Corrected Repair or Replacement Forms
ML030990528
Person / Time
Site: LaSalle  
Issue date: 03/28/2003
From: Barnes G
Exelon Generation Co, Exelon Nuclear
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML030990528 (7)


Text

ExeI n..

Exelon Generation Company, LLC LaSalle County Station 2601 North 21"Road Marseilles, IL 61341-9757 www exelon corp corn Nuclear March 28, 2003 10 CFR 50.55a(g)

United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 LaSalle County Station, Units 1 and 2 Facility Operating License Nos. NPF-11 and NPF-18 NRC Docket Nos. 50-373 and 50-374

Subject:

Corrected Repair or Replacement Forms

References:

(1)

Letter from Charles G. Pardee (EGC) to the United States Nuclear Regulatory Commission, "90 Day Post-Outage ISI Summary Report," dated February 20, 2001 (2)

Letter from George P. Barnes (EGC) to the United States Nuclear Regulatory Commission, "Post-Outage 90 Day Inservice Inspection (ISI) Summary Report,"

dated May 6, 2002 Exelon Generation Company (EGC), LLC in accordance with 10 CFR 50.55a(g), is required to maintain an Inservice Inspection Program in accordance with the requirements of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code. During a November 2002 American National Standards Institute N626.1 audit of ASME Code activities at LaSalle County Station, conducted by The Hartford Steam Boiler Inspection & Insurance Company of Connecticut, errors of omission were discovered on two ASME NIS-2, "Owners Report of Repair or Replacement," forms.

The errors involved the failure to note the use of ASME Code Case N-496-1, "Helical - Coil Threaded Inserts,Section XI, Division 1," on the NIS-2 form.

These errors have been documented in the LaSalle County Station Corrective Action Program.

The original NIS-2 forms were submitted within References (1) and (2) above. The purpose of this correspondence is to transmit the corrected NIS-2 forms. The use of Code Case N-496-1 is documented on the corrected forms in section 5(b).

0C

March 28, 2003 U.S. Nuclear Regulatory Commission Page 2 Should you have any questions concerning this letter, please contact Mr. Glen T. Kaegi, Regulatory Assurance Manager, at (815) 415-2800.

Respectfully, George P. Barnes Site Vice President LaSalle County Station Attachments: Form NIS-2, Owner's Report of Repair or Replacement - Unit 1 Form NIS-2, Owner's Report of Repair or Replacement - Unit 2 cc:

Regional Administrator - NRC Region IlIl NRC Senior Resident Inspector - LaSalle County Station

FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xl 1.

Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way, Kenneth Square, PA.. 19348 (Address)

Plant LaSalle County Nuclear Station UaLC ULIDUL Sheet I

of 2

99211207 Repair Organization, P.O. No., Job No., etc.

2.

Unit 1 3.

(Name) 2601 N. 21" Rd. Marseilles. II. 61341 (Address)

Work Performed by Mechanical Maintenance (Name)

Mechanical Maintenance (Address)

Type Code SymbolStamp.

Authorization No.

Expiration Date N/A N/A N/A 4.

5.

Identification of System (MS) Main Steam (a) Applicable Construction Code Sect III 19 71 Edition S72 Addenda, Code Cases 1567 & 1711 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements-I 9 89, No Ad, Code Cases N-496-1 Identfifatiofn nf rnmnnnants Rennired nr Rpn~ar-pd.i and Rpnhac-mPnt Cnmnonents Name of Name Mfrs. Ser.

Nat'l CRN Other Year Repaired ASME Code Component of No.

Bd.

No.

Identi-Built

Replaced, Stamped Mfr.

No.

fication Replacement (Yes or No)

SRV Valve AG N63790-00-0072 N/A NIA 99211207 Replaced N/A Crosby SRV Valve **

AG N63790-00-0017 N/A NIA Receipt #

Replacement N/A Crosby or N63790 70818 l_

0017 (Modified)

Disc Insert AG N93185-32-0003 N/A N/A Replaced NIA Crosby Disc Insert AG N97499-38-0065 N/A Receipt #

2001 Replacement NIA Crosby 70818

7.

Description of Work Class I Repair & Replacement.

Per N-5 Code Data Report on file at LaSalle County Station.

8.

Tests Conducted:

Hydrostatic I I Pneumatic I _ I Normal Operating Pressure I X I Other Visual Pressure 1034 psi Test Temp.

171 Deg. F

9.

Remarks Valve SN# N63790-00-0017 was refurbished at Wyle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached )

Receipt #70818 and installed as a replacement for SN# N63790-00-0072 under work order # 99211207. For the remainder of the Repaired. Replaced and Replacement items, see Form NIS-2 Supplemental Sheet on Pages 2 of 2.

