ML031080534

From kanterella
Jump to navigation Jump to search
Two 18 Ultrasonic Flowmeters Serial Numbers Wmp 2, & Wmp 3, Westinghouse Electric Corporation Purchase Order Number 87GC-WJ-47042
ML031080534
Person / Time
Site: Indian Point Entergy icon.png
Issue date: 04/10/2003
From:
Worcester Polytechnic Institute
To:
Office of Nuclear Reactor Regulation
References
Download: ML031080534 (33)


Text

CALIBRATION INDIAN POINT TWO 18" ULTRASONIC FLOWMETERS SERIAL NUMBERS WMP.2, and WPP #3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 MAY, JUNE 1979 -

ARL NO. 106-79/C91 121 HUH.

.. 1.,

.4.

___ =.

=

A>.

1

-_ 4.

v.

SUMMARY

Two 18" Ultrasonic Flowmeters, Serial Numbers WMP #2 and WMP #3, were calibrated at the ALDEN RESEARCH LABORATORY of Worcester Polytechnic Institute for WESTINGHOUSE ELECTRIC CORPORATION under their Purchase Order Number 87GC-WJ-47042.

Both 18" ultrasonic flowmeters were calibrated using straight pipe configurations. The details of the piping immediately upstream and downstream of the ultrasonic meters are shown on the piping diagram.

The results are presented in the form of a tabulated data sheet as well as a plot of the average temperature and pressure corrected mean meter factor (T,P) versus the average flow rate (q) in cubic feet per second or pounds per hour.

The flow meters were calibrated at seven flow rates ranging from 5 to-35 cubic feet per.second, or 1 to 7.7 million pounds per hour.

Tests 1 and 4 in May, 1979 identified a scaling error of approximately 0.45% which was corrected for Tests 5 and 6 conducted in June, 1979.

The error was determined to be due to incorrect placement of the paths in the LEFM meter section.

f-

SUMMARY

WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 TEST NUMBER 1 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #2 Average Flow Rate cfs.

DATE:

24 MAY 1979 Average Corrected Mean Meter Factor (T,P)

First Series of Seven Flows Second Series of Seven Flows 34.812 29.791 24.554 19.970 14.795 9.956 4.839 0.9941 0.9956 0.9958 0.9955 0.9960 0.9958 0.9957

,4.825 9.975 14.909 19.997 24.815 29.719 34.726 0.9934 0.9967 0.9968 0.9964 0.9962 0.9964 0.9964 Data includes 0.45% error due to path misplacement AME, -S I_~

SUMMARY

WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 TEST NUMBER 4 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 (WITHOUT DAMPING)

DATE:

23 MAY 1979 Average Flow Rate cfs.

Average Corrected Mean Meter Factor (T,P)

First Series of Six Flows 34.463 29.480 24.557 19.816 14.686 10.0485 0.9900 0.9901 0.9919 0.9917 0.9939 0.9942 l

Second Series of Six Flows 10.055 14.992 19.809 24.837 29.538 34.845 0.9947 0.9926 0.9913 0.9917 0.9922 0.9936 Third Series of One Flow 14.710 0.9935 Data includes 0.45% error due to path misplacement

-- -- -b -

4' A

W

-4I

-A--

page 1 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 ARL DATA WESTINGHOUSE DATA Test Run No.

No.

Line Temp 0 F Pressure Downstream psi:

Wreight W

lbs.-

Time t

sec.

Flow q

cfs.

Average LEFM Flow Mean Meter Factor Corrected Mean Meter Factor (T,P) 3 Sig %

First Series of Seven Flows 5-5 5

5 5

5 5

5 5,

5 5

5 5

5 5

5 5

1 2

3 4

5 6

7 8

9 10 11 12 13 14 15 16 17 104 104 104 104 104 104 104 104 104 104 104 105 105 105 105 105 105 42 42 42 42 42 42 48 48 48 48 48 58 58 58 58 58 58 98174 96951 96971 97297 97164 97265 96687-96799 96758 96839 96534 96122 96077 96097 95995 95731 95772 45.325 44.828 44.869 45.045 45.019 45.075 51.957 52.074 52.095

52. 124
51. 983 61.889 61.860 61.913 61.881 76.492
76. 600 35.020 -

34.967 34.942 34.923 34.895.

34.888 30.087 30.054 30.029 30.038 30.024 25.116

25. 116
25. 100 25.086
20. 239
20. 219 34.9257 34.8728 34.8410 34.8811 34.8462 34.8184 30.0239 29.9850 29.9930 29.9392 29.9402 24.9637 24.9737 24.9801 24.9513
20. 1463 20.1384 1.0029 1.0030 1.0032 1.0014 1.0016 1.0022 1.0024 1.0025 1.0014 1.0035 1.0031 1.0064 1.0060 1.0051 1.0057 1.0049 1.0043 1.0027 1.0027 1.0029 1.0012 1.0014 1.0020 1.0021 1.0023 1.0012 1.0033 1.0028 1.0061 1.0057 1.0048 1.0054 1.0046 1.0040 0.617 0.565 0.556 0.550 0.580 0.492 0.578 0.656 0.942 0.484 0.571 0.719 0.558 0.467 0.627 0.779 0.617 I

Im

a64,-

-r4

- - - -- -.4

. z l -

l 2-f page 2 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 ARL DATA WESTINGHOUSE DATA ------------

Test Run No.

No.

Line Temp OF Pressure Downstream psi Weight W;

lbs.

Time t

sec.

