ML030870674
| ML030870674 | |
| Person / Time | |
|---|---|
| Site: | Point Beach (DPR-024, DPR-027) |
| Issue date: | 05/07/2002 |
| From: | Nuclear Management Co |
| To: | Office of Nuclear Reactor Regulation |
| References | |
| FOIA/PA-2003-0094 CAMP 701, Rev 17 | |
| Download: ML030870674 (6) | |
Text
f CAMP 701 SECONDARY SYSTEM AND WATER TREATMENT PLANT SAMPLE POINTS DOCUMENT TYPE:
CLASSIFICATION:
REVISION:
EFFECTIVE DATE:
REVIEWER:
APPROVAL AUTHORITY:
PROCEDURE OWNER (title):
OWNER GROUP:
Technical NNSR 17 May 7, 2002 N/A Manager of Chemistry Manager of Chemistry Chemistry Verified Current Copy:
Signature Date Time List pages used for Partial Performance Controlling Work Document Numbers C *.*"
POINT BEACH NUCLEAR PLANT CAMP 701 CHEMISTRY ANALYTICAL METHODS & PROCEDURES NNSR Revision 17 SECONDARY SYSTEM AND WATER TREATMENT May 7, 2002 PLANT SAMPLE POINTS 1.0 PURPOSE This procedure provides a list of approved sample points, their location, minimum purge volumes for secondary sample collection, and additional sampling guidance as appropriate for secondary water chemistry and water treatment.
2.0 PREREQUISITES Appropriate collection bottles 3.0 PRECAUTIONS AND LIMITATIONS NOTE:
Sample points not included in this procedure require Chemistry lab supervisor approval prior to use.
3.1 In certain instances, alternate sample points may be required to determine the effects, if any, of sample tubing runs.
3.2 Care should be taken when sampling at points other than the sample panels. These points "will not have gone through a heat exchanger and may be hot. They may also be under
, :pressure.
3.3 Sampling in the primary sample room requires the technician to work under a standing RWP. All steps shall be taken to comply with the standing RWP procedure (NP 4.2.21).
3.4 When samples have activity greater than 1.00 E-3 icilcc Beta/Gamma or, 1.00 E-3 vici/cc 1H3, the handling precautions of CAMP 602 shall be followed.
3.5 Secondary samples collected in the primary sample room are to be considered contaminated until verified not to be cofritaminated.
3.6 The discharge of sink sample hoses shall always be directed away from the sampler when first opening any sink sample valve.
3.7 Wear heavy gloves to protect hands from possible bums when obtaining steam generator blowdown filter outlet samples.
3.8 Samples for anion analysis may be grabbed on the discharge of a thoroughly flushed cation column if the cations present in the sample cause matrix problems.
3.9 Sampling and handling shall be done in accordance with NP 3.2.1.
REFERENCE USE Page 3 of 12
POINT BEACH NUCLEAR PLANT CAMP 701 CHEMISTRY ANALYTICAL METHODS & PROCEDURES NNSR Revision 17 SECONDARY SYSTEM AND WATER TREATMENT May 7, 2002 PLANT SAMPLE POINTS NOTE:
Steps 5.2.3 and 5.2.4 can be completed concurrently if sampling both steam generators.
5.2.3 IF sampling the A S/G in the Primary Sample Sink, THEN perform the following:
NOTE:
RE-219 might alarm in the control room due to low flow.
- a. Inform the control room that RE-219 might alarm due to low flow.
- b. Open SS-148 and SS-151.
- c. Purge the line per Attachment A for "A" Steam Generator Controlled Side Sample Room.
- d. Shut SS-148 and SS-151.
- e. Open SS-146 and SS-152.
- f. Collect appropriate sample volume.
- g. Shut SS-146 and SS-152.
- h. IF RE-219 alarmed, T-HEN contact the control room to see if you should reset the alarm.
5.2.4 IF sampling the B S/G in the Primary Sample Sink, THEN perform the following:
NOTE:
RE-219 might alarm in the control room due to low flow.
- a. Inform the control room that RE-219 might alarm due to low flow.
- b. Open SS-149 and SS-151.
- c. Purge the line per Attachment A for "A" Steam Generator Controlled Side Sample Room.
- d. Shut SS-149 and SS-151.