Replacement SRV No. was modified due to Installation of a new flexi-disc seat design.

CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair & Replacement conforms to the rules of the ASME Code, Section Xi.

(repair or replacement)

Type Code Symbol Stamp NONE Certificate of Authorization No.

N/A Expiration Date NIA Signed t o

4 ISI Coordinator Date March 11

. 2003 Owner or Owner's Designee, Title 1

iF A

1l CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler Insp. & Ins. Co. of Connecticut have Inspected the components described in this Owner's Report during the period LI RO8 to LI R09 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

J H

i Commissions IL 1927 df Inspector's Signature National Board, State, Province, and Endorsements Date_

Y%/A kJ/ 1 2003 d

FORM NIS-2 SUPPLEMENTAL SHEET

1.

Owner:

Exelon Generation Company (EGC) LLC 200 Exelon Way, Kenneth Square, PA., 19348 Sheet Date Unit 2

of 2

02/25/02

_1

2.

Plant:

LaSalle County Station 2601 N. 21s5. Rd.

Marseilles, Illinois 61341 99211207 P. O. No., WR No., etc.

3.

Work Performed by: Mechanical Maint.

Name Mechanical Maintenance Address Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A

4.

Identification of System MS 5a.

Applicable Construction Code 71 Edition S72 Addenda 5b.

Applicable Edition of Section Xl utilized 89 Edition Is ---

Addenda I

lI.Wgv:

6.

Identification of Components Repaired or Replaced and Replacement Components.

Name of Name of Manufacturer National Other Year

Repaired, ASME Component Manufacturer Serial No.

Board Identification Built Replaced Code No.

or Stamped Replacement (Yes or No)

Valve Body AG Crosby N93183 N/A Receipt #

Repaired 0006 70818 Heli-Coil AG Crosby N97823-0030 N/A Receipt #

2001 Repaired N/A Insert 70818 (Outlet)

Heli-Coil AG Crosby N97823-0031 N/A Receipt #

2001 Repaired N/A Insert 70818 (Outlet)

Heli-Coil AG Crosby N97823-0032 N/A Receipt #

2001 Repaired NIA Insert 70818 (Outlet)

Heli-Coil AG Crosby N97823-0033 NIA Receipt #

2001 Repaired N/A Insert 70818 (Outlet)

(1) Inlet N/A Replaced NIA Stud (1) Inlet NOVA Heat Code N/A Receipt #

2000 Replacement N/A Stud PWG 47251 (12) Inlet NOVA N/A Replaced N/A Tension Nuts (12) Inlet NOVA Ht. Code N/A Receipt#

2001 Replacement N/A Tension C491 l

69812 1 I Nuts I

l

FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xl 1.

2.

3.

4.

5.

nwn--

fnommnn.annIth Frienn t~nmnm.

Date i1/22/00 v,

(Name)

One First National Plaza. Chicaqo. II.. 60690 (Address)

Plant LaSalle County Nuclear Station Sheet I

of 3

Unit 2 See Item 6 "Other Identification" Below Repair Organization, P.O. No., Job No., etc.

(Name) 2601 N. 21 Rd. Marseilles. II. 61341 (Address)

Work Performed by Mechanical Maintenance (Name)

Mechanical Maintenance Type Code Symbol Stamp Authorization No.

Expiration Date N/A NIA NIA (Address)

Identification of System (MS) Main Steam (a) Applicable Construction Code Sect III 19 71 Edition S72 Addenda, Code Cases 1567 & 1711 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements-1 9 89.

No Ad, Code Cases N-496-1 Identification of Comoonents Repaired or Replaced. and Replacement Comnonents 6.

Name of Name of Mfrs. Ser.

Nat'l CRN Other Year Repaired ASME Code Component Mfr.

No.

Bd.

No.

Identi-Built

Replaced, Stamped No.

fication Replacement (Yes or No)

SRV Valve Crosby N63790100-N/A N/A 990134813 Replaced N/A

_ _ _0 1 0 8 SRV Valve Crosby N63790 N/A N/A RIN #57935

=

Replacement N/A Spindle_

As s e m b l y C r os00 1 1 I_

R I N

  1. 5 9

3

. R e l a e d Nt Spindle Assembly Crosby K62873 N/A N/A RIN #57935 Replaced N/A Spindle Assembly Crosby K82137 N/A N/A RIN #57935 2000 Replacement N/A

_ _ _0 0 7 0 Disc Insert Crosby N93185 N/A N/A RIN #57935 Replaced N/A Disc Insert Crosby N93185 NIA N/A RIN #57935 2000 Replacement NIA

7.