Flow q

cfs. -

Average LEFM Flow Mean Meter Factor Corrected Mean Meter Factor (T,P) 3 Sig %

5 18 5

19 5

20 5

21 5

22 5

23 105 105 105 105 105 105 58 60

  • 60 60 60 60 95741 95310 95294 94959 94887 94846 76.632 102. 170 102.426 152.586 152.595 310.097
20. 204 15.085 15.045 10.064 10.056 4.946 20.1235 14.9593 14.9389 9.9535 9.9505 4.9038 1.0044 1.0087 1.0074 1.0114 1.0109 1.0089 1.0041 1.0084
1.

0071 1.0111 1.0106 1.0086 0.939 0.741 0.800 0.993 1.031 1.780 Second Series of Seven Flows 5

24 5

25 5

26 5

27 5

28 5

29 5

30 5

31 5

32 5

33 105 106 106 106 106 106 106 106 106 106 60 60 60 60 60 58 58 58 58 58 94846 95173 95060 95289 95442 95457 95853 95498 96027 96057 313. 548 154.592 154. 283 102.256 102.461 76.220 76.498

76. 275 62.093 62.082 4.892 9.958 9.966 15.073 15.067
20. 257 20.267 20.251
25. 014 25.027 4.9305 9.9421 9.9441 15.0534 15.0504 20.2813 20.2913 20.2916 25.0365 25.0320 0.9925 1.0019 1.0025 1.0016 1.0014 0.9992 0.9991 0.9983 0.9994 1.0001 0.9922 1.0016 1.0022 1.0013 1.0011 0.9988 0.9988 0.9980
0. 9991
0. 9998 1.860 1.018 0.833 0.642 0.899 0.774 0.539 0.816 0.453 0.567

SUMMARY

WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 TEST NUMBER 5 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 L

.L Average Flow Rate (cfs.)

Average Corrected Mean Meter Factor (T,P)

First Series of Seven Flows 34.939 30.046

25. 105 20.221 15.065 10.060 4.946 1.0022 1.0023 1.0055 1.0042 -

1.0078 1.0109 1.0086 Second Series of Seven Flows 4.892 9.962 15.070

- 20.258 25.014 29.901 34.788 0.9922 1.0019 1.0012 0.9985 1.0000 0.9973 0.9975 i

mma

SUMMARY

WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 TEST NUMBER 6 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 Average Flow-Rate lbs/hr x 106 Mean Meter Factor First Series of Seven Flows Second Series of Seven Flows 7.763

'6.628 5.575 4.476 3.277 2.207 1.089 0.9970 0.9984 1.0019 1.0000 1.0029 1.0013 0.9820 1.098 2.205 3.326 4.426 5.496 6.602 7.726 0.9933 1.0000 1.0021 0.9998 1.0028 1.0003 1.0002

APPARATUS 100,000-POUND WEIGHING TANK FACILITY 36" TEST LINES The flow element was installed in a test line on the main floor of Laboratory Building No. 1 as shown on the Laboratory sketch.

Water for the tests was pumped from a 180,000-gallon capacity sump by means of one (or two) 300-horsepower centrifugal pump(s) arranged to operate in parallel.

The piping arrangement immediately upstream and downstream of the element to be tested is shown on the piping diagram.

Careful attention was paid in aligning the flow element in the pipe.

Vents were provided at various intervals in the pipe to purge the system of air.

The flow rates were obtained by means of a weigh tank mounted on Toledo scales with a capacity of 100,000 pounds, BLH Load Cell Back-up, a Hewlett-Packard "5300A" measuring system crystal reference timer using a 5301A 10 MHZ Frequency Counter Module, A Toledo Systems Crystal Reference Timer as a back-up timer, and a mercury thermometer.

.I h

/

I r r-

. r-K.I..-. r..

I-1 TEST LINE 1 1

Timor Switch 0

i I

I I

I I

I I

TEST LINE 3 High Head Line

_I I

Sump Il L.

Breakdown Valves Scale Sump 10,000 Lb.

Weighing Tank Manifold 0

5 10 L

I I

15 30 I

i I

CALIBRATION FACILITIES LABORATORY BUILDING NUMBER 1

SCALE - FEET

-i Fr -

r--

I -

F 7 r--

F--

F--

r--

Fr

- r-.

r,--

- -

-- l- -

PLAN VIEW B.UILDING 1, LINE 2 36 x 24

-FLOW STRAIGHTENER 18 x 24

/

24 x 20 7-20 x 18 DRESSER COUPLINGS 36" 27' 2'

1 PIPING DIAGRAM TWO 18" ULTRASONIC FLOWMETERS WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 JUNE 1979

PROCEDURE After the LEFM had been installed in the test line, water was pumped into the system and all air was purged from the lines.

The control valve at the downstream end of the test line was set to give the desired flow rate with the discharge being diverted to the sump.

When steady state conditions were reached, the discharge valve on the weighing tank was closed and the scale indicator and the electronic timer were both zeroed. The water was then diverted to the weighing tank and the electronic timer and the Westinghouse readout on the Indian Point LEFM were actuated at the instant of diversion.

At the end of the run the water was diverted to the sump and the electronic timer and the LEFM readout were stopped, terminating the test run.

The accumulated weight in the tank, the time, the water temperature, and the readout data were recorded.

The flow was then adjusted to the next desired flow rate and the procedure repeated.

Testing on the 18" pipe section and LEFM was done at seven flow rates of 35, 30, 25, 20, 15, 10, and 5 cubic feet per second. In order to accumulate enough data from the LEFM, at least six weigh tank readings were done at 35 cfs, five at 30 cfs, four at 25 cfs, three at 20 cfs, three at 15 cfs, two at 10 cfs, and one at 5 cfs.

