April 3, 2003 LICENSEE:
Entergy Nuclear Operations, Inc.
FACILITY:
Indian Point Nuclear Generating Unit Nos. 2 and 3
SUBJECT:
SUMMARY
OF FEBRUARY 13, 2003, MEETING REGARDING PLANS FOR STRETCH POWER UPRATE PROJECTS On February 13, 2003, the U.S. Nuclear Regulatory Commission (NRC) staff held a meeting at its offices in Rockville, Maryland, with representatives from Entergy Nuclear Operations, Inc.,
the licensee for the Indian Point Nuclear Generating Unit Nos. 2 and 3 (IP2 and 3). The list of meeting attendees is included as Enclosure 1. Enclosures 2 is a copy of the slides presented at the meeting by the licensee. The presentations closely followed information presented in the slides.
The licensee presented information discussing the background and overview of its plans for power uprates for IP2 and 3 in 2004 and 2005, respectively. In these uprates, the licensee will attempt to match the power levels for both units while keeping the power level within the current maximum design for the station. The analyses to support the uprates will include a combination of new analyses and references to prior applicable analyses. The licensee also stated that it would integrate other plant betterment projects with the uprates such as high pressure turbine components and main power transformer cooling modifications.
With regards to the analysis methodology that would be used for each units uprate, the licensee discussed the codes and modeling. The licensee stated that for IP3 the analysis assumes the full application of alternate source term.
The licensee discussed their belief that Regulatory Issue Summary (RIS) 2002-03, "Guidance on the Content of Measurement Uncertainty Recapture Power Uprate Applications," dated January 31, 2002, should be used as guidance for the Indian Point power uprates. The licensee stated that many existing analyses will continue to bound proposed plant operation for power uprates. The staff stated that for such cases, the guidance in the RIS may be appropriate. However, the staff stated that the licensee also should consider past experience and requests for additional information related to recently completed stretch power uprates.
The staff is currently working on making this information available on the NRC's power uprate website (http://www.nrc.gov/reactors/operating/licensing/power-uprates). The information is currently available through ADAMS. In addition, the staff stated that the licensee should consider the guidance, scope of staff's review, and information expected in an application as discussed in the guidance found in Review Standard (RS)-001, "Review Standard for Extended Power Uprates," issued for interim use and public comment in December 2002. This is especially true for those areas that may not bounded by existing analyses of record. The staff acknowledged that the review standard is intended for larger power uprates than the licensee was planning to request for IP2 and 3 and, therefore, may not be directly applicable in all areas to the planned power uprates. The staff stated that it wants to see more detail in support of the accident analyses rather than general statements regarding the meeting of various regulations.
In addition, an application should include a description of the codes used in the analyses and whether the codes were previously approved by the staff.
/RA/
Patrick D. Milano, Senior Project Manager, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-247 and 50-286
Enclosures:
As stated cc w/encls: See next page to the planned power uprates. The staff stated that it wants to see more detail in support of the accident analyses rather than general statements regarding the meeting of various regulations.
In addition, an application should include a description of the codes used in the analyses and whether the codes were previously approved by the staff.
/RA/
Patrick D. Milano, Senior Project Manager, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-247 and 50-286
Enclosures:
As stated cc w/encls: See next page DISTRIBUTION:
PUBLIC PDI-1 Reading File S. Richards J. Wermeil R. Laufer F. Akstulewicz R. Caruso L. Raghavan P. Milano R. Landry S. Little L. Lois A. Attard F. Orr W. Lyon M. Shuaibi C. Sydnor T. McGinty, OEDO P. Eselgroth, RGN-I B. Platchek, RGN-I OGC ACRS DOCUMENT NAME: C:\\ORPCheckout\\FileNET\\ML030930103.wpd ADAMS Accession Number: ML030930103
- See previous concurrence OFFICE PDI-1:PM:
PDI-1:LA SRXB:SC*
SRXB:SC*
PDI-1:SC NAME PMilano SLittle RCaruso FAkstulewicz RLaufer DATE 04/02/03 04/2/03 03/26/03 03/30/03 04/2/03 Official Record Copy
Indian Point Nuclear Generating Unit Nos. 2 & 3 cc:
Mr. Jerry Yelverton Chief Executive Officer Entergy Operations 1340 Echelon Parkway Jackson, MS 39213 Mr. Michael R. Kansler Senior Vice President and Chief Operating Officer Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Fred Dacimo Vice President Operations Entergy Nuclear Operations, Inc.
Indian Point Nuclear Generating Units 1 & 2 295 Broadway, Suite 1 P.O. Box 249 Buchanan, NY 10511-0249 Mr. Dan Pace Vice President Engineering Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. James Knubel Vice President Operations Support Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Christopher J. Schwarz General Manager Operations Entergy Nuclear Operations, Inc.
