SIEMENS Westinghouse March 20, 2003 Mr. Brian Benney Project Manager, Section 2 Project Directorate IV Division of Licensing Project Management Document Processing Center, Mail Stop 07E1 United States Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Siemens Westinghouse Power Corporation Topical Report Submittal, "Missile Probability Analysis of BB81/281 13.9m2,"
Dear Sir:
On March 5, 2003 Siemens Westinghouse submitted the above referenced Topical Report to the NRC for review and approval. You later contacted us to advise that the confidentiality statement at the bottom of each page of the report prevented the NRC from further processing the submittal. It was advised that we forward a letter to you releasing the NRC from this confidentiality agreement.
Accordingly, the purpose of this letter is to advise that Siemens Westinghouse releases the NRC from the confidentiality agreement so that they may proceed with the submittal process. Thus transmitting, reproduction, dissemination and/or editing of the submittal document within the NRC are acceptable.
We only ask that the submittal document not be released into the public domain. Thank you for contacting us on this matter.
- Regards, Peter Bird Field Service Engineering S326 Siemens Westinghouse Power Corporation Phone: (407) 736-4686 cc:
James McCracken S326 Jim Auman S326
SIEMENS Westinghouse March 5, 2003 Mr. Brian Benney Project Manager, Section 2 Project Directorate IV Division of Licensing Project Management Document Processing Center, Mail Stop 07E1 United States Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Siemens Westinghouse Power Corporation Topical Report Submittal, "Missile Probability Analysis of BB81/281 13.9m2 "
Dear Sir:
Missile probability analysis is presented for the Siemens 13.9m2 retrofit design of LP turbine (See ). These modern upgraded designs are used in various applications including replacement of Westinghouse original BB81 and BB281 nuclear LP rotors and internals.
Results of the P1 analysis indicate that the missile probabilities remain well below the Nuclear Regulatory Commission (NRC) limits of 1 E4 for a favorably oriented unit and 1 E-5 for an unfavorably oriented unit for up to 100,000 operating hours between disc inspections providing that no cracks are detected in the discs. Previously, in the Siemens submittal for the Limerick unit (See Enclosures 2 and 3), the NRC had approved the missile analysis methodology for 10 years, which is about 87,600 operating hours. The subject report justifies external missile probabilities out to 100,000 operating hours in comparison with the NRC limits.
We request NRC review and approval of the 100,000 operating hour inspection interval for Siemens LP retrofits with shrunk-on rotor discs and modern upgraded features as typically described for this 1 3.9m2 design.
I have mailed one copy of the reports to Document Processing Center and the second copy directly to Brian Benney. Should you have any questions or need for additional information, please contact the writer.
- Regards, Peter Bird Field Service Engineering S326 Siemens Westinghouse Power Corporation Siemens Westinghouse Power Corporation A Siemens Company 4400 Alafaya Trail Orlando, FL 32826-2399 NRC Topical Report.doc
SIEMENS Westinghouse Phone: (407) 736-4686
Enclosures:
- 1. "Missile Probability Analysis of BB81/281 13.9m2 ", by Dr. A. Bagaviev and P. Bird, February 26, 2003, CT-27332, Siemens Westinghouse Restrictive.
- 2. Letter from Mr. Bartholomew C. Buckley, NRC Senior Project Manager to Mr. George A. Hunger, Jr., PECO Energy Company Director of Licensing, dated February 3, 1998,
Subject:
Limerick Generating Station (LGS), Units 1 and 2 of Main Turbine Rotor Replacement, Extension of Turbine Rotor Inspection Intervals and Valve Testing Frequencies (TAC Nos. M99341 and M99342).
- 3. "Safety Evaluation of the Submittal to Replace Turbine Rotors at the Limerick Generating Station Units 1 and 2", NRC Docket Nos. 50-352 and 50-353.
cc:
James McCracken S326 Jim Auman S326 Andreas Feldmueller S327 Dr. Albert Bagaviev S321 Siemens Westinghouse Power Corporation A Siemens Company 4400 Alafaya Trail Orlando, FL 32826-2399 NRC Topical Report.doc