This combined testing procedure was called a series of seven flows in this report.

The following table summarizes the number of tests that were conducted on the 18" pipe sections and Indian Point LEFM.

Test Flow Piping Number Pipe S/N No.

Unit Configuration Of Tests WMP #2 1

cfs Straight Two series of seven flows WMP r3 4

cfs Straight (without Two series of six flows damping)

One series of one flow WMP

  1. 3 5

cfs Straight Two series of seven flows WdMP

  1. 3 6

lb§/hr Straight Two series of seven flows

Page 1 of 2 CALCULATIONS Actual Flow Rate q

W Lqa

=

ty1

.q = actual flow rate in cubic feet per second E

W

= weight of water accumulated during run in pounds t

= duration of run in seconds Ylia = specific weight of water in air at run temperature in pounds per cubic foot Note: See Appendix Temperature Correction -

(TC)

TC = 1 + 3 (u) (t - T)

-6 u = coefficient of thermal expansion = 6.5 x 10 T = temperature of meter section = 701F (during measurement of pipe dimensions) t = temperature of fluid during run -F L

Pressure Correction -

(PC)

PR LC 1 + (1-f-)

1 + (0.5-v)

IL th.E v = Poission's ratio = 0.3 E = modulus of elasticity = 3.0 x 107 th = pipe wall thickness = 0.5" R = pipe radius P = fluid pressure during run

Page 2 of 2 CALCULATIONS Total Correction Factor = (TC) (PC)

Mean Meter Factor = MF MF

=

Weigh Tank Average LEFM Flow Weigh Tank = ARL actual flow rate in cubic feet per second Average LEFM Flow = Qavg = N1 Q4sec N = number of LEFM samples during run Temperature and Pressure Corrected Mean Meter Factor - MF (T,P)

MF (T,P) = MF x TC x PC Standard Deviation - a%

N Q.

1 1i Qavg

~avg N-1 o

= standard deviation Qj= individual sampled LEFM flow

RESULTS The tabulated data and result sheets indicate the experimental testing information for the individual test points and the plot of temperature and pressure corrected mean meter factor (T,P) versus average flow rate show the trend of the coefficient over the flow range tested.

Since the flows were measured to the nearest ten pounds and the time to the nearest 0.001 second, the average flow rate for each run should be within +/-0.25% of the true value.

The Laboratory's standards for the measurement of temperature, time, weight and length are traceable to the National Bureau of Standards.

Ll LK.

L L

L.

!1E

F- -

r -

r r- -,--

r---

F---

r---

f----

I -

F-

~

r 4 1

I

.r

[-

n

- ~

I~ I.

- n -

page 1 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #2 DATE:

24 MAY 1979 Data includes 0.45% error due to path misplacement

--- WESTINGHOUSE DATA ARL DATA Test No.

Run No.

Line Temp OF Pressure Downstream psi

.Vlight W

lbs.

Time t

sec.

Flow q

cfs.-

Average LEFM Flow Mean Meter Factor Corrected Mean Meter Factor (T;P) 3 Sig %

First Series of Seven Flows 1

58 1

59 1

60 1

61 1

62 1

63 1

64 1

65 1

66 1

67 1

68 1

69 1

70 1

71 1i 72 1

73 1

74 96 96 96 96 96 96 96 96 96 96 96 96 96 96 96 96 97 40 40 40 40 40 40 48 48 48 48 48 54 54 54 54 57 57 97646 97526 97475 97414 97414 97434 96977 97150 97110 97039 97029 96521 96490 96460 96420 96156 96106 45.242 45.234

45. 176 45.189 45.183
45. 189 52.402 52.630 52.638
52. 637 52.646
63. 346
63. 400 63.429 63.510 77.704 77.695 34.838 34.802 34.;828 34.796 34.801 34.804 29.872 29.796 29.779 29.758 29.750
24. 595
24. 566
24. 547
24. 506 19.975 19.970 35.0448-35.0332 35.0382 35.0096 35.0040 34.9754-i 30.0342 29.9007 29.9106 29.8925 29.8725 24.6938 24.6523 24.6505 24.6316 20.0734 20.0623 0.9942 0.9935 0.9941 0.9939k>

0.9943 0.9952 0.9947 0.9966 0.9957 0.9956 0.9960 0.9961 0.9966 0.9959 0.9950 0.9952 0.9956 0.9941 0.9934 0.9940 0.9939 0.9942 0.9951 0.9946 0.9965 0.9956 0.9955 0.9959 0.9960 0.9965 0.9958 0.9949 0.9951 0.9954 0.463 0.429 0.361 0.511 0.373 0.563 0.641 0.649 0.569 0.545 0.471 0.348 0.635 0.573 0.566 0.753 0.798

r- -

ra i--- r--- o -, r--

rlo. -

r--

.r-,. f,.

( - - I -

, I.I.-I -I

, -11 I- -

 ;-I,-.

b-t a.

.1

-i Is A*

.;..6 Ybi&

.1-Jz1,9L-2, I.

I I

-,I F-F V

~

i I-,

xmw-4ft, WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 page 2 of 3 DATE:

24 MAY 1979 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #2 ARL DATA


WESTINGHOUSE DATA ------------

Test No.

Run No.

1 75 1

76 1

77 1

78 1

79 1

80 1

81 Line Temp OF 97 97 97 97 97 97 97 Pressure Downstream psi 57 60 60 60 60 60 60 Weight W

lbs.

