Technical Specification for Amendment No. 154, Refueling Equipment Interlocks, 3.9.1, S106973
ML031210562
Person / Time
Site: Fermi DTE Energy icon.png
Issue date: 04/28/2003
From:
NRC/NRR/DLPM
To:
Stang J
References
TAC MB6387
Download: ML031210562 (2)


Text

Refueling Equipment Interlocks 3.9.1 3.9 REFUELING OPERATIONS 3.9.1 Refueling Equipment Interlocks LCO 3.9.1 APPLICABILITY:

The refueling equipment interlocks associated with the refuel position of the reactor mode switch shall be OPERABLE.

During in-vessel fuel movement with equipment associated with the interlocks when the reactor mode switch is in the refuel position.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Suspend in-vessel Immediately refueling equipment fuel movement with interlocks inoperable.

equipment associated with the inoperable interlock(s).

OR A.2.1 Insert a control rod Immediately withdrawal block AND A.2.2 Verify all control Immediately rods are fully inserted.

FERMI - UNIT 2 3.9 -1 Amendment No. j04, 154