ML030770338

From kanterella
Jump to navigation Jump to search
CAP029261, Appendix R Classification Discrepancies in AFW Common Recirc Line
ML030770338
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 09/10/2002
From: Chapman R
Nuclear Management Co
To:
Office of Nuclear Reactor Regulation
References
CAP029261, FOIA/PA-2003-0094
Download: ML030770338 (1)


Text

TeamrackRepots Pge lofI SECTION 1 Activity Request Id:

Activity Type:

41 One Line

Description:

IN Detailed

Description:

CAP029261 CAP Submit Date:

9/10/2002 4:39.06 PM Appendix R Classification Discrepancies in AFW Common Recirc Line 9/10/2002 4:39.06 PM - ROB CHAPMAN:

MR 02-029 is upgrading the AFW Mini-recirc AOVs (1/2AF-4002, AF-4007, AF-4014) to have a safety function to open to provide flow for pump cooling As part of this upgrade, it was decided to keep the existing safety related boundary at the flow restricting orifices. All piping downstream of these orifices to the CSTs will not be classified as safety related, but will be required to be inservice for AFW pump operability per revised Tech Spec Bases B 3.7.5..

However, this common recirc piping is currently identified on Appendix R drawing APPRM-217 Sh. 1 as being a hot shutdown flowpath. This introduces an inconsistency with how this recirc line is classified, since the function of the recirc line in the Appendix R scenario is identical to the safety-related function. If the line is not safety-related to support AFW pump cooling, then the line should not be augmented quality for Appendix R (QA code 20) to support the same function.

Initiator.

Date/Time of Discovery:

Identified By:

Equipment # (1st):

Equipment # (2nd):

Equipment # (3rd):

Site/Unit:

Why did this occur?:

CHAPMAN, ROB 9/10/2002 4:22:19 PM Site-identified (None)

(None)

(None)

Initiator Department:

Date/Time of Occurrence:

System:

Equipment Type (1st):

Equipment Type (2nd):

Equipment Type (3rd):

EDMP Engineeri*gDesign Mechanical PB In 9/10/2002 4:22:19 PM AF PB (None)

(None)

(None)

Point Beach Common 9/10/2002 4:39:06 PM - ROB CHAPMAN:

Unknown Immediate Action Taken: 9/11/2002 2:12:08 AM - RON HARPER:

None Recommendations:

Ni Notify Me During Eval?:

9/10/2002 4:39:06 PM - ROB CHAPMAN.

Revise APPRM-217 Sh. 1 and CHAMPS to eliminate the Appendix R classification of this common recirc line downstream of the flow restricting orifices.

Y SECTION 2 Operability Status:

NA Basis for Operability:

9/

N Z Unplanned TSAC Entry:

N 0l SRO Review Required?:

.6 Compensatory Actions:

11/2002 2:12:08 AM - RON HARPER:

ot an equipment operability issue.

0 External Notification:

Y N

N SECTION 3 Screened?:

INPO OE Reqd?:

N N

0i QA/Nuclear Oversight?:

N Good Catch/Well Doc'd?: NA SSignificance Level:

Potential MRFF?:

0 Licensing Review?:

https:H//nmc.ttrackonline.com/tmtrack/tmtrack.dll?ReportPage&Template=reports/rptexec&l...

9/11/2002 (None)

N N

TeamTrack Reports Page 10 of 18