95994 95801 95750 95527 75651 95548 88793 Time t

sec.

77.625 103. 865 104.694 104.708 122. 625 155.017 296.221 Flow q

cfs.

19.965 14.891 14.765

14. 729 9.960 9.951 4.839 Average LEFM Flow 20.0472 14.9538 14.8139 14.7941 9.9990 9.9960 4.8599 Mean Meter Factor 0.9960 0.9960 0.9969 0.9957 0.9962 0.9956 0.9958 Corrected Mean Meter Factor (T,P) 0.9959 0.9958 0.9967 0.9956 0.9961 0.9955 0.9957 3 Sig %

0.552 0.819 0.645 0.792 0.773 0.725 1.285 Second Series of Seven Flows 1

82 1

83 1

84 1

85 1

86 1

87 1

88 1

89 1

90 1

91 1

92 1

93 98 98 98 98 98 98 98 98 98 98 98 98 60 -

60 60 60 60 57 57 57 54 54 54 54 46901 85843 85712 95781" 95801 95963 95892 96054 96399 96379 96521 96440 156. 971 138.987 138.746 103. 726 103.778 77.513 77.430 77.550 62.655 62,708 62.859 62.790 4.825 9.973 9.976

14. 911 14.907 19.991 19.998 20.001 24.845 24.818 24.795 24.802 4.8571 10.0050 10.0100 14.9679 14.9459 20.0693 20.0743 20.0652 24.9248 24.9152 24.9021 24.9016 0.9935 0.9970 0.9968 0.9964 0.9975 0.9963 0.9964 0.9970 0.9969 0.9963 0.9958 0.9961 0.9934 0.9968 0.9966 0.9962
0. 9974 0.9961
0. 9962 0.9968 0.9968 0.9961 0.9957 0.9960 1.273 0.877 0.683 0.719 0.685 0.673 0.587 0.825 0.488 0.408

.0.469 0.662 Data includes 0.45% error due to path misplacement

-~

A

-r- -, -,

11 -.-I r

, I

'-* -f- ---

j- -- 11_1_r---_,J-,F--,,---F k-r

-~A,~LJ 1,4-

,,d64,

11,r I

page 3 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #2 DATE:

24 MAY 1979 ARL DATA WESTINGHOUSE DATA ------

Test No.

Run No.

1 94 1

95 1

96 1

97 1

98 1

99 1

100 1

101 1

102 1

103 1

104 Line Temp 9F 98 98 98.

98 98 99 99 99 99 99 99 Pressure Downstream psi 48 48 48 48 48 40 40 40 40 40 40 Weight W

lbs.

96775 97008 96755 96988 96846 97474 97231 97282 97272 97130 97322 Time t

sec.

52. 531 52.735 52.583 52.699 52.635 45.320
45. 223
45. 248 45.244 45.186
45. 266 Flow q

cfs.

29.748 29.705 29.713 29.719 29.711 34.738 34.725 34.724 34.724 34.718

34. 725 Average LEFM Flow 29.8495 29.8093 29.8353 29.8144 29.8273 34.8635 34.8715 34.8425 34.8425 34.8609 34.8330 Mean Meter Factor 0.9968 0.9966 0.9960 0.9969 0.9962 0.9965 0.9959 0.9968 0.9967 0.9961 0.9971 Corrected Mean Meter Factor (T,P) 0.9966 0.9965 0.9959 0.9968 0.9961 0.9964 0.9958 0.9966 0.9966 0.9959 0.9969 3 Sig %

0.451 0.712 0.517 0.671 0.666 0.629 0.497 0.523 0.506 0.354 0.456 WITNESSED AND ASSISTED BY CLIENT REPRESENTATIVES WITNESSED BY CONSOLIDATED EDISON REPRESENTATIVES ARL DATA CERTIFIED BY:

Data includes 0.45% error due to path misplacemefnt

_ _ _I- -

,-2 2X- --

U --.17716O

.11,1,0

.. 17 -

J -

xz X

i7I'77-[

ii m

ri UWMIt M

NS#S-it1m4SttEtSli P:

M o-

¢ P4 W: 0

¢ Z4

¢ C

......... W -

k g

i~

W g

I I..

gmlmI i

Data includes 0.45% error due to path misplacement mIS M n111nlfM 11I-1flWM0 I :tM 3Mi-TMWIMENIM1NSMINN 011-01111E