- e. Open SS-147 and SS-153.
- f. Collect appropriate sample volume.
g, Shut SS-147 and SS-153.
REFERENCE USE Page 5 of 12
POINT BEACH NUCLEAR PLANT CHEMISTRY ANALYTICAL METHODS & PROCEDURES SECONDARY SYSTEM AND WATER TREATMENT PLANT SAMPLE POINTS CAMP 701 NNSR Revision 17 May 7, 2002 Unit 1 Grab Samples Sample Valve Number Location Min. Purge Volume (ml) 4 Condensate Pump Discharge Steam Generator Feed Pump Suction 5B Feedwater Heater Outlet4 Heater Drain Tank Atixiliary Feed Main Steam Hotwell 1. 2, 3, 4 ISS-68 1TSS-69 ISS-70 ISS-71 lSS-72 ISS-73 1CS84F 1CS84G "A" Steam Generator5 IFI-4251A "B" Steam Generatorj 1FI-4253A "A" Steam Generator "B" Steam Generator L
Steam Generator Blowdown Filter Out Steam Generator Blowdown Filter Inlet Steam Generator Blowdown Filter Inlet Radwaste Steam Condensate Return 1SS-152 ISS-153 Sample Panel lUrbine a-lal 8 Sample Panel
-Turbine Hall 8' I _________________________________________
137OO
Sample Panel Turbine Hal] 8' Sample Panel Turbine Hall 8' Sample Panel Turbine Hall 8' Sample Panel Turbine Hall 8'
-Sample Panel Turbine Hall 81 8' Level U1 Turbine Hall SGBD Panel Turbine Hall 8' SGBD Panel Turbine Hall 8' U1 Controlled Side Sample Room U1 Controlled Side Sample Room Aux. Bldg-8" Level South Aux. Bldg. 8' Level South Aux. Bldg. 8" Level South 8' U1I Turbine Hall 11100' 8500' 8800i 4000' 36300' 3200' N/A 145000 137000' 3W 3W 200 1700 1600 2300 Samples that have continuous flow.
Minimum purge volume when there is continuous flow through FI-04251A (minimum purge volume when NOT continuous is 72900mn).
3 Minimum purge volume when there is continuous flow through FI-04253A (minimum purge volume when NOT continuous is 65900 ml).
Integrated samples for condensate pump discharge, 5B feedwater heater outlet, and heater drain tank are taken from ISS-38, 1SS-40, and ISS-41, respectively.
5 Anion samples for SGIA and SGIB are taken from 1FI-4251C and IFI-4253C, respectively.
REFERENCE USE
-,...i' Page 7 of 12 ATTACHMENT A TABLE OF PURGE VOLUMES FOR SECONDARY SYSTEM NOTE:
Hotwell conductivity verification to be sampled at outlet of installed conductivity cell.
JK/K/*
111001 13700W I-MS-310 I-MS-302 I-MS-306 RW-7
POINT BEACH NUCLEAR PLANT CAMP 701 CHEMISTRY ANALYTICAL METHODS & PROCEDURES NNSR Revision 17 SECONDARY SYSTEM AND WATER TREATMENT May 7, 2002 PLANT SAMPLE POINTS ATTACHMENT B TABLE OF COMMON GRAB SAMPLES FOR SECONDARY SYSTEM Sample Valve Number Location Min. Purge Volume (ml)
"A" Condensate Storage Tank AF-13B 26' Turbine Hall 100 "B" Condensate Storage Tank AF-14B 26' Turbine Hall 100 Heating Boiler Feed/Condensate AF-68B 8' U2 Turbine Hall 300 (SW corner)
"A" House Heating Boiler HV-757 26' U2 Turbine Hall 600 "B" House Heating Boiler HV-771 26' U2 Turbine Hall 1000 1P29 Auxiliary Feed Pump Suction 1AF25 8' Level Turbine Hall 100 IP29 Auxiliary Feed Pump Leakoff Local 8' Level Turbine Hall 900g P38A Auxiliary Feed Pump Suction AF38 8' Level Turbine Hall 100 P38A Auxiliary Feed Pump-Leakoff Local 8' Level Turbine Hall 900' P38B Auxiliary Feed Pump Suction AF51 8' Level Turbine Hall -
100 P38B Auxiliary Feed Pump Leakoff Local 8' Level Turbine Hall 1500' 2P29 Auxiliary Feed Pump Suction 2AF63 8' Level Turbine Hall 100 2P29 Auxiliary Feed Pump Leakoff Local 8' Level Turbine Hall 900g Unit 1 Service Water Overboard SW-146H 8' Level Ul Control Side 5007 Unit 2 Service Water Overboard SW-104H 8' Level Turbine Hall 500W Samples that have a continuous drip or flow.
