ML030660213

From kanterella
Jump to navigation Jump to search
Permit 001854, Unauthorized Discharge Notification
ML030660213
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 02/28/2003
From: Johnson G, Kelley J
TXU Electric
To: Espino F
Office of Nuclear Reactor Regulation, State of TX, Commission on Environmental Quality
References
001854, 223, TXX 03054
Download: ML030660213 (3)


Text

TXU TXU Electric P.O. Box 1002 Glen Rose. TX 76043-1002 Tel-254 897 5202 Fax. 254 897 6652 ikelley@txu corn James J. Kelley Jr.

Vice President February 28, 2003 Certified Mail 7000 0600 0025 0812 8548 File #223 TXX #03054 Mr. Frank Espino, Director Texas Commision on Environmental Quality Region 4 2301 Gravel Dr.

Fort Worth, TX 76118-6951 Attn.: Ms. Carrie Landrum Environmental Investigator Comanche Peak Steam Electric Station TPDES Permit #001854 Unauthorized Discharge Notification

Dear Ms. Landrum:

This letter is provided as a follow-up to the voicemail originally left for Ms. Shannon Kennedy 26 February 2003, 09:15 hours, and the follow-up notification conversation with Ms. Jan Malone, 27 February 2003 concerning the release of fire protection water from the above referenced facility to Squaw Creek Reservoir. The following information is provided concerning this release:

Date/Time:

Release Source:

02/25/2003, 17:05 - 19:02 hours. This is the automatically logged run time of a fire water pump in response to the loss of water from the system; A single sprinkler head malfunctioned and was activated in an unoccupied on-site storage building, flooding a portion of the building, and draining off to Squaw Creek Reservoir;

Ms. Carrie Landrum TCEQ, Region 4 Page 2 Release

Description:

Cause:

Corrective Actions:

Estimated 8,000 to 9,000 gallons may have reached Squaw Creek Reservoir. Firewater tank drawdown indicated a loss of 11,500 gallons. Estimate is based upon this value minus an estimate of water contained in the building. The water in the fire protection system is normally maintained with an approximate concentration of the biocide, Bulab 6002 (CAS #31075-24-8), of 50 mg/L as product.

This biocide does not contain any components or substances listed by SARA 302, SARA 313, CERCLA, RCRA, or the CWA. There were no dead or stressed fish identified in subsequent inspections of the reservoir in the vicinity of the release.

The preliminary cause determination is that the sprinkler head may have inadvertently activated due to freezing.

Immediate response was to isolate the fire protection water to this building, and repair leak.

A root cause analysis is currently in progress.

If you require additional information, please contact Mr. David Rutledge at 214/812-8477 or by e-mail at d.rutledge(di-txu.com.

Sincerely, James J. Kelley, Jr.

By: Gerald R.

DER

xc:

U. S. Nuclear Regulatory Commission ATTN:Document Control Desk Washington, D.C. 20555 Certified Mail 7000 0600 0025 0812 8531 Mr. David Jaffe U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation One White Flint North 11555 Rockville Pike MS O-7D1 Rockville, MD 20852 Certified Mail: 7000 0600 0025 0812 8524