1. nrn_

~~~

1-1--

U U1

i.....

I................

1 11 111....I.....................~l l li il lsi il lil Il-r rlra rr 1 Ill I Ili Ill I § i 0.99-fit-fl-11t

--.~m o~

I... IiII.

IIII IIII : 4

.1111 1111 IIII 44Th1i4-fl-I fI I

,'14 HA itNiI1tIIH

i11, 1141M 1t 1+/-

I I

- I IIlulllmlllle+ee itl-1ttrtttt~t m1

-t-l td 1 t tdtd+

1-id tdI t d1-t1 11-

-i +i-i 4

I-J-U MA-M-i

-M 1. I-1-4 1ti oiifmi 10 20 30 AVERACE FLOW RATE -

q (efs) aVAS

' -a CERTIFIED BY:

TEST NUMBER 1 (3 -

First Series of Seven Flows CD-Second Series of Seven Flows INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #2 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042

MAY, JUNE 1979

I

-L--F

-~

r 7;

-r, F J

page 1 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT DATE:

23 MAY 1979 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 (WITHOUT DAMPING)

ARL DATA ------------------------


WESTINGHOUSE DATA -------------

Line Pressure Weight Time Flow Average Mean Corrected Test Run Temp Downstream W

t q

LEFM Meter Mean Meter No.

No.

OF psi lbs.

sec.

cfs.

Flow Factor Factor (T,P) 3 Sig %

First Series of Six Flows, 4

1 93 40 97434 45.582 34.484 34.8570 0.9893 0.9893 0.406 4

2 93 40 97525 45.631 34.479 34.8410 0.9896 0.9896 0.533 4

3 93 40 97384 45.586 34.484 34.8253 0.9902 0.9902 0.390 4

4 93 40 97616 45.707 34.454 34.7880 0.9904 0.9904 0.387 4

5 93 40 97555 45.706 34.433 34.7878 0.9898 0.9898 0.463 4

6 93 40 97535 45.681 34.445 34.7613 0.9910 0.9909 0.624 4

7 93 48 97010 53.008 29.524 29.8132 0.9903 0.9903 0.656 4

8 93 48 96839 52.985 29.485 29.8009 0.9895 0.9894 0.462 4

9 93 48 96899 53.062 29.460 29.7666 0.9898 0.9897 0.448 4

10 93 48 96869 53.044 29.461 29.7526 0.9902 0.9902 0.683 4

11 93 48 97000 53.100 29.470 29.7406 0.9909 0.9909 0.486 4

12 93 54 96464 63.204 24.622 24.8331 0.9915 0.9915-0.631 4

13 93 54 96414 63.340 24.556 24.7590 0.9918 0.9918 0.631 4

14 93 54 96212 63.268 24.533 24.7383 0.9917 0.9917 0.539 4

15 93 54 96333 63.394 24.515 24.7027 0.9925 0.9924 0.745 4

16 93 57 96101 78.194 19.827 20.0151 0.9907 0.9906 0.614 4

17 93 57 95969 78.173 19.805 19.9627 0.9921 0.9921 0.685 4

18 93 57 95898 78.066 19.817 19.9668 0.9925 0.9925 0.578 4

19 93 60 95586 104.746 14.722 14.8168 0.9936 0.9936 0.852 4

20 93 60 95495 105.159 14.650 14.7355 0.9942 0.9942 0.830 Data includes 0.45% error due to path misplacement I

'I rw b

F-----

-F-F A-

(( -

-W

--- 4 page 2 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 (WITHOUT DAMPING)

DATE:

23 MAY 1979

__--- ------------- -ARL DATA WESTINGHOUSE DATA ----------

Test Run No.

No.

Line Temp OF Pressure Downstream psi Weight W

lbs.

Flow t

sec.

Flow q

cfs.

Average LEFM Flow Mean Meter Factor Corrected Mean Meter Factor (T,P) 3 Sig %

4 21

.4 22 93 93 60 60 75459 75520 121. 115 121.293 10.051 10.044 10.1046

10. 1087 0.9948 0.9936 0.9947 0.9936 0.941 0.804 Second Series of Six Flows Data includes 0.45% error 4

23 4

24 4

25 4

26 4

27 4

28 4

29 4

30 4

31 4

32 4

33 4

34 4

35 4

36 4

37 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 60.

60 60 60 60 57 57 57 54 54 54 54 48 48 48

75515 75934 95487 95812 95578 95923 95984 96207 96328 96460 96298 96197 96846 96897 97059 121. 129 121.851 102.760 103.097 102.843 78.077 78.192 78.375 62.548 62.647
62. 547 62.455 52.846 52.926 53.044 10.057 10.053 14.991 14.992 14.993 19.820 19.803 19.803 24.822 24.840 24.838 24.848 29.564 29.535
29. 519
10. 1014 10.1167 15.1073
15. 1053 15.0972 19.9859 19.9788 19.9849 25.0500 25.0403 25.0408 25.0459 29.8174 29.7522 29.7511 due to path 0.9956 0.9938 0.9924 0.9925 0.9932 0.9918 0.9912 0.9910 0.9910 0.9921 0.9920 0.9922 0.9915 0.9927 0.9923 misplacement 0.9956 0.866 0.9937 0.713 0.9923 0.884 0.9925 0.954 0.9931 0.612 0.9917 0.746 0.9912 0.763 0.9909 0.772 0.9909 0.630 0.9920 0.736 0.9919 0.651 0.9921 0.660 0.9915 0.584 0.9927 0.448 0.9922 0.562 1

-k-k

---

near ir,

,*r. -I I--

l I

r

--.-I ESIHU I

