June 13, 2003 Mr. Thomas Coutu Site Vice President Kewaunee Nuclear Power Plant Nuclear Management Company, LLC N490 State Highway 42 Kewaunee, WI 54216

SUBJECT:

KEWAUNEE NUCLEAR POWER PLANT - REQUEST FOR ADDITIONAL INFORMATION FOR PROPOSED AMENDMENT REQUEST, CHANGES TO STEAM GENERATOR INSPECTION REPORTING CRITERIA (TAC NO. MB6993)

Dear Mr. Coutu:

By letter dated December 19, 2002, Nuclear Management Company, LLC (NMC or the licensee) submitted a request for a proposed amendment to revise the Kewaunee Nuclear Power Plant technical specifications regarding changes to the steam generator inspection reporting criteria.

The Nuclear Regulatory Commission staff finds that the additional information identified in the enclosure is needed.

A draft of the request for additional information was e-mailed to Mr. G. Riste (NMC) on March 19, 2003.

A phone call was held between G. Riste (NMC) and myself on June 9, 2003, to discuss the questions to ensure that there was no misunderstanding. Also, the phone call established a mutually agreeable response date of 30 days from the date of this letter.

Please contact me at (301) 415-1446 if future circumstances should require a change in this response date.

Sincerely,

/RA/

John G. Lamb, Project Manager, Section 1 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-305

Enclosure:

Request for Additional Information cc w/encl: See next page

June 13, 2003 Mr. Thomas Coutu Site Vice President Kewaunee Nuclear Power Plant Nuclear Management Company, LLC N490 State Highway 42 Kewaunee, WI 54216

SUBJECT:

KEWAUNEE NUCLEAR POWER PLANT - REQUEST FOR ADDITIONAL INFORMATION FOR PROPOSED AMENDMENT REQUEST, CHANGES TO STEAM GENERATOR INSPECTION REPORTING CRITERIA (TAC NO. MB6993)

Dear Mr. Coutu:

By letter dated December 19, 2002, Nuclear Management Company, LLC (NMC or the licensee) submitted a request for a proposed amendment to revise the Kewaunee Nuclear Power Plant technical specifications regarding changes to the steam generator inspection reporting criteria.

The Nuclear Regulatory Commission staff finds that the additional information identified in the enclosure is needed.

A draft of the request for additional information was e-mailed to Mr. G. Riste (NMC) on March 19, 2003.

A phone call was held between G. Riste (NMC) and myself on June 9, 2003, to discuss the questions to ensure that there was no misunderstanding. Also, the phone call established a mutually agreeable response date of 30 days from the date of this letter.

Please contact me at (301) 415-1446 if future circumstances should require a change in this response date.

Sincerely,

/RA/

John G. Lamb, Project Manager, Section 1 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-305

Enclosure:

Request for Additional Information cc w/encl: See next page DISTRIBUTION:

PUBLIC OGC THarris LRaghavan PD III-1 R/F JLamb ACRS PLouden, RIII ACCESSION NO. ML031640206 OFFICE PDIII-1/PM PDIII-1/LA PDIII-1/SC NAME JLamb THarris LRaghavan DATE 06/13/03 06/13/03 06/13/03 OFFICIAL RECORD COPY

REQUEST FOR ADDITIONAL INFORMATION (RAI)

REGARDING PROPOSED AMENDMENT ON CHANGES TO THE STEAM GENERATOR INSPECTION REPORTING CRITERIA KEWAUNEE NUCLEAR POWER PLANT DOCKET NO. 50-305 In letter dated December 19, 2002, Nuclear Management Company (NMC) submitted changes to the technical specifications (TSs) for the Kewaunee Nuclear Power Plant. NMC proposed to change: (1) the tube plugging reporting requirement from the current 30 days to 60 days in TS 4.2.b.7.a and (2) the C-3 category notification from 10 CFR 50.72(b)(2)(ii) to 10 CFR 50.72(b)(3)(ii) in TS 4.2.b.7.c. To complete its review, the U.S. Nuclear Regulatory Commission (NRC) staff requests the following additional information:

1.

In the proposed TS 4.2.b.7.a, it is stated that...Following each in-service inspection of steam generator tubes during which tubes are plugged, the number of tubes plugged shall be reported to the Commission within 60 days... The current TS requires a 30-day reporting period. The licensee proposed the 60-day reporting requirement to be consistent with 10 CFR 50.73, License Event Report System.

Please provide a technical basis for the proposed change: (a) Please cite the specific subparagraph in 10 CFR 50.73 that is applicable to the tube plugging report and explain why that subparagraph is applicable, and (b) 10 CFR 50.73 requires that licensees submit a license event report within 60 days of the discovery of an event. Please clarify when the 60-day period starts, e.g., from the completion of the eddy current data analysis of the steam generator inspection results, completion of the tube plugging effort, restart of the unit, or, closure of the steam generator manways.

2.

In the proposed TS 4.2.b.7.c, it is stated that...If a steam generator tube inspection result falls into Category C-3, the Commission shall be promptly notified according to requirements of 10 CFR 50.72(b)(3)(ii)... This will change the 4-hour notification in the current TS to the 8-hour notification as specified 10 CFR 50.72(b)(3)(ii).

Please provide a technical basis for extending the notification from 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> to 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />s:

(a) Please cite the specific subparagraph in 10 CFR 50.72(b)(3)(ii) that is applicable to the C-3 category notification and to explain why the subparagraph is applicable, (b) The NRC staff believes that 10 CFR 50.72(c), Followup Notification, is also applicable to the C-3 category notification. Explain why was 10 CFR 50.72(c) not cited in the proposed TS 4.2.b.7.c, and (c) Confirm that when a C-3 category is established, the licensee is required by 10 CFR 50.73, Licensee event report system, to submit a written license event report.

ENCLOSURE

Kewaunee Nuclear Power Plant cc:

John Paul Cowan Chief Nuclear Officer Nuclear Management Company, LLC 27780 Blue Star Memorial Highway Cover, MI 49043 Kyle Hoops Plant Manager Kewaunee Nuclear Power Plant N490 Highway 42 Kewaunee, WI 54216-9511 Gordon P. Arent Manager, Regulatory Affairs Kewaunee Nuclear Power Plant N490 Highway 42 Kewaunee, WI 54216-9511 David Molzahn Nuclear Asset Manager Wisconsin Public Service Corporation 600 N. Adams Street Green Bay, WI 54307-9002 Thomas Webb Nuclear Asset Manager Wisconsin Public Service Corporation 600 N. Adams Street Green Bay, WI 54307-9002 Resident Inspectors Office U. S. Nuclear Regulatory Commission N490 Hwy 42 Kewaunee, WI 54216-9510 Regional Administrator Region III U. S. Nuclear Regulatory Commission 801 Warrenville Road Lisle, IL 60532-4351 Jonathan Rogoff, Esquire General Counsel, Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 Larry L. Weyers Chairman, President and CEO Wisconsin Public Service Corporation 600 North Adams Street Greey Bay, WI 54307-9002 David Zellner Chairman - Town of Carlton N2164 County B Kewaunee, WI 54216 Sarah Jenkins Electric Division Public Service Commission of Wisconsin PO Box 7854 Madison, WI 53707-7854