Indian Point Nuclear Generating Unit 2 295 Broadway, Suite 1 P.O. Box 249 Buchanan, NY 10511-0249 Mr. Joseph DeRoy General Manager Operations Entergy Nuclear Operations, Inc.
Indian Point Nuclear Generating Unit 3 295 Broadway, Suite 3 P.O. Box 308 Buchanan, NY 10511-0308 Mr. John Kelly Director of Licensing Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Ms. Charlene Faison Manager, Licensing Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. John McCann Manager, Nuclear Safety and Licensing Indian Point Nuclear Generating Unit 2 Entergy Nuclear Operations, Inc.
295 Broadway, Suite 1 P.O. Box 249 Buchanan, NY 10511-0249 Mr. Harry P. Salmon, Jr.
Director of Oversight Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Thomas Walsh Secretary - NFSC Entergy Nuclear Operations, Inc.
Indian Point Nuclear Generating Unit 2 295 Broadway, Suite 1 P.O. Box 249 Buchanan, NY 10511-0249
Indian Point Nuclear Generating Unit Nos. 2 & 3 cc:
Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector, Indian Point 2 U. S. Nuclear Regulatory Commission 295 Broadway, Suite 1 P.O. Box 38 Buchanan, NY 10511-0038 Resident Inspectors Office, Indian Point 3 U.S. Nuclear Regulatory Commission 295 Broadway, Suite 3 P.O. Box 337 Buchanan, NY 10511-0337 Mr. John M. Fulton Assistant General Counsel Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Ms. Stacey Lousteau Treasury Department Entergy Services, Inc.
639 Loyola Avenue Mail Stop: L-ENT-15E New Orleans, LA 70113 Mr. William M. Flynn, President New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 Mr. J. Spath, Program Director New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 Mr. Paul Eddy Electric Division New York State Department of Public Service 3 Empire State Plaza, 10th Floor Albany, NY 12223 Mr. Charles Donaldson, Esquire Assistant Attorney General New York Department of Law 120 Broadway New York, NY 10271 Mr. Ronald Schwartz SRC Consultant 64 Walnut Drive Spring Lake Heights, NJ 07762 Mr. Ronald J. Toole SRC Consultant Toole Insight 605 West Horner Street Ebensburg, PA 15931 Mr. Charles W. Hehl SRC Consultant Charles Hehl, Inc.
1486 Matthew Lane Pottstown, PA 19465 Mayor, Village of Buchanan 236 Tate Avenue Buchanan, NY 10511 Mr. Ray Albanese Executive Chair Four County Nuclear Safety Committee Westchester County Fire Training Center 4 Dana Road Valhalla, NY 10592 Alex Matthiessen Executive Director Riverkeeper, Inc.
25 Wing & Wing Garrison, NY 10524 Paul Leventhal The Nuclear Control Institute 1000 Connecticut Avenue NW Suite 410 Washington, DC, 20036
Indian Point Nuclear Generating Unit Nos. 2 & 3 cc:
Karl Copeland Pace Environmental Litigation Clinic 78 No. Broadway White Plains, NY 10603 Jim Riccio Greenpeace 702 H Street, NW Suite 300 Washington, DC 20001
MEETING ATTENDEES CONSOLIDATED EDISON COMPANY OF NEW YORK, INC.
INDIAN POINT NUCLEAR GENERATING UNIT NO. 2 AND 3 FEBRUARY 13, 2003 NRC Staff:
Name Ralph Caruso Frank Akstulewicz Ralph Landry Frank Orr Warren Lyon Lambros Lois Anthony Attard Chris Sydnor L. Raghavan Mohammed Shuaibi Patrick Milano Title Section Chief Section Chief Sr. Reactor Engineer Reactor Engineer Sr. Reactor Systems Eng.
Sr. Nuclear Engineer Sr. Nuclear Engineer Materials Engineer Section Chief Sr. Project Manager Sr. Project Manager Organization NRR/Division of Systems Safety and Analysis (DSSA)/Reactor Systems Branch (SRXB)
NRR/DSSA/SRXB NRR/DSSA/SRXB NRR/DSSA/SRXB NRR/DSSA/SRXB NRR/Division of Engineering/
Materials and Chemical Engineering Branch NRR/Division of Licensing Project Management (DLPM)/Project Directorate I (PDIII)
NRR/DLPM/PDIII NRR/DLPM/PDI Entergy Nuclear Operations:
Name Charles Richardson David Morris Ardesar Irani Kevin Kingsley Walter Wittich Title Fleet Uprate Project Manager Manager, Power Uprates Supervisor, Nuclear Engineering NRR Project Manager Sr. Project Manager Westinghouse Electric Company:
Name Robert Laubham Charles Brinkman Robert Kemper James Sechrist Jill Monahan Title Certified Sr. Project Manager Director, Washington Operations Sr. Engineer Manager Project Manager Other
Participants:
None