CORPORATI WESTINGHOUSE ELECTRIC CORPORATION

-f~

-i pa, ge 3 of 3

page 3 of 3 PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 (WITHOUT DAMPING)

DATE:

23 MAY 1979 ARL DATA WESTINGHOUSE DATA Test Run No.

No.

Line Temp 0 F Pressure Downstream psi Weight W

lbs.

Time t

sec.

Flow q

cfs.

Average LEFM Flow Mean Meter Factor Corrected Mean Meter Factor (T,P) 3 Sig %

4 38 93 4

39 93 4

40 93 4

41 93 4

42 93 4

43 93 4

44 93 4

45 93 Third Series of One Flow 4

46 93 4

.47 93 4

48 93 4 8 48 40 40 40 40 40 40 96755 96917 97424 97323 97495 97475 97495 97434 52.848 52.938 45.114 45.046 45.141

45. 122 45.150
45. 103 29.536 29.535 34.838 34.855 34.843 34.850 34.836 34.850 29.7652 29.7582 35.0589 35.0972 35.0568 35.0886 35.0569 35.0674 0.9924 0.9926 0.9937

.0.9932 0.9939 0.9933 0.9937 0.9938 0.9923 0.9925 0.9937 0.9931 0.9939 0.9932 0.9937 0.9938 0.543 0.318 0.505 0.621 0.427 0.496 0.483 0.496 60 60 60 95680 95517 95568 104.489 104.600 105.411 14.772 14.732 14.626 14.8806 14.8269 14.7128 0.9928 0.9937

0.

9942 0.9927 0.9936

0.

q941 0.699 0.946 0.738 WITNESSED AND ASSISTED BY WITNESSED BY CONSOLIDATED CLIENT REPRESENTATIVES EDISON REPRESENTATIVES ARL DATA CERTIFI ED BY:

Data includes 0.45% error due to path misplacement

r4t- - -;

r1 >

F F

F 1--

F-V r-r~-

[---

r---

r-r-

r--

[--

r--

o ggt1 iI-lli1t1;

~

-~

ata includes 0.457. error 1

due to path misplacement U r4 M~O 10 20 30 AVERAGE FLOW RATE -

q (cfs)

TEST NUMBER 4 (without damping)

First Series of Six Flows CERTIFIED BY:

[ -

Second Series of Six Flows Third Series of One Flow-INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 MAY, JUNE 1979

-1

em! [

-, 1---

r --~ i -

r -

[.

I I

-~

F, f--

--', FV

[-

[7-f--

r----

w--; h 4

page 3 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 ARL DATA WESTINGHOUSE DATA Test Run No.

No.

Line Temp OF Pressure Downstream psi Weight W

lbs.

Time t

sec.

Flowv q

cfs.

Average LEFM Flow Mean Meter Factor Corrected Mean Meter Factor (T,P) 3 Sig %

5 34 5

35 5

36 5

37 5

38 5

39 5

40 5

41 5

42 5

43 5

44 5

45 5

46 106 106 106 107 107 107 107 107 107 107 107 107 107 58 58 48 48 48 48 48 42 42 42 42 42 42 96102 95986 96565 96555 96382 96351 96708 97104 96809 96789 97063 96849 97083

62. 157 62.085
52. 191 52.241
52. 140 52.176 52.338
45. 111 45.028 44.998
45. 166 45.044
45. 176 25.008 25.007 29.927 29.902 29.906 29.876 29.894 34.825 34.783 34.799 34.768, 34.785 34.767 24.9955 24.9945 29.9930 29.9799 30.0020 29.9389 29.9900 34.9228 34.8807 34.8583 34.8412 34.8617 34.8786 1.0008 1.0008
0. 9981 0.9978
0. 9971
0. 9982 0.9971 0.9975
0. 9975 0.9986
0. 9982 0.9981
0. 9971 1.0005 1.0005 0.9978 0.9974
0. 9968
0. 9979
0. 9968 0.9972 0.9972 0.9983
0. 9979 0.9978
0. 9968 0.338 0.698 0.366 0.695 0.554 0.472 0.776 0.402 0.550 0.413 0.466 0.438 0.643 WITNESSED AND ASSISTED BY-CLIENT WITNESSED BY CONSOLIDATED EDISON REPRESENTATIVES REPRESENTATIVES ARL DATA CERTIFIED BY:

'.2E-

i e ra[

Wrat r- '

re

[--a r---

r-F -1 r r--"-,

w--

I r" rum r

-- -r >-- f --

7-r FMT 1.01-m EH E-4 W

O A;C) 0<

m 1.00-0.9 W ~Z oz s

10 20 30 AVERAGE FLOWI RATE -

q (cfs)

TEST 11MBER 5 0 - First Series of Seven Flows E]-

Second Series of Seven Flows CERTIFIED BY:

i INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 MAY, JUNE 1979 1§Ž7ZIL

F--

I--,

I --

I

[--

FF-

>F.-

r f----

F--

[

r--,

F 7-F-,

r I-

?(

page 1 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 ARL DATA WESTINGHOUSE DATA Test Run No.

No.

Line Temp OF Pressure Downstream psi Weight W

lbs.

Time t

sec.

Flow (q) lbs/hr x 106 Average LEFM Flow Mean Meter Factor 3 Sig %

First Series of Seven Flows 6

47 6

48 6

49 6

50 6

51 6

52 6

53 6

54 6

55 6

56 6

57 6

58 6

59 6

60 6

61 6

62 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 42 42 42 42 42 42 48 48 48 48 48 58 58 58 58 58 97033 97206 96849 97033 96941 97113 96346 96484 96494 96524 96565 96077 96057 96117