Description of Work Class 1 Repair & Replacement.

  • Per N-5 Code Data Report on file at LaSalle County Station.
8.

Tests Conducted:

Hydrostatic I I

Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1030 psi Test Temp.

Amb.

Deg. F

9.

Remarks Valve SN# N63790-00-0011 was refurbished at Wyle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached )

Receipt Inspection #57935 and Installed as a replacement for SN# N63790-00-0108 under work request 990134813.

For the remainder of the Repaired, Replaced and Replacement items, see Form NIS-2 Supplemental Sheet on Pages2and 3of3 CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair & Replacement conforms to the rules of the ASME Code, Section Xl.

(repair or replacement)

Type Code Symbol Stamp NONE Certificate of Authorization No.

N/A Expiration Date N/A Sig ne

/

ISI Coordinator Date March 11

. 20 03 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler Insy. & Ins. Co. Of Hartford, CT. have inspected the components described in this Owner's Report during the period L2R07 to L2R08 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

4 t i/.

Commissions IL 1927 In Efctor's Signature ur*-A/t 20 03 National Board, State, Province, and Endorsements Date---,

1.

Owner:

2.

Plant:

FORM NIS-2 SUPPLEMENTAL SHEET Commonwealth Edison Company Sheet.

One First National Plaza Chicago, Illinois 60690 Unit LaSalle County Station 2601 N. 21st. Rd.

Marseilles, Illinois 61341 2

of 3

Date 11/22/00 2

990134813

3.

Work Performed by: Mechanical Maint.

Name Mechanical Maintenance Address

4.

Identification of System MS P. O. No., WR No., ets.

Type Code Symbol Stamp NIA Authorization No.

N/A Expiration Date N/A 5a.

5b.

6.

Applicable Construction Code 71 Edition Applicable Edition of Section Xi utilized 89 Edition _

Identification of Components Repaired or Replaced and S72 Addenda None Addenda Replacement Components.

Name of Name of Manufacturer National Other Year

Repaired, ASME Component Manufacturer Serial No.

Board Identification Built Replaced Code No.

or Stamped Replacement (Yes

_____or No)

Valve Body Crosby N93183 N/A RIN #57935 Repaired N/A 0056 Heli-Coil Crosby N97823-0019 NIA RIN #57935 1999 Repaired NIA Insert Heli-Coil Crosby N97823-0020 N/A RIN #57935 1999 Repaired N/A Insert Heli-Coil Crosby N97823-0021 N/A RIN #57935 1999 Repaired NIA Insert Heli-Coil Crosby N97823-0022 NIA RIN #57935 1999 Repaired NIA Insert Heli-Coil Crosby N97823-0023 N/A RIN #57935 1999 Repaired N/A Insert Heli-Coil Crosby N97823-0024 NIA RIN #57935 1999 Repaired N/A Insert Heli-Coil Crosby N97823-0025 NIA RIN #57935 1999 Repaired NIA Insert Heli-Coil Crosby N97823-0026 NIA RIN #57935 1999 Repaired NIA Insert

1.

Owner:

2.

Plant:

FORM NIS-2 SUPPLEMENTAL SHEET Commonwealth Edison Company Sheet One First National Plaza Chicago, Illinois 60690 Unit LaSalle County Station 2601 N. 2 1 st Rd.

Marseilles, Illinois 61341 3

of 3

Date 11/22/00 2

990134813

3.

Work Performed by: Mechanical Maint.

Name Mechanical Maintenance Address

5.

Identification of System MS P. 0. No., WR No., ets.

Type Code Symbol Stamp NIA Authorization No.

N/A Expiration Date N/A 5a.

5b.

7.

Applicable Construction Code 71 Edition S72 Addenda Applicable Edition of Section Xi utilized 89 Edition None Addenda Identification of Components Repaired or Replaced and Replacement Components.

Name of Name of Manufacturer National Other Year

Repaired, ASME Component Manufacturer Serial No.

Board Identification Built Replaced Code No.

or Stamped Replacement (Yes or No)

(10) Inlet Crosby N/A RIN #57935 Replaced N/A Studs (9) Inlet Nova Ht. Code NIA RIN #57935 1999 Replacement N/A Studs PWG (1) Inlet Crosby Ht. Code N/A 2B21-F013K 2000 Replacement N/A Stud VAW (12) Inlet Crosby N/A 2B21-F013K Replaced N/A Nuts (12) Inlet Nova Ht. Code TGD NIA 2B21-F013K 2000 Replacement N/A Nuts