Feb.

07, 2003 Page 1

of 1 MANUAL HARD COPY DISTRIBUTION DOCUMENT TRANSMITTAL 2003-6 89 USER INFORMATION:

CA#:

0363

-U--

TRANSMITTAL INFORMATION:

02/07/2003 LOCATION:

DOCUMENT CONTROL DESK FROM:

NUCLEAR RECORDS DOCUMENT CONTROL CENTER

'NUCSA-2)

\\,_iHE FOLLOWING CHANGES HAVE OCCURRED TO THE HARDCOPY OR ELECTRONIC MANUAL ASSIGNED TO YOU:

134 -

HEALTH PHYSICS RADIOMAN:

EMERGENCY PLAN POSTION SPECIFIC INSTRUCTION REMOVE MANUAL TABLE OF CONTENTS DATE:

08/22/2002 ADD MANUAL TABLE OF CONTENTS DATE:

02/06/2003 CATEGORY:

PROCEDURES TYPE:

EP ID:

EP-PS-134 REPLACE:

REV:O REPLACE:

REV:0 REMOVE:

PCAF 2002-1551 REV:

N/A ADD:

PCAF 2002-1551 REV:

N/A UPDATES FOR HARD COPY MANUALS WILL BE DISTRIBUTED WITHIN 5 DAYS IN ACCORDANCE WITH DEPARTMENT PROCEDURES.

PLEASE MAKE ALL CHANGES AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX UPON RECEIPT OF HARD COPY.

FOR ELECTRONIC MANUAL USERS, ELECTRONICALLY REVIEW THE APPROPRIATE DOCUMENTS AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX.

'ro e

\\/ý

Tab 2 EP-PS-134-2 CALCULATION AND TRACKING SHEET FOR ESTIMATED IODINE CDE AND TEDE DOSES USE THIS FORM:

1.

When the iodine CDE dose rate at a team sampling location exceeds 1,000 mrem/hr.

(1,200 cpm frisker).

OR

2.

As directed by the TSC Dose Calculator or the DAST.

Methodology:

1.

Initiate this form. Identify the affected team and the highest year-to-date (YTD) dose for any individual on the team.

2.

Enter the time, current SRD dose and iodine to gamma ratio (I/7). (Note: Iodine to gamma ratio can be obtained from the RMS Emergency Field Monitoring Secondary Data Report.)

The highest ratio obtained since tracking was initiated should be used (obtain from previously printed reports).

NOTE:

If the SRD dose is less than 10 mrem enter "<10" in the SRD Dose Field, multiply the I/y times 10 and enter the CDE and TEDE doses as < dose value.

3.

Calculate the iodine CDE:

SRD x 1/y = CDE (mrem)

4.

Calculate TEDE:

ODE x 0.03 + SRD + (YTD) = TEDE (mrem)

5.

Notify the TSC Dose Calculator or DAST immediately and pull the team to a low background area if any member of a team reaches or exceeds the following:

TEDE = 3800 mrem CDE = 10,000 mrem TEAM:

Year-to-Date (YTD) Dose:

EP-AD-000-084, Revision 4, Page 1 of 1 Iodine/gamma Iodine CDE TEDE Date/Time SRD Dose(mrem)

Ratio (I/y)

(mrem)

(mrem) 1-4 4

4 1-4 4

4

+

4 4

A

+

4 4

4 A ___________________

I ___________________