.96097 95843 44.994 45.048 44.919 45.012 44.954 45.060 52.314 52.392 52.394 52.456 52.453 61.992 62.034 62.067 62.081 77.019 7.764 7.768,.

7.762 7.761 7.763 7.759 6.630

.6.630 6.630

6.

624 6.627 5.579 5.574' 5.575 5.572 4.480' 7.7866 7.7968 7.7908 7.7851

7.

7871 7.7839 6.6479 6.6413 6.6440 6.6340 6.6376

5.

5695 5.5684

5.

5639

5.

5648 4.4813 0.9974 0.9967 0.9966

0.

9972 0.9972 0.9971 0.9976 0.9987 0.9983 0.9988 0.9987 1.0020 1.0013 1.0024 1.0017 1.0000 0.631 0.447 0.674 0.655 0.573 0.524 0.700 0.495 0.728 0.719 0.535 0.768 0.868 0.727 0.660 0.849

-1 r-I--- --

F.-

-- I r--

rr-r-

I r--:

F---

rm rI---

r--

F-f7 C w ra page 2 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979 ARL DATA WESTINGHOUSE DATA Test Run No.

No.

6 63 6

64 6

65 6

66 6

67 6

68 6

69 Line Temp OF 109 109 109 109 109 109 109 Pressure Downstream psi 58 58 60 60 60 60 60 Weight W.

lbs.

95533 95620 95183 95163 95158 94979 -

94836 Time t

sec.

76.881 76.913 104.214 104.898 155. 157 154.917 313.642 Flow (q) lbs/hr x lob 4.473 4.476 3.288 3.266 2.208 2.207 1;089 Average LEFM Flow 4.4761 4.4760 3.2791 3.2585 2.2034 2.2077 1.1094 Mean Meter Factor 0.9997 1.0004 1.0031 1.0027 1.0024 1.0001 0.9820 3 Sig %

0.705 0.821 1.195 0.903 1.032 1.018 1.837 Second Series of Seven Flows 6

70 6

71 6

72 6

73 6

74 6

75 6

76 6

77 6

78 6

79 109 109 110 110 110 110 110 110 110 110 60 60 60 60 60 58 58 58 58 58 95856 95143 95000 95345 95295 95609 95659 95609 95925 95955 314.357 155. 383 155.052 103.177 103. 148 77.770 77.788 77.790 62.787 62.870 1.098 2.204 2.206 3.327 3.326 4.426 4.427 4.425 5.500-5.494

1.

1057 2.2053 2.2064

3.

3217 3.3200 4.4291 4.4283 4.4290 5.4879 5.4808

0.

9933 0.9997 1.0002

1.

0020 1.0022 0.9997 1.0001 0.9995 1.0026 1.0028 1.949 1.097 0.981 0.810 0.913 0.685 0.831 0.768 0.769 0.505

!&r7JL

rI I

r--

r--

re--

r r----. r -4 page 3 of 3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 DATE:

16 JUNE 1979


ARL DATA WESTINGHOUSE DATA Test Run No.

No.

Line Temp OF Pressure Downstream psi Weight W

lbs.

Time t

sec.

Flow (q) lbs/hr O x 106, Average LEFM Flow Mean Meter Factor 3 Sig %

6

'80 6

81 6

82 6

9 83 6

84

.6 85 6

86 6

87 6

88 6

89 6

90 6

91 6

92 110 110 110 110 110 110 110 110 110 110 110 110 110 58 58 48 48 48 48 48 42 t42 42 42 42 42 96006 95924 96524 96743 96524

96336, 96433 96951 96707 97022 96799 96951 97033 62.911 62.845 52.618 52.763 52.607 52.535 52.612
45. 135 45.048 45.210
45. 114 45.193 45.237 5.494 5.495,

6.603 6.601 6.605 6.601 6.599 7.733 7.728 7.726 7.724 7.721 7.722 5.4781 5.4835

6.

5974 6.6030 6.6030 6.6050 6.6036 7.7307 7.7249 7.7275

7.

7263 7.7241 7.7290

1.

0033 1.0025-1.0012 1.0001 1.0007 0.9998 0.9996 1.0007 1.0007 1.0002 1.0001 1.0000 0.9994 0.725 0.606 0.852 0.522 0.448 0.719 0.711 0.385 0.590 0.394 0.473 0.551 0.843 I

WITNESSED AND ASSISTED BY WITNESSED BY CONSOLIDATED CLIENT REPRESENTATIVES EDISON REPRESENTATIVES ARL DATA CERTIFIED BY:

1,

0,7 f-F-i rF7 F--- 

F- -

rem m} r.--m ru-row F--

r-F~---

r -

re m

1.01 0~

H C-,

W 1.00 0.99 0.98 I

I I

0 2

4 6

8 AVERAGE FLOW RATE - lbs/hr x 106 TEST NUMBER 6 0 - First Series of Seven Flows

[ -

Second Series of Seven Flows CERTIFIED BY:

INDIAN POINT 18" ULTRASONIC FLOWMETER SERIAL NUMBER WMP #3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 MAY, JUNE 1979

, zarn

APPENDIX

PHYSICAL CHARACTERISTIC OF WATER AND AIR AT ARL Sp Wt Water Sp Wt.Water Air at Temp in vacu Sp.Wt Air Same Temp Kin Vis lF lb/ft3 lb/ft3 lb/ft3 Sq Ft/Sec Sp.Wt.Wdter Sp.Wt.Water Air at Temp.

in vacu Sp.Wt.Air SameTemp.

Kin Vis aF lb/ft3 lb/ft3 lb/ft3 Sq. Ft/Sec.

32 62 3980 0 0807 33

.3998 0.0805 34

.4017 0.0804 35 62.4035 0.0802 36

.4040 0.0800 L37

.4046 0 0799 38

.4051 0.0797 39

.4057 0.0796 K

40 62.4062 0 0794 41

.4052 0.0792 42

.4041 0 0791 43

.4031 0.0789 L

44

.4020 P.0788 45 62.4010 0.0786 46

.3987 00784 47

.3963 00783 48

.3940 00781 49

.3916 0.0780 50 62.3893 00778 S 1

.3856 Q0777 52

.3819 G0775 53

