FENOC

_t&UNd Perry Nuclear Power Plant 10 Center Road Perry, Ohio 44081 James R. Hayes Manager - Radwaste. Environmental, Chemistry 440-280-7519 Fax: 440-280-5681 April 22, 2002 PY-CEIIOEPA-0398L Ohio Environmental Protection Agency Division of Surface Water P. O. Box 1049 Columbus, OH 43216-1049 Ladies and Gentlemen, The Perry Nuclear Power Plant (PNPP) has been unsuccessful in the cleaning of air conditioning cooling coils using water without detergents as required by National Pollutant Discharge Elimination System Permit 3IB00016*GD. To prevent the costly replacement of several units, PNPP is requesting a one-time approval for the us~eCIP 300 Neutral pH Cleaner. The MSDS for CIP 300 is attached and is proposed to be used as follows:

1) PNPP will clean no more than 30 air conditioning units.
2) PNPP will use approximately 2 gallons of diluted product per unit.
3) Product will be limited to a maximum of 5% concentration for use.
4) Each unit will be rinsed with a minimum of 10 gallons of water.

Under the above guidelines, the product effluent to the storm drains will be a maximum of 1% CIP 300.

Based on the MSDS aquatic toxicology, the use under the above guidelines should not be harmful to aquatic life.

PNPP hopes to continue the cleaning of the cooling coils as soon as possible, and appreciates your attention to this matter. If you have any questions or require additional information, please contact Mr. Leo Harte at (440) 280-5514.

Very Truly Yours, Attachments cc:

OEPA Northeast District Office NRC Region El NRC Resident Inspector NRC Project Manager NRC Document Control Desk (Docket No' 50-440)

p.

1 mac, CC<,*/zX &i M I/

(7 7

,'A-_

'5 C4ac,;-jo 5i>67J.

c_1' 5J

+L H cL-ne 5X AIGear.

Z

(-" toN4 CLEP9A4F, STE RI S STERIS Corporation NoUh Anades al

- Scliific 980 maaley Road a"4or.

01144060.-134 -USA 4410-34-9600 - 000-444-9.r Neil Hanson Sa8 Re.'eentatlv.

Pax 57423-3580 E-Mlil n"L"naon@iterh..oom Voic-maR 800-889-7575, E,. 23007 CIP 300 is designed to be low-foaming at all use temperatures, from ambient to boiling. Typical use-concentrations for CIP 300 alone will range from 1-6 oz/gal (0.8-4.7 percent V/v). depending upon residue type. residue load, available water temperature and time allotted for cleaning.

For nigh melting point hydrocarbon-type residues (waxes. petrolatums. etc.). CIP 300 can be used to boost the effective-ness of other cleaning products. Its superior dispersive properties provide emulsification power to tackle these tough-to-remove residues.

A titration for use-concentration determination (Test Kit E0141 1).

See your local STERIS sales representative for methods for testing of residuals of CIP 300.

STORAGE AND DISPOSAL Storage This product should be stored in an area where it will not be exposed to extreme temperatures. Product may freeze. Swirls and precipitate may occur in frozen material, but readily go into solution when Ihawed and mixed.

Disposal Flush with plenty ot water to the sanitary sewer. Dispose of In accordance with local. state. and federal regulations.

\\ I SAFETY DATA SHEET S I'L RI S

1. identificatIon of the Substance end Company CIP 300 Product No. 1030 NFPA 70JIHAZARDRA17NG:

MSDS No. 1D03 HEALTH:

FIRE:

1 Prepared by M. Ebers REACTVITY:

0 Date Created: December 1, 2001 Date Revised: NA STERIS Corporation. P.O. Box 147, St Louis. MO 63166. US Emergency Telephone No.1-314.535-1395 (STERIS): 1-800424-9300 (CHEMTREC)

Telephone Number for Information: 1400-444.9009 (Customer Sarvice-Serenlific Products)

STERIS Limited, STERIS House, Jays Close, Viables, Basilngstoke. Hampshire, RG22 4AX. UK Emergency Phone No: U44 (0) 1895 622639 ProductJTeclinlcal information Phone No: *44 (0) 1256 840400 2 Compositlonhlnformntion on Inredients Hazardous Cmponsnt(tl EEC NIL CAI N.

%UeyWL Iymbol N

P reees Acooradinrgto HAHeard omunicarionSteandar,,29CfFRt1910.12

,hPMLductconinnohoanbetormagdenbt.

Acording to the Controt Prodrts Rgristionsn tis product coatins no hazardous Irgrediorns.

Non of Ihs Ingrednta tl intbto any cisstitndon required undor the CilP Rulations at the Concentrations Present.

3. Hazards Identification NA
4. FIrst Aid Measures Eye

Contact:

Flush eyes immediately with water for at least 15 mInutes. Gel medical attention if Irritation develops.

Skin

Contact:

Flush skin irnmedlately with water hor at least 15minutes. Get medical attention Il Irrilation develops.

Inhalation: Remove patient to fresh air. If not breathing, give argriicis respiration. Get medical attention.

Ingestion: Do nol induce vomiting. Got modical atantion. Do not give anything by mouth to en unconscious person. Ufconsdous, drinkalargequanIyofmikorwater.

