3/4 LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE REQUIREMENTS 3/4.7 PLANT SYSTEMS 3/4.7.5 CONTROL ROOM VENTILATION SYSTEM CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.5.1 The control room emergency ventilation system (CREVS) shall be OPERABLE with:

a.

Two independent pressurization trains, and

b.

One charcoal adsorber/HEPA filter unit.

The control room envelope/pressure boundary may be opened intermittently under administrative control.

APPLICABILITY:

MODES 1, 2, 3, 4, and during the movement of irradiated fuel assemblies.

ACTION:

MODES 1, 2, 3, and 4:

a.

With one pressurization train inoperable, restore the inoperable train to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With the filter unit inoperable, restore the filter unit to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With two CREVS pressurization trains inoperable due to an inoperable control room envelope/pressure boundary, restore the control room envelope/pressure boundary to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

During the movement of irradiated fuel assemblies:

d.

With one pressurization train inoperable, restore the inoperable pressurization train to OPERABLE status within 7 days, or initiate and maintain operation of the remaining OPERABLE train in the pressurization/cleanup alignment.

e.

With any of the following: (1) both pressurization trains inoperable; (2) the filter unit inoperable; or (3) the control room envelope/pressure boundary inoperable, immediately suspend all operations involving the movement of irradiated fuel assemblies.

f.

The provisions of Specification 3.0.4 are not applicable to movement of irradiated fuel assemblies.

COOK NUCLEAR PLANT-UNIT 2 Page 3/4 7-14 AMENDMENT 44-3, Aim, 258

3/4 LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE REQUIREMENTS 3/4.7 PLANT SYSTEMS 3/4.7.5 CONTROL ROOM VENTILATION SYSTEM CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMMING CONDITION FOR OPERATION 3.7.5.1 The control room emergency ventilation system (CREVS) shall be OPERABLE with:

a.

Two independent pressurization trains, and

b.

One charcoal adsorber/HEPA filter unit.

The control room envelope/pressure boundary may be opened intermittently under administrative control.

APPLICABILITY:

MODES 1, 2, 3, 4, and during the movement of irradiated fuel assemblies.

ACTION:

MODES 1, 2, 3, and 4:

a.

With one pressurization train inoperable, restore the inoperable train to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With the filter unit inoperable, restore the filter unit to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With two CREVS pressurization trains inoperable due to an inoperable control room envelope/pressure boundary, restore the control room envelope/pressure boundary to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

During the movement of irradiated fuel assemblies:

d..

With one pressurization train inoperable, restore the inoperable pressurization train to OPERABLE status within 7 days, or initiate and maintain operation of the remaining OPERABLE train in the pressurization/cleanup alignment.

e.

With any of the following: (1) both pressurization trains inoperable; (2) the filter unit inoperable; or (3) the control room envelope/pressure boundary inoperable, immediately suspend all operations involving the movement of irradiated fuel assemblies.

  • f The provisions of Specification 3.0.4 are not applicable to movement of irradiated fuel assemblies.l COOK NUCLEAR PLANT-UNIT 1 Page 3/4 7-19 AMENDMENT 4159, A4, 276