.3783 00774 L

54

.3746 00772 55 62.3709 00771 56

.3660 Q0769 57

.3611 00768 1

58

.3562 00766 59

.3516 a00765 60 62.3464 00763 61 3404 0.0762 62-

.3345 00760 63

.3285 -

00759 64

.3226 G0757 1

65 62.3166 0.0756 L 66

.3096 0.0755 67

.3025 0.0753 L

68

.2955 0 0752 69

.2884 0.0750 70 62 2814 0.0749 71 2734 0.0748 72 2653 0.0746 L

.2573 0.0745 74

.2492 0.0743 75 62 2412 0 0742 76

.2322 0 0741 77

.223' 0 0739 78

.2143 0 0738 79

.2053 0.0736 62.3173

.3193

.3213 62.3233

.3240

.3247

.3254

.3261 62.3268

.3259

.3250

.3242

.3233 62 3224

.3202

.3 180

.3159

.3 137 62 3115

.3080

.3044

.3009

.2973 62.2938

.2891

.2843

.2796

.2748 62.2701

.2643

.2585

.25 26 2468 62 2410

.2341 2272

.2203

.2 134 62.2065

.1986

.1907

.18 28

.1749 62.1670

.1582 1493

.1405

.1316 1.9292 x 10 5 1.8933 1.8573 1.8214 1.7899 1.7585 1.7270 1 6956 1.6641 1.6367 1.6093 1 5819 1.5545 1.5271 1.5033 1 4795 1.4556 1.4318 1.4080 1.3871 1.3662 1.3452 1.3243 1.3034 1.2848 1.2662 1.2477 1 2291 1.2105 1.1942 1.1779 1 1615 1.1452 1.1289 1 1142 1.0995 1.0847 1.0700 1.0553 1.0421 1.0289 1.0156 1.0024 0.9892 0.9773 0.9654 0.9535 0 9416 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 Ill 112 113 114 115 116 117 118 119 120 121 122 123 124 125 62.1963 00735

.1864 Q0734

.1766 Q0732

.1667 0.0731

.1569 Q0729 62.1470 a0728

.1363 00727

.1255 00726

.1148 10724

.1040 010723 62.0933 0.0722

.0818 00721

.0702 0 0719

.0587 0 0718

.0471 00716 62.0356 0 0715

.0233 0 0714 62.0110 0.0713 61.9988 0 0711

.9865 0 0710 61.9742 0.0709

.9610 0 0708

.9478 0 0707

.9347 0 0705

.9215 0 0704 61.9083 0.0703

.8947 0 0702

.8812 0.0700

.8676 0.0699

.8541 0 0697 61.8405 00696

.8260 0 0695

.8115 0.0694

.7971 0.0692

.7826 0 0691 61.7681 0 0690

.7531 0.0689

.7381 0 0688

.7230 0 0686

.7080 0 0685 61.6930 0.0684

.6773 0.0683

.6615 0 0682

.6458 0 0681

.6300 0.0680 61.6143 0 0679 62.1228 0.9297 x 10'5

.1131 0.9189

.1034 0.9082

.0936 0.8974

.0839 0.8867 62.0742 Q8759

.0636 0 8661

.0530 0 8563

.04-23 0 8466

.0317 0.8368 62.0211 0.8270 62.0097 0.8181 61.9983 0.8091

.9869 0.8002

.9755 0 7912 61.9641 0.7823

.9519 0.7742

.9398 0.7661

.9276 0.7579

.9155 0.7498 61.9033 0.7417

.8902 0.7342

.8772' 0.7268

.8641 0.7193

.8511 0.7119 61.8380 0.7044

.8246 0.6976

.8112 0 6908

.7977 0 6839

.7843 0.6771 61.7709 0 6703

.7565 0.6640

.7422 0.6576

.7278 0.6513

.7135 0 6449 61.6991 0 6386 6842 0 6328

.6693 0 6270

.6544 0.6211

.6395 0.6153 61.6246 0.6095

.6090 0.6041

.5933 0.5987 5777 0.5934

.5620 0.5880 61.5464 0.5826 6-1-76

CALIBRATION INDIAN POINT TWO 18" ULTRASONIC FLOWMETERS SERIAL NUMBERS WMP #2, and WMP #3 WESTINGHOUSE ELECTRIC CORPORATION PURCHASE ORDER NUMBER 87GC-WJ-47042 MAY, JUNE 1979 - ARL NO. 106-79/C91 Certified By Albert G. Ferron George E. Hecker, Director ALDEN RESEARCH LABORATORY WORCESTER POLYTECHNIC INSTITUTE HOLDEN, MASSACHUSETTS 01520

SUMMARY

Two 18" Ultrasonic Flowmeters, Serial Numbers WMP #2 and WMP #3, were calibrated at the ALDEN RESEARCH LABORATORY of Worcester Polytechnic Institute for WESTINGHOUSE ELECTRIC CORPORATION under their Purchase Order Number 87GC-WJ-47042.

Both 18" ultrasonic flowmeters were calibrated using straight pipe configurations.

The details of the piping immediately upstream and downstream of the ultrasonic meters are shown on the piping diagram.

The results are presented in the form of a tabulated data sheet as well as a plot of the average temperature and pressure corrected mean meter factor (T,P) versus the average flow rate (q) in cubic feet per second or pounds per hour.

The flow meters were calibrated at seven flow rates ranging from 5 to 35 cubic feet per second, or 1 to 7.7 million pounds per hour.

Tests 1 and 4 in May, 1979 identified a scaling error of approximately 0.45% which was corrected for Tests 5 and 6 conducted in June, 1979.

The error was determined to be due to incorrect placement of the paths in the LEFM meter section.