S. Fiwe.Flghtlng Measures Flash Point: Not flammable Special Hazards: None known Extingulehing Media: Suitable for surrounding fire.

Special Fire Fighting Procedures: Use caution whsn fighing any fire Involving chemicals. A self-contained breathing apparatus is essential.

6. Accidental Release Meaures Spitis maybe picked upwith a mop end folowed byewate rinse. Sni spit msaybe flushed to a sanitaryswr with copious amounts o water.

T. HandlIng and Storage 7.1 HandlIng Avoid wontai vwith eyes skIn and dothing. Keep container closed. Wash thoroughly after handflng. For ldusttle use only.

7.2 Storage Store in a cool, well ventilated area.

. Exposure Controwersonal Protection 8.1 Occupattonal Exposure Limits No chemIcal is present which requires statutory control.

s.2 Personal Protection Respirator Protercton: Not normnany required.

Eye Protecthon Safety glasses or goggles.

Protective Gloves: Rubber.

Other Protective ClothIng and Equipment: NA Ventilation: Normal.

P. Physical and Chemical Properties Solubility In Waler: Complete Specific Gravity. Approximately 1.04 Appeiranceddor: Colorless to light strew, viscous liquldrnild odor.

pH: Appronimately 7.8-8.1

10. Stability end Reactivity Stability Stable Hazardous Potymerlzatlon: Wit not occur.

Incompetible Materiels Strong alkalis and oxidizers.

Conditions to Avoid. None known.

Hazardous Decomposlnlon or Byproducte: CO) and CO.

11. Toxicological Informatlon 11.1 Acute (Primary Routes of Exposure)

Eyes: May result In temporary Irritation.

Skin: Prolonged or repealed skin contact may cause IrrHation.

Ingepaeon: May euse gastric upset, pn and diarrhea.

11.2 Long Term Exposure None known.

Carclnogenolqct IARC, NTP and OSHA do not list this product or its Ingredients as carcinogens.

12. EcologIcal Infornatlon Aquatic ToxlctV. 10% vh solution: LCSO (fathead minnows)
  • 750 mgfml
13. Disposel Con siereljons Product may be flushed to a sanitary sewer witi copious amounts of water, If in accordance with stM local and federal regulations. For additIonal guidance, contact ths State Water Board or the Regional Offie of the EPA
14. Transport Information Ground: Non-hazardous Sea: IMGD Clasn Non-hazardous Air: ICAOJIATA Class: Non-hazardous
15. Regulatory Information None avellable
16. Other iformation The Information on this sheet Is not a apecslion and doe not guarantee spefic properties. The informellon Is Inended lo provide general knowledge as to health nd saety based upon our knowledge ofthe handling, storage end use of the product It Is not applicable to unusual or non-standard uses of the product or where inetrunion or recommendations anr not followed.

NA-Not Applicable ND -No Date

-a

p. 3 STERI S' CIP 30W NEUTRAL pH CLEANER TECHNICAL DATA GENERAL DESCRIPTION CIP 300 is a phosphate-free neutral pH liquid detergent and detergent additive. Its unique blend of surfactants allows it to be used alone or with existing cleaning products to boost their cleaning power. This low-foaiming product is ideal for use in recirculating wash systems (automated CIP. parts washers, etc.). Although low-foaming, it retains the cleaning pertor-mance of high-foaming cleaners and can also be used in manual cleaning applications. As a stand alone detergent, it will have a use and discharge pH between 6 and 9 (this will be affected by the pH of the mix water). CIP 300 is tree of perfumes and dyes, and is safe for use on aluminum and other soft metals.

FEATURES BENEFITS Neutral pH between 6 and 9 No need to neutralize before disctiarge to sewer Low-foarming at all use temperatures Easy rinsing; also, will not cavitate recirculation pumps Detergent booster Improves cleaning performance when added to existing products PHYSICAL PROPERTIES Form.....................

Slight yellow, clear liquid Odor Mild Specific gravity (77 F (250C])

................... 1.04. typical pH (undiluted) 7.8, typical Foam.....................

Low Phosphates........................................................................... None DIRECTIONS FOR USE CIP 300 is designed to be low-foaming at all use temperatures, from ambient to boiling. Typical use-concentrations for CIP 300 alone will range from 1-6 oz/gal (0.8-4.7 percent v/v), depending upon residue type. residue load, available water temperature and time allotted for cleaning.

For high melting point hydrocarbon-type residues (waxes, petrolatums, etc.), CIP 300 can be used to boost the effective-ness of other cleaning products. Its superior dispersive properties provide emulsification power to tackle these tough-to-remove residues.

A titration for use-concentration determination (Test Kit EQ1411).

See your local STERIS sales representative for methods for testing of residuals of CIP 300.

STORAGE AND DISPOSAL Storage This product should be stored in an area where it will not be exposed to extreme temperatures. Product may freeze. Swirls and precipitate may occur in frozen material, but readily go into solution when thawed and mixed.

Disposal Flush with plenty of water to the sanitary sewer. Dispose of in accordance with local, state, and federal regulations.

410-100-1D30(10199)

_