US NRC ST LUCIE RESIDENT Operations Department Chronological Log Unit 2 4-Apr-02 10:30 Received ANN-34 'GAS ANNALYZERS TROUBLE" SNPO reports while changing a light bulb the light socket grounded and caused a power supply failure for the AUTO GAS ANNALYZER. Entered ONOP 2-0530030.

Contacted I&C toinvestigate and notified chemristry to perform grab samples every24 hours. Entered UFSAR 13.7.1-5.

10:35 Declared the SGTBF radation monitor RM-45-1 OOS for chemisrty sample. Entered Tech Specs 3.3.3.1 table 3,3-6#2Ciiaction 27also entered Offsite Dose Calculation Manual 3.3.3.108 #6 action 47 and 51.

11:05 Declared the BLOWDOWN BUILDING radation monitor RM-45-1 Back In Service. Chemisrty sample compicte.

Exited Tech Specs 3.3.3.1 B table 3.3-6 #2Ciii acUon 27 also exited Offsite Dose Calculation Manual 3.3.3.10 B

  1. 6 action 47 and 51 11:30 Declared the Plant Vent WRGM RIM-26-90 Back in Service. Completed I&C functional test in accordance with 2-IMP-26.02. Exited Tech Specs 3.3.3.1 B table 3.3-6 #2Cii action 27.

11-.40 Completed the 2B EDG periodic test. Stopped the 2B EDG. Notified Maint and Chemistry to collect the appropriate samples.

12:00 Declared the 2B EDG Back In Service.

11:45 (Late Entry) Placed Clearance order 2-02-04-071 on 2-MV-08-19B B side ADV to replace the modutronics unit.

ADV already OOS. OOS log entry #6833.

12:45 Replaced blovn fuses and declared the Auto Gas Analyzer Back In Service. Exited ONOP 2-0530030 and UFSAR spec 13.7.1 -5. Notified Chemistry to cancel 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> grab samples.

13:00 Placed the Ax Feedwater Actuatlon System in a two of three logic for &C replacement of the B Chan bistable switch. Entered Tech Specs 3.3.2 table 3.3-. #7 actlon 12(48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />).

13:30 Notiried the NRC of an Injured sea turle requiring rehabilitation that was rescued from the Intake and transported offsite. The notiication to the NRC was nade because the Stale was Notified.

13:42 Declared the SGBTF radiation monitor Rm-45-1 OOS for an &C functional test to be performed in accordance with 2-IMP-26.05. Entered Tech Specs 3.3.3.1 B table 3.3-6 #2Ciii action 27 also entered Offsite Dose Calculation Manual 3.3.3.10 8 #6 action 47 and 51.

14:45 Declared the SGBTF radia:lon monitor Rm-45-1 Back In Service. I&C functional test completed in accordance vwith 2-IMP-26.05. Exited Tech Specs 3.3.3.1 B table 3.3-6 #2Ciii action 27 also exited Offsite Dose Calculation Manual 3.3.3.10 B #6 action 47 and 51.

16:10 ANPO reports started AUX HYPO to the Unit 2 Circ wells.

18:05 ANPO reports completed AUX HYPO to the Unit 2 Circ wells.