AFW System 3.7.5 3.7 PLANT SYSTEMS 3.7.5 Auxiliary Feedwater (AFW)
LCO 3.7.5 The AFW System shall be OPERABLE with; one turbine driven AFW pump system and two motor driven AFW pump systems.
NOTE----------------------
Only the motor driven AFW pump systems associated with steam generators relied upon for heat removal are required to be OPERABLE in MODE 4.
APPLICABILITY:
MODES 1, 2, and 3, MODE 4 when steam generator is relied upon for heat removal.
ACTIONS CONDITION REQUIRED ACTION COMPLETION'iME A.
One steam supply to A.1 Restore steam supply to 7 days turbine driven AFW pump OPERABLE status.
system inoperable.
AND 10 days from discovery of failure to meet the LCO B.
One turbine driven AFW B.1 Restore turbind driven 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> pump system inoperable AFW pump system to in MODE 1, 2 or 3 for OPERABLE status.
AND reasons other than Condition A.
10 days from discovery of failure to meet the LCO (continued)
Point Beach 3.7.5-1 SUnit 1 - Amendment No. 201 Unit 2 - Amendment No. 206
AFW System 3.7.5 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETIONTIME C.
One motor driven AFW C.1 Restore motor driven 7 days pump system inoperable AFW pump system to in MODE 1, 2 or 3.
OPERABLE status.
AND 10 days from discovery of failure to meet the LCO D.
Required Action and D.1
NOTE -----------
associated Completion Each unit may be Time for Condition A, B,..
sequentially placed in or C not met.
MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when both units are in OR Condition D concurrently.
Two AFW pump systems inoperable in MODE 1, 2, or 3.
Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND D.2 NOTE -----------
Entry into MODE 4 is not required unless one motor driven AFW pump system is OPERABLE.
Be in MODE 4.
18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> (continued)
Point Beach 3.7.5-2 Unit 1 - Amendment No. 201 Unit 2 - Amendment No. 206
AFW System 3.7.5 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME E.
Three AFW pump E.1A
NOTE -----------
systems inoperable in LCO 3.0.3 and all other MODE 1, 2, or 3.
LCO Required Actions requiring MODE changes are suspended until one AFW pump system is restored to OPERABLE status.
Initiate action to restore Immediately one AFW pump system to OPERABLE status.
F.
One or more required F.1 Initiate action to restore Immediately AFW pump systems AFW pump system(s) to inoperable in MODE 4.
OPERABLE status.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.5.1 NOTE --------------------------
AFW pump system(s) may be considered OPERABLE during alignment and operation for steam generator level control, if it is capable of being manually realigned to the AFW m6de of operation.
Verify each AFW manual, power operated, and 31 days automatic valve in each water flow path, and in both steam supply flow paths to the steam turbine driven pump, that is not locked, sealed, or otherwise secured in position, is in the correct position.
(continued)
Point Beach 3.7.5-3 Unit 1 - Amendment No. 201 Unit 2 - Amendment No. 206