Herman 0. Olsen (410) 495-6734 REPORT MONTH May 2003

' Reason:

A - Equipment Failure B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training & License Examination F - Administrative G - Operational Error H - Other 2 Method:

I - Manual 2 - Manual Scram.

3 - Automatic Scram.

4 - Continued 5 - Other NO.

DATE TYPE DURATION REASON' METHOD OF CAUSE/CORRECTIVE ACTIONS F:

FORCED (HOURS)

SHUTTING S:

SCHEDULED DOWN 2 COMMENTS03-002 030528 F

31.5 B

3 On 05/28/03 at 1134 an automatic trip occurred from 100% power. The trip was caused by a short circuit that was created while connecting the test equipment used for trouble shooting in an instrument cabinet. The trouble shooting was being perfonned to determine the cause of and to correct the Main Turbine Governor Valve oscillations. The unit was brought to a safe shutdown condition in Mode 3. Testing was performed to verify the exact cause of the trip. The unit was returned to service on 05/29/03 at 1903. The immediate corrective action was to suspend trouble shooting of the valve oscillation problem and require management approval for any on-line maintenance performed in the affected cabinets. A detailed root cause analysis and a Licensee Event Report (LER) are in progress.

r

DOCKET NO. 50-318 CALVERT CLIFFS - UNIT 2 June 5, 2003

SUMMARY

OF OPERATING EXPERIENCE May 2003 The unit began the month at 100% reactor power.

On 05/28/03 at 1134 an automatic reactor trip from 100% power occurred. The trip was caused by a short circuit that was created when connecting the test equipment that was being used for trouble shooting in an instrument cabinet. The unit was taken critical on 05/29/03 at 1442 and was paralleled to the grid at 1903. The unit reached 100% on 05/30/03 at 0400.

The unit continued to operate at 100% power for the remainder of the month.