2 Minimum purge volume when service water return header pump is running (minimum purge volume when NOT running is 3000 ml).
3 Minimum purge volume when service water return header pump is running (minimum purge volume when NOT running is 9800 ml).
C REFERENCE USE St I
Page 9 of 12
POINT BEACH NUCLEAR PLANT CHEMISTRY ANALYTICAL METHODS & PROCEDURES SECONDARY SYSTEM AND WATER TREATMENT PT ANT SAMPLE:: POINTS CAMP 701 NNSR Revision 17 May 7, 2002
- 1.-
ATTACHMENT C WATER TREATMENT GRAB SAMPLES (continued)
Sample Valve Number Location Root Min. Purge Valve Volume(ml)
"C" Reverse Osmosis Feedwater WT-651C U2 TH 8'/U17C WT-650C 100 "C" Manual Feedwater SDI Sample WT-654C U2 TH 8'/U17C WT-650C 200 F-225C First Stage "A" Membrane Outlet WT-665C U2 TH 8'/U17C WT-650C 100 F-226C First Stage "B" Membrane Outlet WT-666C U2 TH 8"/UI7C WT-650C 100 F-227C First Stage "C" Membrane Outlet WT-667C U2 TH 8'IUI7C WT-650C 100 F-228C Second Stage "A" Membrane WT-668C U2TH 8'IU17C WT-650C 100 Outlet F-229C Second Stage "B" Membrane WT-669C U2 TH 8'/U17C WT-650C 100 Outlet F-230C Third Stage "A" Membrane Outlet WT-670C U2 TH 8'/U17C WT-650C 100 F-231C Third Stage "B" Membrane Outlet WT-671C U2 TH 8'1U17C WT-650C 100 F-232C Fourth Stage "A" Membrane Outlet WT-672C U2 TH 8'/UI7C WT-650C 100 F-233C Fourth Stage "B" Membrane Outlet WT-673C U2 TH 8'/U17C WT-650C 100 "C" Reverse Osmosis Product WT-662C U2 TH 8'/U 17C WT-650C 100 "C" Reverse Osmosis Reject WT-660C U2 TH 8'IU17C WT-650C 100 "A" Cation Inlet WT-303A U10A WT-300A 100 "B" Cation Inlet WT-303B U10B WT-300B 100 "C" Cation Inlet WT-303C U10C WT-300C 100 "A" Cation Outlet FI-9354A WT Sample Panel WT 312A 16000 "B" Cation Outlet FI-9354B WT Sample Panel WT 312B 14500 "C' Cation Outlet FI-9354C WT Sample Panel WT 312C 13000 Deaerator Outlet 2 "A" Anion Inlet WT 403A U14A WT 402A 600 "B" Anion Inlet WT403B U14B WT 402B 600 "C" Anion Inlet WT403C U14C WT 402C 600 "A" Anion 2/3 FI-9363A WT Sample Panel WT 413A 15400 "B" Anion 2/3 FI-9363B WT Sample Panel WT413B 15100 "C" Anion 2/3 FI-9363C WT Sample Panel WT 413C 16500 "A" Anion Outlet FI-9369A WT Sample Panel WT 412A 14200 "B" Anion Outlet FI-9369B WT Sample Panel WT 412B 13900 "C" Anion Outlet FI-9369C WT Sample Panel WT 412C 15300 "A" Mixed Bed Outlet FI-9378A WT Sample Panel WT512A 9200 "B" Mixed Bed Outlet FI-9378B WT Sampe Panel WT'512B 9200 Water Treatment Reverse Osmosis Reject WT-688 U2 TH 8' Sample WT-687 14000 Panel Neutralizing Tank Sample WT-58 WT Bench Sink WT-57 500 2 Sample the deaerator outlet at the online anion inlet listed below.
REFERENCE USE Page I1I of 12