ML030980674
| ML030980674 | |
| Person / Time | |
|---|---|
| Site: | Wolf Creek |
| Issue date: | 04/01/2003 |
| From: | Harris K Wolf Creek |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RA 03-0042 | |
| Download: ML030980674 (3) | |
Text
W0LF CREEK
'NUCLEAR OPERATING CORPORATION Karl A. (Tony) Harris Manager Regulatory Affairs APR 1 2003 RA 03-0042 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555
Subject:
Docket No.: 50-482: Changes to Wolf Creek Generating Station Radiological Emergency Response Data System Data Point Library Air Stability at the Reactor Site Gentlemen:
In accordance with 10 CFR 50, Appendix E, paragraph VI.3.a, this letter transmits changes to the Wolf Creek Generating Station (WCGS) Emergency Response Data System (ERDS) Data Point Library (DPL).- The parameter for determining stability class or air stability at the reactor site has been changed to use the vertical temperature difference between 10 and 60 meters versus the 10 to 85 meter vertical temperature difference. Emergency Response Data System point RDT0005 was deleted. Point RDT0004 was added for the vertical temperature difference between 10 and 60 meters.
The attachment to this letter updates the WCGS ERDS DPL and describes point RDT0004.
This change was implemented March 5, 2003.
There are no commitments identified in this correspondence.
If you have any questions concerning this matter, please contact me at (620) 364-4038, or Ms. Jennifer Yunk at (620) 364-4272.
Very truly yours, Karl A. (Tony) Harris RO Box 411 / Burlington, KS 66839 Phone (620) 364-8831 oc(>
An Equal Opportunity Employer M/F/HC/VET
RA 03-0042 Page 2 of 2 KAH/rig Attachment cc: J. N. Donohew (NRC), w/a -
D. N. Graves (NRC), w/a E. W. Merschoff (NRC), w/a Senior Resident Inspector (NRC), wla
Attachment to RA 03-0042 Page 1 of 1 ERDS DATA POINT LIBRARY REFERENCE FILE DATE: (8)
Reactor Unit: (3)
Data Feeder: (10)
NRC ERDS Parameter: (12)
Point ID: (12)
Plant Spec Point Desc: (40)
Generic/Cond Desc: (32)
Analog/Digital: (1)
Engr Units/Dig States: (12)
Engr Units Conversion: (40)
Minimum Instr Range: (10)
Maximum Instr Range: (10)
Zero Point
Reference:
(6)
Reference Point Notes: (40)
PROC or SENS: (1)
Number of Sensors: (3)
How Processed: (40)
Sensor Locations: (40)
Alarm/Trip Set Points: (40)
NI Detector Power Supply Cut-off Power Level: (15)
NI Detector Power Supply Turn-on Power Level: (15)
Instrument Failure Mode: (30)
Temperature Compensation For DP Transmitters: (1)
Level Reference Leg: (3)
Unique System Desc: (100) 03/05/03 WC1 N/A STAB CLASS RDT0004 CEL 60-10 M VERT TEMP DIFFERENCE AIR STABILITY AT THE RX SITE A
DEGC N/A
-4
+6 N/A N/A P
2 SUBTRACTION METEOROLOGICAL TOWER N/A N/A N/A Low=LOP N/A N/A TEMPERATURE DIFFERENCE BETWEEN 60 METER LEVEL AND 10 METER LEVEL IN DEGREES CELCIUS